Integ ONE GEN3 hybrid inverter (with its rebadges) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
255
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
109942
Meter phase A power
Signed; the cited template negates it, so a positive register value means export.
Int32W-1R
109962
Meter phase B power
Int32W-1R
109982
Meter phase C power
Int32W-1R
110002
Total power on meter
Signed; the cited template negates it, so a positive register value means export.
Int32W-1R
110282
PV input total power
UInt32W1R
302582
Battery power
Int32W1R
311022
Grid energy injected, total
UInt32kWh0.1R
311042
Grid energy purchased, total
UInt32kWh0.1R
311082
Battery energy charged, total
UInt32kWh0.1R
311102
Battery energy discharged, total
UInt32kWh0.1R
311122
PV input total energy
UInt32kWh0.1R
330001
Battery state of charge
UInt16%0.01R
500001
Battery work mode
The cited template writes 257 for normal, 258 for eco (hold) and 259 for UPS (charge).
UInt16-1RW
525031
On-grid battery end state of charge
Read by the template to seed its minimum-SOC setting; it is not written by it.
UInt16%0.1R
525061
Battery maximum state of charge
Present on newer firmware only, per the cited template.
UInt16%0.1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: the evcc meter template https://raw.githubusercontent.com/evcc-io/evcc/master/templates/definition/meter/solinteg-gen3.yaml, used as a secondary source - no Solinteg register document was retrieved. The template covers the GEN3 hardware sold as Solinteg Integ ONE GEN3, M-TEC Energy Butler GEN3, Wattsonic 3p AIO GEN3, Sunways STH GEN3, A-Tronix Hybridpower AX2 GEN3 and SunEnergyBox SEB GEN3. It offers both RS-485 and TCP access with unit ID 255; this seed records the TCP path (port 502, unit ID 255), which is the one that needs no serial framing and is therefore the one this file can state without guessing. All values are holding registers (function code 3; the write at 50000 is a single-register write). The GEN2 generation has a different map (evcc template solinteg-gen2, unit ID 247) and is not covered here, because no public source states its factory RS-485 serial settings; see the delivery record for that skip. The template's battery-control writes and the min/max SOC services are the only writes it makes, and the two read-only SOC limit rows are included so on-site verification can compare them. Values the template does not publish (per-string PV, inverter temperatures, fault codes) are absent rather than guessed.