Carlo Gavazzi · Energy meter

EM210 (AV5 / MV5 modular energy meter) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
Voltage L1-N
Int32V0.1R
22
Voltage L2-N
Int32V0.1R
42
Voltage L3-N
Int32V0.1R
62
Voltage L1-L2
Int32V0.1R
82
Voltage L2-L3
Int32V0.1R
102
Voltage L3-L1
Int32V0.1R
122
Current L1
Int32A0.001R
142
Current L2
Int32A0.001R
162
Current L3
Int32A0.001R
182
Active power L1
Int32W0.1R
202
Active power L2
Int32W0.1R
222
Active power L3
Int32W0.1R
242
Apparent power L1
Int32VA0.1R
262
Apparent power L2
Int32VA0.1R
282
Apparent power L3
Int32VA0.1R
302
Reactive power L1
Int32var0.1R
322
Reactive power L2
Int32var0.1R
342
Reactive power L3
Int32var0.1R
362
Voltage L-N, system
Int32V0.1R
382
Voltage L-L, system
Int32V0.1R
402
Active power, system
Int32W0.1R
422
Apparent power, system
Int32VA0.1R
442
Reactive power, system
Int32var0.1R
461
Power factor L1
Int16-0.001R
471
Power factor L2
Int16-0.001R
481
Power factor L3
Int16-0.001R
491
Power factor, system
Int16-0.001R
501
Phase sequence
-1 corresponds to L1-L3-L2, 0 to L1-L2-L3; meaningful only in a three-phase system.
Int16-1R
511
Frequency
Int16Hz1R
522
kWh imported, total
Int32kWh0.1R
542
kvarh imported, total
Int32kvarh0.1R
782
kWh exported, total
Int32kWh0.1R
902
Hour counter
Int32h0.01R
922
Hour counter, negative
Int32h0.01R
1302
THD current L1
16th harmonic THD.
Int32%0.01R
1322
THD current L2
16th harmonic THD.
Int32%0.01R
1342
THD current L3
16th harmonic THD.
Int32%0.01R
1382
THD voltage L1-N
16th harmonic THD.
Int32%0.01R
1402
THD voltage L2-N
16th harmonic THD.
Int32%0.01R
1422
THD voltage L3-N
16th harmonic THD.
Int32%0.01R
1462
THD voltage L1-L2
16th harmonic THD.
Int32%0.01R
1482
THD voltage L2-L3
16th harmonic THD.
Int32%0.01R
1502
THD voltage L3-L1
16th harmonic THD.
Int32%0.01R
1522
Neutral current
Int32A0.001R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above. Source: Carlo Gavazzi "EM210 - Communication Protocol", version 4 revision 1 (18 May 2016), section 2.3 "Instantaneous variables and meters (grouped by variable type)", table 2.3-1, and section 2.8 table 2.8-10 (serial port configuration menu). The document numbers registers both in "Modicom" (6-digit) and "physical" (wire) form; the physical addresses are used here as wire addresses. Word order is LSW->MSW for every 32-bit row and the byte order inside each word is MSB->LSB (section 2.1), hence LowFirst. The values are read with function code 03 or 04. The factory serial settings are the documented defaults of registers 2000h/2001h/2002h: 9.6 kbps, no parity, 1 stop bit, 8 data bits; the RS-485 node address (register 2000h, range 1...247) is set per site and the meter is delivered at address 1. Scaling follows the table's "Value weight" column: voltages x0.1, currents x0.001, powers x0.1, power factor x0.001, energies x0.1 kWh/kvarh, hour counters x0.01 h, THD x0.01 %. The two system THD rows (300137h and 300145h in the document) are deliberately not listed: the meter does not calculate them and always answers 0. The section 2.4 table repeats the same measurements grouped by phase; only the section 2.3 rows are listed so no value appears twice. Writable setup registers (password, system/CT/VT configuration, serial port, pulse output, reset commands) are documented in section 2.8.