All devices

Carlo Gavazzi · Energy meter

EM111 / EM112 / ET112 Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
Voltage L-N
Int32V0.1R
22
Current
Int32A0.001R
42
Active power
Int32W0.1R
62
Apparent power
Int32VA0.1R
82
Reactive power
Int32var0.1R
102
Active power demand
Int32W0.1R
122
Active power demand peak
Int32W0.1R
141
Power factor
Int16-0.001R
151
Frequency
Int16Hz0.1R
162
Active energy imported, total
Int32kWh0.1R
182
Reactive energy imported, total
Int32kvarh0.1R
202
Active energy imported, partial
Int32kWh0.1R
222
Reactive energy imported, partial
Int32kvarh0.1R
242
Active energy imported, tariff 1
Int32kWh0.1R
262
Active energy imported, tariff 2
Int32kWh0.1R
322
Active energy exported, total
Int32kWh0.1R
342
Reactive energy exported, total
Int32kvarh0.1R
442
Hour counter
Only available on ET112.
Int32h0.01R
2562
Current, system
Int32A0.001R
2582
Voltage L-N, system
Int32V0.1R
2622
Active power, system
Int32W0.1R
2642
Apparent power, system
Int32VA0.1R
2662
Reactive power, system
Int32var0.1R
2682
Power factor, system
Int32-0.001R
2722
Frequency, system
Int32Hz0.1R
2742
Active energy imported, total (second copy)
Int32kWh0.1R
2762
Reactive energy imported, total (second copy)
Int32kvarh0.1R
2782
Active energy exported, total (second copy)
Int32kWh0.1R
2802
Reactive energy exported, total (second copy)
Int32kvarh0.1R
2822
Active power demand, system
Int32W0.1R
2842
Active power demand peak, system
Int32W0.1R
3282
Active energy imported, partial (second copy)
Int32kWh0.1R
3302
Reactive energy imported, partial (second copy)
Int32kvarh0.1R
3382
Active energy imported, tariff 1 (second copy)
Int32kWh0.1R
3402
Active energy imported, tariff 2 (second copy)
Int32kWh0.1R

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (slave address 1, 9600 bps, 8N1). Source: Carlo Gavazzi 'EM111 MV5 - Modbus serial protocol' rev. 2.12, tables 2.4-1, 2.4-2 and 2.7-6. Carlo Gavazzi stores 32-bit values least significant word first (LSW -> MSW), hence the LowFirst word order. Function codes 03 and 04 return the same values. The register bank at 0x0100 repeats the same measurements except the hour counter. Values are transmitted in tenths (V, W, var, VA, kWh, kvarh) or thousandths (A, PF), which the scale factors convert.