WPM / WPM 3 / WPM 3i heat pump manager via ISG web Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
5071
Outside temperature
Int16°C0.1R
5081
Actual temperature heating circuit 1
Room temperature of heating circuit 1 (WPMsystem, WPM 3).
Int16°C0.1R
5091
Set temperature heating circuit 1
Int16°C0.1R
5111
Actual temperature heating circuit 2
Int16°C0.1R
5121
Set temperature heating circuit 2
Int16°C0.1R
5131
Actual flow temperature heat pump
Int16°C0.1R
5141
Actual flow temperature additional heat stage
Int16°C0.1R
5151
Actual flow temperature
Int16°C0.1R
5161
Actual return temperature
Int16°C0.1R
5181
Actual buffer temperature
Int16°C0.1R
5191
Set buffer temperature
Int16°C0.1R
5211
Flow rate
Int16l/min0.1R
5221
Actual DHW temperature
Int16°C0.1R
5231
Set DHW temperature
Int16°C0.1R
25011
Operating status
Bit-coded: B0 = heating circuit 1 pump, B1 = heating circuit 2 pump, B2 = heat-up program, B3 = additional heat stages running, B4 = heat pump in heating mode, B5 = heat pump in DHW mode, B6 = compressor running, B7 = summer mode active, B8 = cooling mode active, B9 = at least one heat pump in defrost, B10 = silent mode 1 active, B11 = silent mode 2 active (heat pump off).
UInt16-1R
25021
Power-off (utility lock)
Bit-coded: B0 = power-off active (EVU lock).
UInt16-1R
25031
Operating status compressors and buffer pumps
Bit-coded: B0-B5 = compressor 1-6, B6-B11 = buffer charging pump 1-6.
UInt16-1R
25041
Fault status
0 = no fault, 1 = system fault. Faults can only be acknowledged on the ISG service interface, not over Modbus.
UInt16-1R
25061
Defrost active
0 = off, 1 = defrost initiated.
UInt16-1R
25071
Active fault number
UInt16-1R
25091
Heating circuit pump 1
0 = off, 1 = on. Only available on the WPMsystem.
UInt16-1R
25151
Source pump
0 = off, 1 = on. Only available on the WPM 3.
UInt16-1R
36801
Inverter power consumption, heat pump 1
Electrical input power of inverter heat pump 1; the WPM 3 without inverter does not provide it.
Int16kW0.1R
50011
SG Ready operating state
1 = heating system must not start (frost protection assured), 2 = standard operation, 3 = accelerated mode with raised heating and DHW temperatures, 4 = immediate maximum heating and DHW temperatures.
UInt16-1R

Notes

Source: STIEBEL ELTRON, "Software documentation - Modbus TCP/IP" for the ISG web / ISG plus (document 321798-44755-9770, multilingual, sections 6 and 7: Modbus system values for heat pumps with WPM and further registers). The ISG is the Modbus TCP server on port 502 with the permanent slave ID 1; system values are read from input registers (function code 04) and system parameters from holding registers (function code 03/06/16). ISG addressing is 1-based, hence one_based above: the guide's register 501 is wire address 500. Values are 16-bit; data type 2 = signed x0.1, 7 = signed x0.01, 6 and 8 = unsigned integer, which the scale factors above reflect. Objects that are not available on the connected appliance return the substitute value 32768 (0x8000), so a reading of -3276.8 °C after scaling means "not available". Availability depends on the appliance family: the WPMsystem, WPM 3 and WPM 3i expose different subsets, and the guide marks each row with the families that support it. The Modbus TCP/IP function is a software extension for the ISG (part number 316303) and cannot be combined with other ISG interfaces except read-only access next to the EMI energy management extension. Faults cannot be acknowledged over Modbus, only in the ISG service interface; the heat pump energy and runtime blocks (3501-3560 and up) are not included because their row alignment is only partly unambiguous in the published table.