ADAM-4050 / ADAM-4050-F (15/16-channel digital I/O) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Digital input 0 signal
0 = off, 1 = on (coil reference 00001).
Binary-1R
11
Digital input 1 signal
0 = off, 1 = on (coil reference 00002).
Binary-1R
21
Digital input 2 signal
0 = off, 1 = on (coil reference 00003).
Binary-1R
31
Digital input 3 signal
0 = off, 1 = on (coil reference 00004).
Binary-1R
41
Digital input 4 signal
0 = off, 1 = on (coil reference 00005).
Binary-1R
51
Digital input 5 signal
0 = off, 1 = on (coil reference 00006).
Binary-1R
61
Digital input 6 signal
0 = off, 1 = on (coil reference 00007).
Binary-1R
71
Digital input 7 signal
0 = off, 1 = on (coil reference 00008).
Binary-1R
161
Digital output 0 value
0 = off, 1 = on (coil reference 00017).
Binary-1RW
171
Digital output 1 value
0 = off, 1 = on (coil reference 00018).
Binary-1RW
181
Digital output 2 value
0 = off, 1 = on (coil reference 00019).
Binary-1RW
191
Digital output 3 value
0 = off, 1 = on (coil reference 00020).
Binary-1RW
201
Digital output 4 value
0 = off, 1 = on (coil reference 00021).
Binary-1RW
211
Digital output 5 value
0 = off, 1 = on (coil reference 00022).
Binary-1RW
221
Digital output 6 value
0 = off, 1 = on (coil reference 00023).
Binary-1RW
231
Digital output 7 value
0 = off, 1 = on (coil reference 00024).
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 remote I/O: the module reaches Modbus Connect through a Modbus RTU-to-TCP gateway, and the serial block holds the factory settings the gateway must use. Addressing: the manual's Modbus mapping table prints Modbus reference numbers ("ADDR 0X" 00001..., "ADDR 4X" 40001...) and this seed stores the equivalent zero-based wire addresses (reference minus one), as the ADAM-6000 seeds in this library do. Source: Advantech "ADAM-4000 Series User Manual" Ed.9 (2023), Appendix G.1 "ADAM-4000 I/O Modbus Mapping Table", item 7 "ADAM-4050 15 or *16-ch Digital I/O Module" (manual page 268); factory communication settings from chapter 2.2 "Default Factory Settings" (baud rate 9600 bit/s, address 01 hexadecimal) and Appendix H.1 (initial COM settings 9600 baud, N-8-1). The ADAM-4050 has seven digital inputs and eight digital outputs; the eighth input (channel 7) exists only on the ADAM-4050-F, as the table's footnote "* New Input for ADAM-4050-F" states. The module has no analog channels and no counter block in this map. A Modbus-version module can leave the factory set to the ADAM ASCII protocol; Appendix H.1 documents switching it to Modbus with the Adam/Apax .NET utility before the map above applies.