All devices

Daikin · Chiller controller

EKDICMPA Intelligent Chiller Manager (iCM, option 184) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11001
System Operating State
Vendor range: 1 1 Stop R
UInt16-1R
11011
SCM type
Vendor range: 1 0 Mst/Slv R
UInt16-1R
11021
Configuration type
Vendor range: 1 0 Undef R
UInt16-1R
11031
System Cooling leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11041
System heating leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11051
System avg evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11061
System avg condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
18901
System controlled heat temp.
Vendor range: 10 °C R
Int16°C0.1R
11071
System actual setpoint
Vendor range: 10 °C R
Int16°C0.1R
11081
System heat setpoint
Vendor range: 10 °C R
Int16°C0.1R
11091
Next chiller on
Vendor range: 1 0 None R
UInt16-1R
11101
Next chiller off
Vendor range: 1 as Next Chiller On R
UInt16-1R
11111
Standby chiller Value
Vendor range: 1 as Next Chiller On R
UInt16-1R
11121
System load
Vendor range: 1 0…100% R
Int16%1R
11131
Cooling load
Vendor range: 1 0…100% R
Int16%1R
11141
Heating load
Vendor range: 1 0…100% R
Int16%1R
11151
System Demand Limit Value
Vendor range: 1 0…100% R
Int16%1R
11161
System Demand Limit Operating State
Vendor range: 1 1 No R
UInt16-1R
11171
Energy monitoring configured
Vendor range: 1 1 N/Cfgd R
UInt16-1R
11181
Heat recovery configured
Vendor range: 1 1 N/Cfgd R
UInt16-1R
11191
Master - Actual mode
Vendor range: 1 0 Cool R
UInt16-1R
11201
Master - Circuit #1 Current mode
Vendor range: 1 0 Off R
UInt16-1R
11211
Master - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
11241
Master - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11251
Master - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
11281
Master - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11291
Master - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11301
Master - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11311
Master - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11321
Master - Load
Vendor range: 1 0…100% R
Int16%1R
11351
Master - Standalone
Vendor range: 1 1 No R
UInt16-1R
11361
Master - State
Vendor range: 1 0 Off R
UInt16-1R
11371
Slave #1 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
11381
Slave #1 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11391
Slave #1 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
11421
Slave #1 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11431
Slave #1 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
11461
Slave #1 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11471
Slave #1 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11481
Slave #1 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11491
Slave #1 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11501
Slave #1 - Load
Vendor range: 1 0…100% R
Int16%1R
11531
Slave #1 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
11541
Slave #1 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
11551
Slave #2 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
11561
Slave #2 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11571
Slave #2 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
11601
Slave #2 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11611
Slave #2 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
11641
Slave #2 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11651
Slave #2 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11661
Slave #2 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11671
Slave #2 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11681
Slave #2 - Load
Vendor range: 1 0…100% R
Int16%1R
11711
Slave #2 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
11721
Slave #2 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
11731
Slave #3 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
11741
Slave #3 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11751
Slave #3 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
11781
Slave #3 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11791
Slave #3 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
11821
Slave #3 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11831
Slave #3 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11841
Slave #3 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
11851
Slave #3 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
11861
Slave #3 - Load
Vendor range: 1 0…100% R
Int16%1R
11891
Slave #3 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
11901
Slave #3 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
11911
Slave #4 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
11921
Slave #4 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11931
Slave #4 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
11961
Slave #4 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
11971
Slave #4 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
12001
Slave #4 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12011
Slave #4 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12021
Slave #4 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12031
Slave #4 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12041
Slave #4 - Load
Vendor range: 1 0…100% R
Int16%1R
12071
Slave #4 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
12081
Slave #4 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
12091
Slave #5 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
12101
Slave #5 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
12111
Slave #5 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
12141
Slave #5 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
12151
Slave #5 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
12181
Slave #5 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12191
Slave #5 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12201
Slave #5 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12211
Slave #5 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12221
Slave #5 - Load
Vendor range: 1 0…100% R
Int16%1R
12251
Slave #5 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
12261
Slave #5 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
12271
Slave #6 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
12281
Slave #6 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
12291
Slave #6 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
12321
Slave #6 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
12331
Slave #6 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
12361
Slave #6 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12371
Slave #6 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12381
Slave #6 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12391
Slave #6 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12401
Slave #6 - Load
Vendor range: 1 0…100% R
Int16%1R
12431
Slave #6 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
12441
Slave #6 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
12451
Slave #7 - Actual mode
Vendor range: 1 as MasterData'ActMode R
UInt16-1R
12461
Slave #7 - Circuit #1 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
12471
Slave #7 - Circuit #1 Load
Vendor range: 1 0…100% R
Int16%1R
12501
Slave #7 - Circuit #2 Current mode
Vendor range: 1 as MasterData'CurrentModeC1 R
UInt16-1R
12511
Slave #7 - Circuit #2 Load
Vendor range: 1 0…100% R
Int16%1R
12541
Slave #7 - Condenser entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12551
Slave #7 - Condenser leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12561
Slave #7 - Evaporator entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12571
Slave #7 - Evaporator leaving water temp.
Vendor range: 10 °C R
Int16°C0.1R
12581
Slave #7 - Load
Vendor range: 1 0…100% R
Int16%1R
12611
Slave #7 - Standalone
Vendor range: 1 as MasterData'StandAlone R
UInt16-1R
12621
Slave #7 - State
Vendor range: 1 as MasterData'State R
UInt16-1R
12631
System electrical power
Vendor range: 10 MW R
Int16-0.1R
12641
System thermal power
Vendor range: 10 MW R
Int16-0.1R
12651
System COP
Vendor range: 10 - R
Int16-0.1R
12661
Master - Energy monitoring configured
Vendor range: 1 1 N/Cfgd R
UInt16-1R
12671
Master - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12681
Master - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12701
Slave #1 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12711
Slave #1 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12731
Slave #2 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12741
Slave #2 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12761
Slave #3 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12771
Slave #3 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12791
Slave #4 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12801
Slave #4 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12821
Slave #5 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12831
Slave #5 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12851
Slave #6 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12861
Slave #6 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12881
Slave #7 - Thermal power
Vendor range: 10 kW R
Int16kW0.1R
12891
Slave #7 - Electrical power
Vendor range: 10 kW R
Int16kW0.1R
12901
System Heat recovery operating state
Vendor range: 1 1 Stop R
UInt16-1R
12911
Average Heat Recovery Entering Water temp.
Vendor range: 10 °C R
Int16°C0.1R
12921
Master - Heat recovery configured
Vendor range: 1 1 N/Cfgd R
UInt16-1R
12931
Master - Heat recovery state
Vendor range: 1 1 Stop R
UInt16-1R
12941
Master - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12951
Slave #1 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
12961
Slave #1 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12971
Slave #2 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
12981
Slave #2 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
12991
Slave #3 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
13001
Slave #3 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
13011
Slave #4 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
13021
Slave #4 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
13031
Slave #5 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
13041
Slave #5 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
13051
Slave #6 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
13061
Slave #6 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
13071
Slave #7 - Heat recovery state
Vendor range: 1 as MasterData'HeatRecRun R
UInt16-1R
13081
Slave #7 - Heat recovery entering water temp.
Vendor range: 10 °C R
Int16°C0.1R
13091
Freecooling Status
Vendor range: 1 0 Off:Switch R
UInt16-1R
13101
System Outside Air Temperature
Vendor range: 10 °C R
Int16°C0.1R
13111
Master - Freecooling configured
Vendor range: 1 1 N/Cfgd R
UInt16-1R
13121
Master - Freecooling available
Vendor range: 1 1 N/Avail R
UInt16-1R
13131
Master - Freecooling Mode
Vendor range: 1 0 Mech_All R
UInt16-1R
13141
Slave #1 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
13151
Slave #2 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
13161
Slave #3 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
13171
Slave #4 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
13181
Slave #5 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
13191
Slave #6 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
13201
Slave #7 - Freecooling Mode
Vendor range: 1 as MasterData'FreeClgMode R
UInt16-1R
3301
Standalone Mode Setpoint
Vendor range: 1 0 No R/W
UInt16-1RW
13241
Master enabling
Vendor range: 1 0 Disable R/W
UInt16-1RW
13251
Master - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13261
Master - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13271
Slave #1 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13281
Slave #1 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13291
Slave #2 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13301
Slave #2 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13311
Slave #3 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13321
Slave #3 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13331
Slave #4 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13341
Slave #4 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13351
Slave #5 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13361
Slave #5 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13371
Slave #6 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13381
Slave #6 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13391
Slave #7 - Priority (Cooling mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
13401
Slave #7 - Priority (Heating mode)
Vendor range: 1 1…8 R/W
UInt16-1RW
3311
Standby Unit Setpoint
Vendor range: 1 0 No R/W
UInt16-1RW
13411
Standby temp compensation
Vendor range: 1 0 No R/W
UInt16-1RW
13421
Master - Unit type
Vendor range: 1 0 Undef R
UInt16-1R
13431
Slave #1 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13441
Slave #2 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13451
Slave #3 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13461
Slave #4 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13471
Slave #5 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13481
Slave #6 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13491
Slave #7 - Unit type
Vendor range: 1 as MstUnitType R
UInt16-1R
13501
Evap PM - Application Version
Application version, gain 100 with the vendor range printed as X,XX: the raw value divided by 100 is the version (123 displays as 1.23).
UInt16-0.01R
13511
Evap PM - Number of Pump
Vendor range: 1 0…10 R
UInt16-1R
13521
Evap PM - Status
Vendor range: 1 0 Off:Auto R
UInt16-1R
13531
Evap PM - Operating state
Vendor range: 1 1 Stop R
UInt16-1R
13541
Evap PM - General Alarm
Vendor range: 1 1 None R
UInt16-1R
13551
Evap Pump #1 - Status
Vendor range: 1 0 Off R
UInt16-1R
13561
Evap Pump #2 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13571
Evap Pump #3 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13581
Evap Pump #4 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13591
Evap Pump #5 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13601
Evap Pump #6 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13611
Evap Pump #7 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13621
Evap Pump #8 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13631
Evap Pump #9 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13641
Evap Pump #10 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13651
Evap Pumps - Running
Vendor range: 1 0…10 R
UInt16-1R
13661
Evap Pumps - Speed
Vendor range: 1 0…100% R
UInt16%1R
13671
Evap PM - Speed Control Type
Vendor range: 1 0 NULL R
UInt16-1R
13681
Evap Speed Control - Delta Temp
Vendor range: 10 °Dc R
Int16-0.1R
13691
Evap Speed Control - Actual Setpoint
Vendor range: 10 °Dc R
Int16-0.1R
13701
Evap Speed Control - Setpoint Network
Vendor range: 10 °Dc R/W
Int16-0.1RW
13711
Evap Speed Control - Differential Pressure
Vendor range: 1 kPa R
Int16-1R
13721
Evap Speed Control - Actual Setpoint
Vendor range: 1 kPa R
Int16-1R
13731
Evap Speed Control - Setpoint Network
Vendor range: 1 kPa R/W
Int16-1RW
13741
Evap Speed Control - Absolute Pressure
Vendor range: 1 kPa R
Int16-1R
13751
Evap Speed Control - Actual Setpoint
Vendor range: 1 kPa R
Int16-1R
13761
Evap Speed Control - Setpoint Network
Vendor range: 1 kPa R/W
Int16-1RW
13771
Evaporator Bypass Valve - Opening
Vendor range: 1 0…100% R
Int16%1R
13781
Evap PM - Bypass Valve Control Type
Vendor range: 1 0 NULL R
UInt16-1R
13791
Evap Bypass Control - Min Diff Pressure on Units
Vendor range: 1 0 None R
UInt16-1R
13801
Evap Bypass Control - Flow
Vendor range: 10 l/s R
Int16-0.1R
13811
Evap Bypass Control - Actual Setpoint
Vendor range: 10 l/s R
Int16-0.1R
13821
Evap Bypass Control - Setpoint Network
Vendor range: 10 l/s R/W
Int16-0.1RW
13831
Evap Bypass Control - EWT
Vendor range: 10 °C R
Int16°C0.1R
13841
Evap Bypass Control - Actual Setpoint
Vendor range: 10 °C R
Int16°C0.1R
13851
Evap Bypass Control - Setpoint Network
Vendor range: 10 °C R/W
Int16°C0.1RW
13861
Evap PM - Energy Meter Configured
Vendor range: 1 0 N/Cfgd R
UInt16-1R
13871
Evap PM - Electrical Active Power
Vendor range: 10 kW R
Int16kW0.1R
13881
Evap Pump Manager - Speed Control sensor alarm
Vendor range: 1 0 None R
UInt16-1R
13891
Evap Pump Manager - Available pump alarm
Vendor range: 1 0 None R
UInt16-1R
13901
Evap Pump Manager - Configuration alarm
Vendor range: 1 0 None R
UInt16-1R
13911
Cond PM - Application Version
Application version, gain 100 with the vendor range printed as X,XX: the raw value divided by 100 is the version (123 displays as 1.23).
UInt16-0.01R
13921
Cond PM - Number of Pump
Vendor range: 1 0…10 R
UInt16-1R
13931
Cond PM - Status
Vendor range: 1 0 Off:Auto R
UInt16-1R
13941
Cond PM - Operating state
Vendor range: 1 1 Stop R
UInt16-1R
13951
Cond PM - General Alarm
Vendor range: 1 1 None R
UInt16-1R
13961
Cond Pump #1 - Status
Vendor range: 1 0 Off R
UInt16-1R
13971
Cond Pump #2 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13981
Cond Pump #3 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
13991
Cond Pump #4 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14001
Cond Pump #5 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14011
Cond Pump #6 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14021
Cond Pump #7 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14031
Cond Pump #8 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14041
Cond Pump #9 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14051
Cond Pump #10 - Status
Vendor range: 1 as EvapPM'StatusP1 R
UInt16-1R
14061
Cond Pumps - Running
Vendor range: 1 0…10 R
UInt16-1R
14071
Cond Pumps - Speed
Vendor range: 1 0…100% R
Int16%1R
14081
Cond PM - Speed Control Type
Vendor range: 1 0 NULL R
UInt16-1R
14091
Cond Speed Control - Delta Temp
Vendor range: 10 °Dc R
Int16-0.1R
14101
Cond Speed Control - Actual Setpoint
Vendor range: 10 °Dc R
Int16-0.1R
14111
Cond Speed Control - Setpoint Network
Vendor range: 10 °Dc R/W
Int16-0.1RW
14121
Cond Speed Control - Differential Pressure
Vendor range: 1 kPa R
Int16-1R
14131
Cond Speed Control - Actual Setpoint
Vendor range: 1 kPa R
Int16-1R
14141
Cond Speed Control - Setpoint Network
Vendor range: 1 kPa R/W
Int16-1RW
14151
Cond Speed Control - Absolute Pressure
Vendor range: 1 kPa R
Int16-1R
14161
Cond Speed Control - Actual Setpoint
Vendor range: 1 kPa R
Int16-1R
14171
Cond Speed Control - Setpoint Network
Vendor range: 1 kPa R/W
Int16-1RW
14181
Condenser Bypass Valve - Opening
Vendor range: 1 0…100% R
Int16%1R
14191
Cond PM - Bypass Valve Control Type
Vendor range: 10 0 NULL R
UInt16-0.1R
14201
Cond Bypass Control - Flow
Vendor range: 10 l/s R
Int16-0.1R
14211
Cond Bypass Control - Active Setpoint
Vendor range: 10 l/s R
Int16-0.1R
14221
Cond Speed Control - Setpoint Network
Vendor range: 10 l/s R/W
Int16-0.1RW
14231
Cond Bypass Control - EWT
Vendor range: 10 °C R
Int16°C0.1R
14241
Cond Bypass Control - Actual Setpoint
Vendor range: 10 °C R
Int16°C0.1R
14251
Cond Bypass Control - Setpoint Network
Vendor range: 10 °C R/W
Int16°C0.1RW
14261
Cond PM - Energy Meter configured
Vendor range: 1 0 N/Cfgd R
UInt16-1R
14271
Cond PM - Electrical Active Power
Vendor range: 10 kW R
Int16kW0.1R
14281
Cond Pump Manager - Speed Control sensor alarm
Vendor range: 1 0 None R
UInt16-1R
14291
Cond Pump Manager - Available pump alarm
Vendor range: 1 0 None R
UInt16-1R
14301
Cond Pump Manager - Configuration alarm
Vendor range: 1 0 None R
UInt16-1R
14311
Slave - Master Missing
Vendor range: 1 0 None R
UInt16-1R
14321
Slave - Master Disconnected
Vendor range: 1 0 No R
UInt16-1R
8901
Slave - Master Communication Error
Vendor range: 1 0 None R
UInt16-1R
14331
Common Leaving Hot water temp. sensor fault
Vendor range: 1 0 None R
UInt16-1R
5951
Common Leaving water temp. sensor fault
Vendor range: 1 0 None R
UInt16-1R
8911
Slave #1 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14341
Slave #1 - Missing
Vendor range: 1 0 No R
UInt16-1R
8921
Slave #2 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14351
Slave #2 - Missing
Vendor range: 1 0 No R
UInt16-1R
8931
Slave #3 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14361
Slave #3 - Missing
Vendor range: 1 0 No R
UInt16-1R
14371
Slave #4 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14381
Slave #4 - Missing
Vendor range: 1 0 No R
UInt16-1R
14391
Slave #5 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14401
Slave #5 - Missing
Vendor range: 1 0 No R
UInt16-1R
14411
Slave #6 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14421
Slave #6 - Missing
Vendor range: 1 0 No R
UInt16-1R
14431
Slave #7 - Communication Error
Vendor range: 1 0 None R
UInt16-1R
14441
Slave #7 - Missing
Vendor range: 1 0 No R
UInt16-1R
14451
Configuration Alarm
Vendor range: 1 0 NULL R
UInt16-1R
14461
Energy monitoring configuration Error
Vendor range: 1 0 None R
UInt16-1R
14471
Heat recovery configuration Error
Vendor range: 1 0 None R
UInt16-1R
14481
Evap PM - Clear Alarm setpoint
Vendor range: 1 0 --- R/W
UInt16-1RW
14491
Cond PM - Clear Alarm setpoint
Vendor range: 1 0 --- R/W
UInt16-1RW
14501
iCT - Tower Number
Vendor range: 1 0…10 R
UInt16-1R
14511
iCT - Status
Vendor range: 1 0 Off:Auto R
UInt16-1R
14521
iCT - Operating State
Vendor range: 1 1 Stop R
UInt16-1R
14531
iCT - General Alarm
Vendor range: 1 1 None R
UInt16-1R
14541
iCT - Number of Running Tower
Vendor range: 1 0…10 R
UInt16-1R
14551
iCT - Next On Tower
Vendor range: 1 0…10 R
UInt16-1R
14561
iCT - Next Off Tower
Vendor range: 1 0 None R
UInt16-1R
14571
iCT - Leaving Water Termperature
Vendor range: 10 °C R
Int16°C0.1R
14581
iCT - LWT sernsor Alarm
Vendor range: 1 0 None R
UInt16-1R
14591
iCT LWT Control - Setpoint Reset type
Vendor range: 1 0 NULL R
UInt16-1R
14601
iCT LWT Control - Actual Setpoint
Vendor range: 10 °C R
Int16°C0.1R
14611
iCT LWT Control - Setpoint iCM
Vendor range: 10 °C R
Int16°C0.1R
14621
iCT LWT Control - Setpoint Network
Vendor range: 10 °C R/W
Int16°C0.1RW
14631
iCT - Outside Air Temperature
Vendor range: 10 °C R
Int16°C0.1R
14641
iCT - Outside Relative Humidity
Vendor range: 10 %r.H R
Int16%0.1R
14651
iCT - Outside Wet Bulb Temperature
Vendor range: 10 °C R
Int16°C0.1R
14661
Cooling Tower 1 - Status
Vendor range: 1 0 Off R
UInt16-1R
14671
Cooling Tower 1 - Fan Status
Vendor range: 1 0 Stop R
UInt16-1R
14681
Cooling Tower 1 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
14691
Cooling Tower 1 - Inlet Valve Status
Vendor range: 1 0 Close R
UInt16-1R
14701
Cooling Tower 1 - LWT
Vendor range: 10 °C R
Int16°C0.1R
14711
Cooling Tower 1 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
14721
Cooling Tower 2 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
14731
Cooling Tower 2 - Fan Status
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
14741
Cooling Tower 2 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
14751
Cooling Tower 2 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
14761
Cooling Tower 2 - LWT
Vendor range: 10 °C R
Int16°C0.1R
14771
Cooling Tower 2 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
14781
Cooling Tower 3 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
14791
Cooling Tower 3 - Fan Status
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
14801
Cooling Tower 3 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
14811
Cooling Tower 3 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
14821
Cooling Tower 3 - LWT
Vendor range: 10 °C R
Int16°C0.1R
14831
Cooling Tower 3 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
14841
Cooling Tower 4 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
14851
Cooling Tower 4 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
14861
Cooling Tower 4 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
14871
Cooling Tower 4 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
14881
Cooling Tower 4 - LWT
Vendor range: 10 °C R
Int16°C0.1R
14891
Cooling Tower 4 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
14901
Cooling Tower 5 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
14911
Cooling Tower 5 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
14921
Cooling Tower 5 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
14931
Cooling Tower 5 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
14941
Cooling Tower 5 - LWT
Vendor range: 10 °C R
Int16°C0.1R
14951
Cooling Tower 5 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
14961
Cooling Tower 6 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
14971
Cooling Tower 6 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
14981
Cooling Tower 6 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
14991
Cooling Tower 6 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
15001
Cooling Tower 6 - LWT
Vendor range: 10 °C R
Int16°C0.1R
15011
Cooling Tower 6 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
15021
Cooling Tower 7 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
15031
Cooling Tower 7 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
15041
Cooling Tower 7 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
15051
Cooling Tower 7 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
15061
Cooling Tower 7 - LWT
Vendor range: 10 °C R
Int16°C0.1R
15071
Cooling Tower 7 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
15081
Cooling Tower 8 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
15091
Cooling Tower 8 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
15101
Cooling Tower 8 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
15111
Cooling Tower 8 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
15121
Cooling Tower 8 - LWT
Vendor range: 10 °C R
Int16°C0.1R
15131
Cooling Tower 8 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
15141
Cooling Tower 9 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
15151
Cooling Tower 9 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
15161
Cooling Tower 9 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
15171
Cooling Tower 9 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
15181
Cooling Tower 9 - LWT
Vendor range: 10 °C R
Int16°C0.1R
15191
Cooling Tower 9 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
15201
Cooling Tower 10 - Status
Vendor range: 1 as iCT'Twr1'Status R
UInt16-1R
15211
Cooling Tower 10 - Fan Staus
Vendor range: 1 as iCT'Twr1'FanSta R
UInt16-1R
15221
Cooling Tower 10 - Fan Speed
Vendor range: 1 0…100% R
UInt16%1R
15231
Cooling Tower 10 - Inlet Valve Status
Vendor range: 1 as iCT'Twr1'InVlvSta R
UInt16-1R
15241
Cooling Tower 10 - LWT
Vendor range: 10 °C R
Int16°C0.1R
15251
Cooling Tower 10 - LWT Alarm
Vendor range: 1 0 None R
UInt16-1R
15261
iCT - Clear Alarm
Vendor range: 1 0 --- R/W
UInt16-1RW
15271
iCT - CommError
Vendor range: 1 0 None R
UInt16-1R
15281
iCT - Borads CommError
Vendor range: 1 0 None R
UInt16-1R
15291
Mode Changeover management
Vendor range: 1 0 N/Mngd R
UInt16-1R
15301
Defrost Management
Vendor range: 1 0 N/Mngd R
UInt16-1R
15311
Master - Circuit #1 Defrost
Vendor range: 1 1 None R
UInt16-1R
15321
Master - Circuit #2 Defrost
Vendor range: 1 1 None R
UInt16-1R
15331
Slave #1 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15341
Slave #1 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15351
Slave #2 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15361
Slave #2 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15371
Slave #3 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15381
Slave #3 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15391
Slave #4 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15401
Slave #4 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15411
Slave #5 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15421
Slave #5 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15431
Slave #6 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15441
Slave #6 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15451
Slave #7 - Circuit #1 Defrost
Vendor range: 1 as MasterData'DfrstOpStac1 R
UInt16-1R
15461
Slave #7 - Circuit #2 Defrost
Vendor range: 1 as MasterData'DfrstOpStac2 R
UInt16-1R
15551
iSM01 - Pump Group 1 - Status
Vendor range: 1 0 NULL R
UInt16-1R
15561
iSM01 - Pump Group 2 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15571
iSM01 - Pump Group 3 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15581
iSM01 - Pump Group 4 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15591
iSM02 - Pump Group 1 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15601
iSM03 - Pump Group 2 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15611
iSM02 - Pump Group 3 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15621
iSM02 - Pump Group 4 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15631
iSM03 - Pump Group 1 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15641
iSM03 - Pump Group 2 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15651
iSM03 - Pump Group 3 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15661
iSM02 - Pump Group 4 - Status
Vendor range: 1 as iSM01 - Pump Group 1 - Status R
UInt16-1R
15671
iCM Expanded: BACnet Communication error w/2nd
Vendor range: 1 0 None R
UInt16-1R
15681
iCM Expanded: BACnet Communication error w/1st
Vendor range: 1 0 None R
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Daikin Applied Europe "BAS integration guide - Modbus protocol", document D-EIGOC00210-21_03EN_iCM (11/2023, iCM 5.00), published by the vendor at my.daikin.eu and covering the iCM (option 184) Intelligent Chiller Manager, product codes EKDICMPAB / EKDICMPAL / EKDICMPAM. The iCM is the plant controller that groups several Daikin chillers (plus iPM, iCT and iSM units) under one Modbus interface - it is a different device and a different register map from the MicroTech chiller unit controller in the library's daikin-microtech-iii-chiller seed, whose points sit at 40001-40xxx instead of 41100-41890. Section 4.2 gives the communication module's factory parameters - address 1, parity None, 2 stop bits, baud rate 19200 - which is what the serial block records, and section 4.3 gives the controller's own software option as 19200/None with one stop bit and a site-set address, so the serial block follows the module defaults of 4.2. The integration list's Address column is headed "(4xxxx)", so the printed numbers are the one-based 4xxxx register numbers and addressing is one_based (41100 is stored as 1100). Gain 10 in the list means ten times the engineering value, hence scale 0.1 for those rows. Rows whose range column states a 32-bit count ("0...4294967292" for starts/run hours) are left out because the same list types them as a 16-bit word, and the twelve rows the list marks "Reserved" (zero-filled) are left out as well.