TESVOLT · Battery storage controller

TESVOLT Energy Manager 2.0 marketer interface (TS HV storage systems) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first

Register map

AddressCountNameTypeUnitScaleAccess
02
Instantaneous power at the grid connection point
32-bit value, low word first: address 0 is the low word, 1 the high word.
Int32W1R
32
Maximum power value (nominal power) specified by the grid operator
Low word first (3 = low, 4 = high).
Int32W1R
52
Instantaneous PV power
Low word first.
Int32W1R
72
Instantaneous self-consumption power
Low word first.
Int32W1R
92
Battery state of charge
IEEE-754 single, low word first.
Float32%1R
112
Battery charge/discharge power
Positive = charging, negative = discharging; low word first.
Int32W1R
202
Mirrored desired value for PV power
Value the energy manager has accepted as PV setpoint; low word first.
Int32W1R
222
Mirrored desired value for grid-connection power
Low word first.
Int32W1R
241
Mirrored control mode of the grid connection
0 = local control, 1 = control by the marketer.
UInt16-1R
252
Mirrored desired value for the battery power
Low word first.
Int32W1R
302
Power of the PV plant
Low word first.
Int32W1R
322
Maximum possible charging power
Low word first.
Int32W1R
342
Maximum possible discharging power
Low word first.
Int32W1R
362
Storage capacity of the battery storage
Low word first.
UInt32Wh1R
1001
System error flags
Bit field: 0x0000 none, 0x0001 PV system error, 0x0002 battery storage system error, 0x0004 grid-connection activity recording error, 0x0008 PV activity recording error, 0x0010 self-consumption activity recording error, 0x0020 SOC activity recording error.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: TESVOLT AG "Marketer interface - ModBus specifications" for the TESVOLT Energy Manager, revision H.01, 03/2025 (applies to TESVOLT Energy Manager version 2.0 or higher), vendor-hosted at https://www.tesvolt.com/_media/05%20SERVICE/03%20Downloads/Energiemanagementsystem/EN_TESVOLT_Energy_Manager_MarketerInterfaceModbusSpecifications_20250320.pdf. The document gives two address columns, ADDRESS (0-based) and REGISTRY (ADDRESS + 1); the ADDRESS column is stored here and the map is declared zero_based. Every 32-bit row is one value split over two holding/input registers, and the document states in each description which register carries the low and which the high word - low word first - so the seed declares word_order LowFirst. Single-register rows follow standard big-endian. The power values are signed in practice (charge/discharge, import/export), hence Int32; the storage capacity is unsigned. Placeholders, because this document does not state them: the Modbus TCP port (502 assumed) and the unit identifier (1 assumed) - the server is the Energy Manager, so both must be set to whatever the device's Modbus TCP server is configured with. The interface described is the marketer/remote-control interface (PV curtailment, grid-connection and battery setpoints plus measured values), not the complete device map; TESVOLT's internal registers are not published. The watchdog registers 2, 7 and 12 are writable and are listed with their operating rule. Error register 100 is a bit field, documented in its description.