SUN-800-G3 / SUN-M80-G3 micro-inverters Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Device
Values: 0x0000 = Unknown; [0x0002, 0x0200] = String Inverter; [0x0003, 0x0300] = Single-Phase Hybrid Inverter; [0x0004, 0x0400] = Microinverter; [0x0005, 0x0500] = LV 3-Phase Hybrid Inverter; 0x0006 = HV 3-Phase Hybrid Inverter; [0x0007, 0x0600] = HV 3-Phase Inverter 6-15kw; [0x0008, 0x0601] = HV 3-Phase Inverter 20-50kw; 0x0103 = Off-Grid Inverter; 0x0104 = Energy Storage System.
UInt16-1R
11
Device Modbus Address
UInt16-1R
81
Device Flags
Bit 0: 0 = number of channels taken from the rated power, 1 = from the MPPT number. Other bits are not described by the source.
UInt16-1R
91
Device Chip Type
Low 4 bits: 1 = AT32F403A; 2 = SXX32F103; 3 = GD32F103; 4 = GD32F303, as the vendor table prints them; the community definition numbers the same four chips 0-3.
UInt16-1R
162
Device Rated Power
Int32W0.1R
211
Self-check time
UInt16s1R
271
Grid Voltage Upper Limit
UInt16V0.1R
281
Grid Voltage Lower Limit
UInt16V0.1R
291
Grid Frequency Upper Limit
UInt16Hz0.01R
301
Grid Frequency Lower Limit
UInt16Hz0.01R
341
Over-Frequency Load Reduction Start
UInt16Hz0.01R
351
Over-Frequency Load Reduction
UInt16%1R
391
Power Factor Regulation
UInt16-0.001 (offset -1)R
401
Active Power Regulation
Active power limit in 0.1 % steps; the vendor table notes that a raw 800 means 80.0 % and the definition's configurable range is 0-120 %.
UInt16%0.1R
431
On/off switch enable
The vendor table lists it as R/W with range [0,1]: 0 = power off, 1 = power on (its micro-inverter note adds 2 = power off); the community definition's switch maps on to 1 but off to 2. Because the two sources disagree on the off value, the row is read-only here.
UInt16-1R
461
Island Protection
0 = disable, 1 = enable.
UInt16-1R
471
Soft Start
Soft-start (ramp) enable: 0 = disable, 1 = enable.
UInt16-1R
481
GFDI
0 = disable, 1 = enable. The vendor table names it GFDI enable on older units and meter enable on newer ones.
UInt16-1R
491
Over-Frequency Load Reduction
Over-frequency load-reduction enable: 0 = disable, 1 = enable.
UInt16-1R
501
RISO
Insulation-resistance monitoring enable: 0 = disable, 1 = enable.
UInt16-1R
541
EEPROM
Values: 0 = Normal; 1 = Initialize the control board EEPROM; 2 = Initialize the communication board EEPROM.
UInt16-1R
591
Device State
Values: 0x0000 = Standby; 0x0001 = Self-test; 0x0002 = Normal; 0x0003 = Alarm; 0x0004 = Fault.
UInt16-1R
601
Today Production
The vendor table notes it as "signed int" with a printed range of -32768 to 32767, while the definition reads it unsigned; a day's production cannot be negative, so the row stays unsigned.
UInt16kWh0.1R
632
Total Production
Total active production energy, two registers with the low word at 63. The vendor row prints range 0-0xFFFFFFFF but notes the type as "signed int"; its range, evcc's uint32s decode and the fact that the counter cannot go negative all say unsigned, so UInt32 is used.
UInt32kWh0.1R
651
Today Production 1
UInt16kWh0.1R
661
Today Production 2
UInt16kWh0.1R
671
Today Production 3
UInt16kWh0.1R
681
Today Production 4
UInt16kWh0.1R
692
Total Production 1
Cumulative production of channel 1, 32 bits with the high word at 69 and the low word at 70; the vendor table prints the two words as separate rows at 0.1 kWh, the definition reads the low word alone.
UInt32kWh0.1R
712
Total Production 2
Cumulative production of channel 2, 32 bits with the high word at 71 and the low word at 72.
UInt32kWh0.1R
731
Grid Voltage
UInt16V0.1R
742
Total Production 3
Cumulative production of channel 3, 32 bits with the high word at 74 and the low word at 75.
UInt32kWh0.1R
761
Grid Current
Int16A0.1R
772
Total Production 4
Cumulative production of channel 4, 32 bits with the high word at 77 and the low word at 78.
UInt32kWh0.1R
791
Grid Frequency
UInt16Hz0.01R
862
Output active power
Output active power, two registers with the low word at 86. The vendor table prints 0.1 W and evcc decodes register 86 as uint32s at 0.1; the definition's 1.1 scale on this address is an outlier and is not used.
UInt32W0.1R
901
Temperature
Radiator temperature. The vendor table prints 0.1 °C with a 0-3000 range and its worked examples state that 0 °C is raw 1000 (-56.2 °C = 438, 50.5 °C = 1505), hence scale 0.1 with offset -100.0; the definition states the same 1000 offset but a 0.01 scale, which would read 1250 as 2.5 °C, so the vendor scale is used.
UInt16°C0.1 (offset -100)R
1012
Device Alarm
Two warning words, low word at 101. Bits the definition decodes: 1 = fan failure, 2 = grid phase failure, 3 = meter communication failure, 30 = battery loss, 31 = parallel communication quality. Word values are listed in the vendor document's alarm code table, which this map does not transcribe.
UInt32-1R
1091
PV1 Voltage
UInt16V0.1R
1101
PV1 Current
UInt16A0.1R
1111
PV2 Voltage
UInt16V0.1R
1121
PV2 Current
UInt16A0.1R
1131
PV3 Voltage
UInt16V0.1R
1141
PV3 Current
UInt16A0.1R
1151
PV4 Voltage
UInt16V0.1R
1161
PV4 Current
UInt16A0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Deye micro-inverter map. Sources: (1) vendor document 'Deye Modbus protocol V1.18' (mirror https://github.com/user-attachments/files/16597960/Deye.Modbus.protocol.V118.pdf, SHA-256 7444d2ef7dee282d5dbc734e73d6792788bc8a323ca532c8202d8d5f976b3717, 2026-11-23) for the baud line, rows 86, 63 and 90, and the names and scales its table pairs; (2) the Solarman definition deye_micro.yaml (ha-solarman commit 84982c5be1cda2c9642d87dd37e2bffd4aef6b83, SHA-256 18d11190205f0af5c9b99dde05a0e57173743563a47e819ed52d156a8c84d816), SECONDARY, for the address scope; (3) evcc deye-string.yaml and deye-mi.yaml (evcc commit c95e43506df075706ad3de0e994d1da4820dca49), which read 86 and 63 as holding at 0.1. Types and widths follow the definition's rule codes as ha-solarman's parser implements them (1/3 unsigned, 2/4 signed; registers-list length is the width; first listed register is the low word). The vendor table shares one address column across micro, string and hybrid units, so an address can mean different things per family (065 is channel 1 day production on a micro and monthly PV generation on a hybrid); these rows are the micro meanings. The four channel cumulative counters are 32-bit pairs in the vendor table (69/70, 71/72, 74/75, 77/78) while the definition reads only each low word. Area: holding registers, as ha-solarman's default read code is 0x03 (const.py REGISTERS_CODE) and evcc reads 86/63 as holding; the vendor table prints no per-row function code. Frame: it prints only 'Baud rate: 9600bps RS232 or RS485', so the frame is cited from Developer089/deye-modbus-ha at 591a24a09d01cc58e553ca02e6f49a72181ae984 (9600, 8 data bits, parity N, 1 stop bit) plus evcc's 8N1. Left out: ASCII, version and time rows, 64-bit blocks, mask/bit rows, the composite PV-power sensors and the string-only blocks. No write row; no hardware test claimed.