All devices

Brainboxes · Remote I/O

ED-588 Ethernet remote I/O (8 digital inputs + 8 digital outputs) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Digital output 1
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
11
Digital output 2
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
21
Digital output 3
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
31
Digital output 4
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
41
Digital output 5
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
51
Digital output 6
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
61
Digital output 7
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
71
Digital output 8
Logical address 0x0000-0x0007; the ED-588 table gives function codes 1, 5 and 15 for 'Set/read digital outputs', so the same bit can be read as a coil as well as written.
Binary-1RW
321
Digital input 1 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
331
Digital input 2 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
341
Digital input 3 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
351
Digital input 4 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
361
Digital input 5 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
371
Digital input 6 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
381
Digital input 7 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
391
Digital input 8 state (as a coil)
Logical address 0x0020-0x0027, read with function 01 (the table's 'Read digital inputs' row uses the coil area). The same state is available as a discrete input at 0x0000.
Binary-1R
5121
Clear digital input 1 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5131
Clear digital input 2 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5141
Clear digital input 3 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5151
Clear digital input 4 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5161
Clear digital input 5 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5171
Clear digital input 6 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5181
Clear digital input 7 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW
5191
Clear digital input 8 counter
Logical address 0x0200-0x0207, written with function 05/15 to clear that input's counter; the table types this block 'Coil' with function codes 5 and 15.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Brainboxes documentation, 'ED Modbus Product Data Tables' (https://docs.brainboxes.com/reference/protocols/ed-modbus-product-data-tables), section ED-588, which prints every function with its Modbus access type, function codes, logical address and the 984-style and IEC 61131 addresses; plus 'ED Modbus Data Formats' (https://docs.brainboxes.com/reference/protocols/ed-modbus-data-formats) for the data-table widths, and the ED-588 product page (https://www.brainboxes.com/product/remote-io/digital/ed-588) and ED Range Manual for the 8 digital inputs and 8 outputs. The seed stores the logical-address column (0x0000-0x0007 outputs, 0x0020-0x0027 input states and output bit field, 0x0200-0x0207 counter-clear coils, 0x0400-0x0407 overload flags) and declares zero_based. Brainboxes documents Modbus TCP as the protocol of the ED range but prints no TCP port or unit identifier in these tables: port 502 is the Modbus TCP default and unit identifier 1 is a declared placeholder, because a Modbus TCP server may ignore the unit field. The same inputs appear both as coils (function 01) and as discrete inputs (function 02), and the counters both as input registers (function 04) and as holding registers (function 03), exactly as the vendor table lists them. The counter-clear coils are writable bits; reading them returns the coil state. The Modbus counter registers are 16 bits: the data-format page defines input and holding registers as 16-bit integers, and the ED-588 table gives exactly one register per counter in each area (30001-30008 and 40001-40008), with no second word anywhere in the map.