Hinen · Solar inverter
H5000 / H5000-EU hybrid inverter (protocol V1.62 also lists off-grid, C&I ESS and on-grid device types) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 1 | Inverter running status 0x00:standby mode 0x01:Grid-connected state 0x02:Off-grid state 0x03:fault state 0x04:update mode 0x05:charging state 0x06:discharging state 0x07:bypass state | UInt16 | - | 1 | R |
| 1 | 2 | Total PV input power 32-bit value: high word at 1, low word at 2. | UInt32 | W | 0.1 | R |
| 3 | 1 | PV1 voltage | UInt16 | V | 0.1 | R |
| 4 | 1 | PV1 input current | UInt16 | A | 0.1 | R |
| 6 | 2 | PV1 Input power 32-bit value: high word at 6, low word at 7. | UInt32 | W | 0.1 | R |
| 8 | 1 | PV2 voltage | UInt16 | V | 0.1 | R |
| 9 | 1 | PV2 input current | UInt16 | A | 0.1 | R |
| 11 | 2 | PV2 Input power 32-bit value: high word at 11, low word at 12. | UInt32 | W | 0.1 | R |
| 13 | 1 | PV3 voltage | UInt16 | V | 0.1 | R |
| 14 | 1 | PV3 input current | UInt16 | A | 0.1 | R |
| 16 | 2 | PV3 Input power 32-bit value: high word at 16, low word at 17. | UInt32 | W | 0.1 | R |
| 18 | 1 | PV4 Voltage | UInt16 | V | 0.1 | R |
| 19 | 1 | PV4 input current | UInt16 | A | 0.1 | R |
| 21 | 2 | PV4 Input power 32-bit value: high word at 21, low word at 22. | UInt32 | W | 0.1 | R |
| 23 | 2 | Total AC apparent power total AC apparent power of inverter 32-bit value: high word at 23, low word at 24. | Int32 | VA | 0.1 | R |
| 25 | 2 | Total AC active power total AC active power of inverter 32-bit value: high word at 25, low word at 26. | Int32 | W | 0.1 | R |
| 27 | 2 | Total AC reactive power total AC reactive power of inverter 32-bit value: high word at 27, low word at 28. | Int32 | var | 0.1 | R |
| 29 | 1 | R-phase grid voltage | UInt16 | V | 0.1 | R |
| 30 | 1 | R-phase grid current Meter current or CT current | Int16 | A | 0.1 | R |
| 31 | 2 | R-phase apparent power R-phase apparent power of inverter 32-bit value: high word at 31, low word at 32. | Int32 | VA | 0.1 | R |
| 33 | 2 | R-phase active power R-phase active power of inverter 32-bit value: high word at 33, low word at 34. | Int32 | W | 0.1 | R |
| 35 | 2 | R-phase reactive power R-phase reactive power of inverter 32-bit value: high word at 35, low word at 36. | Int32 | var | 0.1 | R |
| 37 | 1 | S-phase grid voltage | UInt16 | V | 0.1 | R |
| 38 | 1 | S-phase grid current meter current | Int16 | A | 0.1 | R |
| 39 | 2 | S-phase apparent power S-phase apparent power of inverter 32-bit value: high word at 39, low word at 40. | Int32 | VA | 0.1 | R |
| 41 | 2 | S-phase active power S-phase active power of inverter 32-bit value: high word at 41, low word at 42. | Int32 | W | 0.1 | R |
| 43 | 2 | S-phase reactive power S-phase reactive power of inverter 32-bit value: high word at 43, low word at 44. | Int32 | var | 0.1 | R |
| 45 | 1 | T-phase grid voltage | UInt16 | V | 0.1 | R |
| 46 | 1 | T-phase grid current meter current | Int16 | A | 0.1 | R |
| 47 | 2 | T-phase apparent power T-phase apparent power of inverter 32-bit value: high word at 47, low word at 48. | Int32 | VA | 0.1 | R |
| 49 | 2 | T-phase active power T-phase active power of inverter 32-bit value: high word at 49, low word at 50. | Int32 | W | 0.1 | R |
| 51 | 2 | T-phase reactive power T-phase reactive power of inverter 32-bit value: high word at 51, low word at 52. | Int32 | var | 0.1 | R |
| 53 | 1 | RS-phase Grid line voltage | UInt16 | V | 0.1 | R |
| 54 | 1 | ST-phase Grid line voltage | UInt16 | V | 0.1 | R |
| 55 | 1 | TR-phase Grid line voltage | UInt16 | V | 0.1 | R |
| 56 | 1 | Grid frequency | UInt16 | Hz | 0.01 | R |
| 57 | 1 | Power factor Power factor = (raw - 10000) x 0.0001, the document's own formula "PF=(readValue-10000)" with its 0.0001 unit column: raw 10000 is 0 and raw 20000 is 1.0. The definition implies raw 10000 = 1.0 instead; the printed formula is followed. | Int16 | - | 0.0001 (offset -1) | R |
| 58 | 1 | Actual output power percentage | UInt16 | - | 0.01 | R |
| 60 | 2 | Power from R phase to user active power detected from R-phase meter or CT 32-bit value: high word at 60, low word at 61. | UInt32 | W | 0.1 | R |
| 62 | 2 | Power from S phase to user active power detected from S-phase meter or CT 32-bit value: high word at 62, low word at 63. | UInt32 | W | 0.1 | R |
| 64 | 2 | Power from T phase to user active power detected from T-phase meter or CT 32-bit value: high word at 64, low word at 65. | UInt32 | W | 0.1 | R |
| 66 | 2 | Total AC power to user Total active power detected from meter or CT 32-bit value: high word at 66, low word at 67. | UInt32 | W | 0.1 | R |
| 68 | 2 | Power from AC side to the grid, R phase active power detected from R-phase meter or CT 32-bit value: high word at 68, low word at 69. | UInt32 | W | 0.1 | R |
| 70 | 2 | Power from AC side to the grid, S phase active power detected from S-phase meter or CT 32-bit value: high word at 70, low word at 71. | UInt32 | W | 0.1 | R |
| 72 | 2 | Power from AC side to the grid, T phase active power detected from T-phase meter or CT 32-bit value: high word at 72, low word at 73. | UInt32 | W | 0.1 | R |
| 74 | 2 | Total power from AC side to the grid Total active power detected from meter or CT 32-bit value: high word at 74, low word at 75. | UInt32 | W | 0.1 | R |
| 76 | 2 | Total power from the inverter to local load total load power calculated from M3 32-bit value: high word at 76, low word at 77. | UInt32 | W | 0.1 | R |
| 78 | 1 | Off-grid frequency | UInt16 | Hz | 0.01 | R |
| 79 | 1 | Off-grid R-phase output voltage | UInt16 | V | 0.1 | R |
| 80 | 1 | Off-grid R-phase output current | UInt16 | A | 0.1 | R |
| 81 | 2 | Off-grid R-phase output Apparent Power off-grid R-phase apparent power of inverter 32-bit value: high word at 81, low word at 82. | UInt32 | VA | 0.1 | R |
| 83 | 2 | Off-grid R-phase output Active Power off-grid R-phase active power of inverter 32-bit value: high word at 83, low word at 84. | UInt32 | W | 0.1 | R |
| 85 | 1 | Off-grid S-phase output voltage | UInt16 | V | 0.1 | R |
| 86 | 1 | Off-grid S-phase output current | UInt16 | A | 0.1 | R |
| 87 | 2 | Off-grid S-phase output apparent power off-grid S-phase apparent power of inverter 32-bit value: high word at 87, low word at 88. | UInt32 | VA | 0.1 | R |
| 89 | 2 | Off-grid S-phase output active Power off-grid S-phase active power of inverter 32-bit value: high word at 89, low word at 90. | UInt32 | W | 0.1 | R |
| 91 | 1 | Off-grid T-phase output voltage | UInt16 | V | 0.1 | R |
| 92 | 1 | Off-grid T-phase output current | UInt16 | A | 0.1 | R |
| 93 | 2 | Off-grid T-phase output apparent power off-grid T-phase apparent power of inverter 32-bit value: high word at 93, low word at 94. | UInt32 | VA | 0.1 | R |
| 95 | 2 | Off-grid T-phase output active Power off-grid T-phase active power of inverter 32-bit value: high word at 95, low word at 96. | UInt32 | W | 0.1 | R |
| 97 | 1 | Off-grid output load percentage | UInt16 | - | 0.01 | R |
| 98 | 2 | System generating power total generating power of PV and battery 32-bit value: high word at 98, low word at 99. | UInt32 | W | 0.1 | R |
| 100 | 2 | Self-generated power load power consumption of the inverter (including device consumption itself) 32-bit value: high word at 100, low word at 101. | UInt32 | W | 0.1 | R |
| 102 | 2 | Battery discharge power 32-bit value: high word at 102, low word at 103. | UInt32 | W | 0.1 | R |
| 104 | 2 | Battery charge power 32-bit value: high word at 104, low word at 105. | UInt32 | W | 0.1 | R |
| 106 | 2 | AC Charge Power 32-bit value: high word at 106, low word at 107. | UInt32 | W | 0.1 | R |
| 108 | 1 | CT1 sampling current It is used to be distinguished from register 30. 15KW grid current value is sampled from inverter. | UInt16 | A | 0.1 | R |
| 109 | 1 | CT2 sampling current Used to be distinguished from register 30 | UInt16 | A | 0.1 | R |
| 110 | 1 | R-phase INV voltage | UInt16 | V | 0.1 | R |
| 111 | 1 | S-phase INV voltage | UInt16 | V | 0.1 | R |
| 112 | 1 | T-phase INV voltage | UInt16 | V | 0.1 | R |
| 113 | 1 | R-phase INV current | UInt16 | A | 0.1 | R |
| 114 | 1 | S-phase INV current | UInt16 | A | 0.1 | R |
| 115 | 1 | T-phase INV current | UInt16 | A | 0.1 | R |
| 116 | 1 | Grid connection countdown | UInt16 | - | 1 | R |
| 117 | 1 | BUS unbalanced current | Int16 | A | 0.1 | R |
| 118 | 1 | Generator voltage | UInt16 | V | 0.1 | R |
| 119 | 1 | CT insertion detection | UInt16 | - | 1 | R |
| 120 | 1 | 3 external heat pump on/off status bit (1-ON,0-OFF) bit00:Heat pump 1 on/off status bit01:Heat pump 2 on/off status bit02:Heat pump 3 on/off status bit03-bit15:reserve | UInt16 | - | 1 | R |
| 121 | 1 | Software subversion DSP Subversion display | UInt16 | - | 1 | R |
| 122 | 1 | Dry contact signal connection status 0:Indicates that the dry contact relay is not closed 1:Indicates that the on/off of dry contact relay is for ATE test use | UInt16 | - | 1 | R |
| 123 | 1 | Monitor board chip temperature | UInt16 | °C | 0.1 | R |
| 124 | 1 | Monitor board environment temperature | UInt16 | °C | 0.1 | R |
| 125 | 1 | Current battery priority 0:load priority 1:battery priority 2:grid priority | UInt16 | - | 1 | R |
| 126 | 1 | Battery Type 0:lead-acid battery 1:lithium battery | UInt16 | - | 1 | R |
| 127 | 1 | Battery voltage | UInt16 | V | 0.1 | R |
| 128 | 1 | Battery state of charge (inverter) | UInt16 | - | 0.01 | R |
| 129 | 1 | The inverter samples the battery voltage | UInt16 | V | 0.1 | R |
| 130 | 1 | Bus1 internal voltage | UInt16 | V | 0.1 | R |
| 131 | 1 | Bus2 internal voltage | UInt16 | V | 0.1 | R |
| 132 | 1 | Inverter temperature | Int16 | °C | 0.1 | R |
| 133 | 1 | Internal IPM temperature of the inverter | Int16 | °C | 0.1 | R |
| 134 | 1 | LLC Radiator temperature | Int16 | °C | 0.1 | R |
| 135 | 1 | Fan speed | UInt16 | - | 1 | R |
| 136 | 1 | Battery temperature | Int16 | °C | 0.1 | R |
| 137 | 1 | LLC voltage | UInt16 | V | 0.1 | R |
| 138 | 1 | Battery pack voltage | UInt16 | V | 0.1 | R |
| 139 | 1 | System fault word0 | UInt16 | - | 1 | R |
| 140 | 1 | System fault word1 | UInt16 | - | 1 | R |
| 141 | 1 | System fault word2 | UInt16 | - | 1 | R |
| 142 | 1 | System fault word3 | UInt16 | - | 1 | R |
| 143 | 1 | System fault word4 | UInt16 | - | 1 | R |
| 144 | 1 | System fault word5 | UInt16 | - | 1 | R |
| 145 | 1 | System fault word6 | UInt16 | - | 1 | R |
| 146 | 1 | System fault word7 | UInt16 | - | 1 | R |
| 147 | 1 | Inverter main fault code | UInt16 | - | 1 | R |
| 148 | 1 | Inverter sub-fault code | UInt16 | - | 1 | R |
| 149 | 2 | Battery power 32-bit value: high word at 149, low word at 150. | UInt32 | W | 0.1 | R |
| 153 | 1 | Derating mode flag | UInt16 | - | 1 | R |
| 154 | 1 | Leading and lagging flag | UInt16 | - | 1 | R |
| 155 | 1 | Battery status | UInt16 | - | 1 | R |
| 156 | 1 | Battery error message 1 master battery fault | UInt16 | - | 1 | R |
| 157 | 1 | Battery error message 2 slave battery 1 fault | UInt16 | - | 1 | R |
| 158 | 1 | Battery error message 3 slave battery 2 fault | UInt16 | - | 1 | R |
| 159 | 1 | Battery warning 1 master battery warning | UInt16 | - | 1 | R |
| 160 | 1 | Battery warning 2 slave battery 1 warrning | UInt16 | - | 1 | R |
| 161 | 1 | Battery warning 3 slave battery 2 warning | UInt16 | - | 1 | R |
| 162 | 1 | Battery SOC | UInt16 | - | 0.01 | R |
| 163 | 1 | Battery voltage | UInt16 | V | 0.1 | R |
| 164 | 1 | Battery current | Int16 | A | 0.1 | R |
| 165 | 1 | Battery temperature | Int16 | °C | 0.1 | R |
| 166 | 1 | The maximum charging current the battery allows | UInt16 | A | 0.1 | R |
| 167 | 1 | The maximum discharging current the battery allows | UInt16 | A | 0.1 | R |
| 168 | 1 | Gauge RM | UInt16 | Wh | 1 | R |
| 169 | 1 | Gauge FCC | UInt16 | Wh | 1 | R |
| 170 | 1 | Software version | UInt16 | - | 1 | R |
| 171 | 1 | Hardware version | UInt16 | - | 1 | R |
| 172 | 1 | Single battery voltage difference | UInt16 | V | 0.001 | R |
| 173 | 1 | Battery Cycle Count | UInt16 | - | 1 | R |
| 174 | 1 | SOH | UInt16 | - | 1 | R |
| 175 | 1 | CV voltage | UInt16 | V | 0.1 | R |
| 176 | 1 | BMS information | UInt16 | - | 1 | R |
| 177 | 1 | Pack information | UInt16 | - | 1 | R |
| 178 | 1 | Maximum single battery voltage | UInt16 | V | 0.001 | R |
| 179 | 1 | Minimum single battery voltage | UInt16 | V | 0.001 | R |
| 180 | 1 | Number of batteries in parallel | UInt16 | - | 1 | R |
| 181 | 1 | Number of cells | UInt16 | - | 1 | R |
| 182 | 1 | Cell number of the maximum cell voltage | UInt16 | - | 1 | R |
| 183 | 1 | Cell number of the minimum cell voltage | UInt16 | - | 1 | R |
| 184 | 1 | Maximum cell temperature | UInt16 | °C | 0.1 | R |
| 185 | 1 | Minimum cell temperature | UInt16 | °C | 0.1 | R |
| 186 | 1 | Cell number of the maximum cell temperature | UInt16 | - | 1 | R |
| 187 | 1 | Cell number of the minimum cell temperature | UInt16 | - | 1 | R |
| 188 | 1 | Faulty battery address | UInt16 | - | 1 | R |
| 189 | 1 | Maximum SOC in parallel | UInt16 | - | 0.01 | R |
| 190 | 1 | Minimum SOC in parallel | UInt16 | - | 0.01 | R |
| 191 | 1 | Battery Manufacturer Information | UInt16 | - | 1 | R |
| 192 | 1 | BMS fault number | UInt16 | - | 1 | R |
| 193 | 1 | Discharge cut-off voltage of lithium battery | UInt16 | V | 0.1 | R |
| 194 | 1 | Battery error message 1 slave battery 3 fault | UInt16 | - | 1 | R |
| 195 | 1 | Battery error message 2 slave battery 4 fault | UInt16 | - | 1 | R |
| 196 | 1 | Battery error message 3 slave battery 5 fault | UInt16 | - | 1 | R |
| 197 | 1 | Battery warning 1 slave battery 3 warning | UInt16 | - | 1 | R |
| 198 | 1 | Battery warning 2 slave battery 4 warning | UInt16 | - | 1 | R |
| 199 | 1 | Battery warning 3 slave battery 5 warning | UInt16 | - | 1 | R |
| 200 | 1 | BMS Slave battery 1 version | UInt16 | - | 1 | R |
| 201 | 1 | BMS Slave battery 2 version | UInt16 | - | 1 | R |
| 202 | 1 | BMS Slave battery 3 version | UInt16 | - | 1 | R |
| 203 | 1 | BMS Slave battery 4 version | UInt16 | - | 1 | R |
| 204 | 1 | BMS Slave battery 5 version | UInt16 | - | 1 | R |
| 250 | 2 | Daily power generation 32-bit value: high word at 250, low word at 251. | UInt32 | kWh | 0.1 | R |
| 252 | 2 | Total power generation 32-bit value: high word at 252, low word at 253. | UInt32 | kWh | 0.1 | R |
| 254 | 2 | Total working hours 32-bit value: high word at 254, low word at 255. | UInt32 | s | 0.5 | R |
| 256 | 2 | PV1 daily energy generation 32-bit value: high word at 256, low word at 257. | UInt32 | kWh | 0.1 | R |
| 258 | 2 | PV1 Total energy generation 32-bit value: high word at 258, low word at 259. | UInt32 | kWh | 0.1 | R |
| 260 | 2 | PV2 daily energy generation 32-bit value: high word at 260, low word at 261. | UInt32 | kWh | 0.1 | R |
| 262 | 2 | PV2 Total energy generation 32-bit value: high word at 262, low word at 263. | UInt32 | kWh | 0.1 | R |
| 264 | 2 | PV3 daily energy generation 32-bit value: high word at 264, low word at 265. | UInt32 | kWh | 0.1 | R |
| 266 | 2 | PV3 Total energy generation 32-bit value: high word at 266, low word at 267. | UInt32 | kWh | 0.1 | R |
| 268 | 2 | PV4 daily energy generation 32-bit value: high word at 268, low word at 269. | UInt32 | kWh | 0.1 | R |
| 270 | 2 | PV4 Total energy generation 32-bit value: high word at 270, low word at 271. | UInt32 | kWh | 0.1 | R |
| 272 | 2 | PV Daily power generation 32-bit value: high word at 272, low word at 273. | UInt32 | kWh | 0.1 | R |
| 274 | 2 | PV Total energy generation 32-bit value: high word at 274, low word at 275. | UInt32 | kWh | 0.1 | R |
| 276 | 2 | Daily charge amount 32-bit value: high word at 276, low word at 277. | UInt32 | kWh | 0.1 | R |
| 278 | 2 | Total charge amount 32-bit value: high word at 278, low word at 279. | UInt32 | kWh | 0.1 | R |
| 280 | 2 | Daily discharge amount 32-bit value: high word at 280, low word at 281. | UInt32 | kWh | 0.1 | R |
| 282 | 2 | Total discharge amount 32-bit value: high word at 282, low word at 283. | UInt32 | kWh | 0.1 | R |
| 284 | 2 | Daily AC charging amount 32-bit value: high word at 284, low word at 285. | UInt32 | kWh | 0.1 | R |
| 286 | 2 | Total AC charging amount 32-bit value: high word at 286, low word at 287. | UInt32 | kWh | 0.1 | R |
| 288 | 2 | Daily extra power from inverter to users 32-bit value: high word at 288, low word at 289. | UInt32 | kWh | 0.1 | R |
| 290 | 2 | Total extra power from inverter to user 32-bit value: high word at 290, low word at 291. | UInt32 | kWh | 0.1 | R |
| 292 | 2 | System daily energy generation 32-bit value: high word at 292, low word at 293. | UInt32 | kWh | 0.1 | R |
| 294 | 2 | System total energy generation 32-bit value: high word at 294, low word at 295. | UInt32 | kWh | 0.1 | R |
| 296 | 2 | Daily energy generation amount of self-generation and consumption 32-bit value: high word at 296, low word at 297. | UInt32 | kWh | 0.1 | R |
| 298 | 2 | Total energy generation amount for self-generation and consumption 32-bit value: high word at 298, low word at 299. | UInt32 | kWh | 0.1 | R |
| 300 | 2 | Daily load consumption of electricity 32-bit value: high word at 300, low word at 301. | UInt32 | kWh | 0.1 | R |
| 302 | 2 | Total load consumption of electricity 32-bit value: high word at 302, low word at 303. | UInt32 | kWh | 0.1 | R |
| 304 | 2 | Daily energy input to the grid 32-bit value: high word at 304, low word at 305. | UInt32 | kWh | 0.1 | R |
| 306 | 2 | Total energy input to the grid 32-bit value: high word at 306, low word at 307. | UInt32 | kWh | 0.1 | R |
| 308 | 2 | Daily energy output from the grid 32-bit value: high word at 308, low word at 309. | UInt32 | kWh | 0.1 | R |
| 310 | 2 | Total energy output from the grid 32-bit value: high word at 310, low word at 311. | UInt32 | kWh | 0.1 | R |
| 312 | 1 | R-phase DC voltage | Int16 | V | 0.1 | R |
| 313 | 1 | S-phase DC voltage | Int16 | V | 0.1 | R |
| 314 | 1 | T-phase DC voltage | Int16 | V | 0.1 | R |
| 315 | 1 | R-phase DC current | Int16 | mA | 0.1 | R |
| 316 | 1 | S-phase DC current | Int16 | mA | 0.1 | R |
| 317 | 1 | T-phase DC current | Int16 | mA | 0.1 | R |
| 318 | 1 | ISO value of resistance | UInt16 | kΩ | 1 | R |
| 319 | 1 | Ground fault circuit interrupter | Int16 | mA | 1 | R |
| 320 | 1 | Test process Autotest Test procedure and parameters | UInt16 | - | 1 | R |
| 321 | 1 | Test status | UInt16 | - | 1 | R |
| 322 | 1 | Test step | UInt16 | - | 1 | R |
| 323 | 1 | Default protection value (Voltage or frequency) | UInt16 | - | 1 | R |
| 324 | 1 | Protection time | UInt16 | - | 1 | R |
| 325 | 1 | Actual sampling value (Voltage or frequency) | UInt16 | - | 1 | R |
| 326 | 1 | Test simulation value(Voltage or frequency) | UInt16 | - | 1 | R |
| 327 | 1 | Actual protection value(Voltage or frequency) | UInt16 | - | 1 | R |
| 328 | 1 | Protection time | UInt16 | - | 1 | R |
| 329 | 1 | Logical interface flag | UInt16 | - | 1 | R |
| 330 | 2 | PV meter R-phase active power 32-bit value: high word at 330, low word at 331. | Int32 | W | 0.1 | R |
| 332 | 2 | PV meter S-phase active power 32-bit value: high word at 332, low word at 333. | Int32 | W | 0.1 | R |
| 334 | 2 | PV meter T-phase active power 32-bit value: high word at 334, low word at 335. | Int32 | W | 0.1 | R |
| 336 | 1 | Number of parallel devices | UInt16 | - | 1 | R |
| 337 | 1 | Parallel ID | UInt16 | - | 1 | R |
| 338 | 1 | Effective Number of parallel devices | UInt16 | - | 1 | R |
| 339 | 2 | Total active power of PV meter 32-bit value: high word at 339, low word at 340. | Int32 | W | 0.1 | R |
| 341 | 1 | Master DSP version main version of master DSP*100+ A subversion of the master DSP | UInt16 | - | 1 | R |
| 342 | 1 | Slave DSP version main version of slave DSP*100+ A subversion of the slave DSP | UInt16 | - | 1 | R |
| 343 | 1 | Total version number 1 ver1 | UInt16 | - | 1 | R |
| 344 | 1 | Total version number 2 ver2 ver3 | UInt16 | - | 1 | R |
| 345 | 1 | R-phase DC current 2 | Int16 | mA | 0.1 | R |
| 350 | 2 | PV annual power generation 32-bit value: high word at 350, low word at 351. | UInt32 | kWh | 0.1 | R |
| 352 | 2 | PV monthly generation energy 32-bit value: high word at 352, low word at 353. | UInt32 | kWh | 0.1 | R |
| 354 | 2 | Annual load consumption of electricity 32-bit value: high word at 354, low word at 355. | UInt32 | kWh | 0.1 | R |
| 356 | 2 | Monthly load consumption of electricity 32-bit value: high word at 356, low word at 357. | UInt32 | kWh | 0.1 | R |
| 358 | 2 | Annual energy input to the grid 32-bit value: high word at 358, low word at 359. | UInt32 | kWh | 0.1 | R |
| 360 | 2 | Monthly energy input to the grid 32-bit value: high word at 360, low word at 361. | UInt32 | kWh | 0.1 | R |
| 362 | 2 | Annual energy amount from the grid 32-bit value: high word at 362, low word at 363. | UInt32 | kWh | 0.1 | R |
| 364 | 2 | Monthly energy amount from the grid 32-bit value: high word at 364, low word at 365. | UInt32 | kWh | 0.1 | R |
| 366 | 2 | Annual charge amount 32-bit value: high word at 366, low word at 367. | UInt32 | kWh | 0.1 | R |
| 368 | 2 | Monthly charge amount 32-bit value: high word at 368, low word at 369. | UInt32 | kWh | 0.1 | R |
| 370 | 2 | Annual discharge amount 32-bit value: high word at 370, low word at 371. | UInt32 | kWh | 0.1 | R |
| 372 | 2 | Monthly discharge amount 32-bit value: high word at 372, low word at 373. | UInt32 | kWh | 0.1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Hinen H5000 hybrid inverter protocol: 'Inverter Modbus RTU Protocol', V1.62, 2024-09-27 (spreadsheet 'Inverter.Modbus.RTU.Protocol.V1.62.20240927.xlsx' with a protocol change record from V1.00 to V1.62). The vendor serves manuals at hinen.com but not this protocol file, so the copy read is the spreadsheet mirrored at https://github.com/user-attachments/files/17622814/Inverter.Modbus.RTU.Protocol.V1.62.20240927.xlsx, SHA-256 1d45b17280ac342e8f38a39188f2d3ea73e4a074a8a777a1092f99c096e0f71e, retrieved 2026-11-23 (MIRROR-SOURCED). The document itself prints no author, company or model name: the brand attribution comes from the Solarman community definition that cites it (ha-solarman commit 84982c5, 'Tested with Hinen H5000-EU') and from its battery-type enumeration, which lists 'HINEN' as a battery brand; treat the provenance as SECONDARY, not a vendor-signed document. Framing is the document's own protocol sheet: RTU, 8 data bits, no parity, 1 stop bit, default 9600 bps, slave addresses 1-254 with 0 as broadcast, function codes 03/04/06/10, and a minimum 850 ms between commands. Register numbers are the wire addresses (the table numbers registers from 0 and the community definition reads the same numbers with function code 03/04), so the seed is zero_based. 32-bit quantities are printed as an 'H' row followed by an 'L' row at the next address; each pair is merged into one 32-bit row whose description names both words. Seeded: the whole input-register table (system operating parameters, battery information and energy statistics) and six holding rows - remote on/off, device type, device ID, baud rate and the two rated-power pairs. Not seeded: the rest of the holding table (battery settings and the grid-safety protection block, 338 rows) because these are write registers for the battery and the grid interface; the ASCII rows (serial 5-19, firmware and model); and the 'reserve' rows. No source claims a hardware test.