CAREL · Chiller controller

µChiller chiller / heat pump controller Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
115200
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
191
Free-Cooling enable
U068 - Enable Free-Cooling (0=Disabled, 1=Enabled)
UInt16-1RW
221
Capacity request from BMS enable
Hd06 - Enable capacity request from BMS (0=Disabled, 1=Enabled)
UInt16-1RW
461
Source type
S068 - Source type (0=Air, 1=Water)
UInt16-1RW
471
Unit of measure (display and BMS)
UoM - Unit of measure used for Display 2-Row and BMS, not for Applica (0=°C/bar, 1=°F/PSI)
UInt16-1RW
481
BMS port database type
Hd07 - BMS port database type (0= 32bit, 1= 16bit)
UInt16-1RW
541
Unit ON/OFF command from keypad
UnSt - Unit ON/OFF command from keypad (0=OFF 1=ON)
UInt16-1RW
551
Cool/Heat mode from keypad
ModE - Cool/Heat mode from keypad (0=Cool, 1=Heat)
UInt16-1RW
561
Reset active alarms from BMS
RES - Reset active alarms from BMS net (0=NO, 1=Reset)
UInt16-1RW
591
Delete alarms log
ClrH - Delete alarms log (0=No, 1=Yes)
UInt16-1RW
631
Unit ON/OFF command by BMS enable
Hd05 - Enable unit ON/OFF command by BMS net (0=Disabled, 1=Enabled)
UInt16-1RW
641
Unit ON/OFF command from BMS
Unit On/Off command from BMS (0=OFF, 1=ON)
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: CAREL "Chiller - Controller for Chiller / Heat Pump, User Manual", +0300053EN rel. 2.4, 09.10.2023 (the revision the cited URL serves; version=1.16 serves rel. 2.5, 03.10.2024), sections 6.8 (BMS port) and 7 (Supervisor table) (https://www.carel.com/documents/10191/0/+0300053EN/36cc33b9-4225-46cc-91aa-734d126b5dcb?version=1.14). Section 7 defines the supervisor database as Modbus RTU over the controller's RS-485 BMS port with factory settings 115,200 bps, 8 data bits, no parity, 2 stop bits, serial address 1 (parameters Hd00/Hd01/Hd02, section 6.8) and states that the table's "Index" is the address specified in the Modbus frame, so the addresses here are wire addresses and the file declares zero_based addressing. The database is 32-bit per Hd07 default 0, so REAL values are IEEE-754 single precision in two registers and UINT values one register. Register numbers shown in the manual's parameter tables (for example HR 147 = serial address) are the supervisor-table indexes of the same variables. Coil and input-status points are bit-addressed in the controller and are listed as one-register values here. Only a working subset of the supervisor table is included: the temperature/pressure probes and alarms that a first integration needs, plus the BMS-port settings. 32-bit hour counters and the secondary-board registers are left out, as is HR 331 (BMS_PwrReq, the BMS capacity request), which section 7.2 does list as a REAL written to two registers big-endian without swap - it is a scope choice, not a missing data type.