HGM6100N series (HGM6110N / HGM6120N, incl. -4G and CAN variants) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Common alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
11
Common warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
21
Common shutdown alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
31
Remote mode
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
61
Mains on load
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
71
Generator on load
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
81
Emergency stop
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
91
Over speed alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
101
Under speed alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
111
Speed signal loss shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
121
Over frequency alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
131
Under frequency alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
141
Over voltage alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
151
Under voltage alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
161
Generator over current shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
171
Crank failure
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
181
High water temperature alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
191
Low oil pressure alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
201
Frequency loss alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
211
Input port shutdown alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
221
Low fuel level shutdown alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
231
Low coolant shutdown alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
241
High water temperature warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
251
Low oil pressure warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
261
Generator over current warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
271
Stop failure warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
281
Low oil level warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
291
Charging failure warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
301
Battery under voltage warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
311
Battery over voltage warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
321
Input port warning alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
331
Speed signal loss warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
341
Low coolant warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
351
Temperature sensor open warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
361
Oil pressure sensor open warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
371
Maintenance time due warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
381
Charger failed to charge warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
391
Over power warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
401
System in test mode
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
411
System in auto mode
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
421
System in manual mode
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
431
System in stop mode
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
441
Temperature sensor open shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
451
Oil pressure sensor open shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
461
Maintenance time due shut alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
471
Over power shutdown alarm
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
481
Emergency stop input
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
491
Configurable input port 1
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
501
Configurable input port 2
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
511
Configurable input port 3
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
521
Configurable input port 4
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
531
Configurable input port 5
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
561
Starting relay output
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
571
Fuel relay output
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
581
Configurable output port 1
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
591
Configurable output port 2
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
601
Configurable output port 3
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
611
Configurable output port 4
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
641
Mains failure
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
651
Mains normal
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
661
Mains over voltage
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
671
Mains under voltage
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
681
Mains loss of phase
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
721
Generator normal
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
731
Generator over voltage
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
741
Generator under voltage
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
751
Generator over frequency
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
761
Generator under frequency
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
771
Generator over current warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
781
In scheduled not run
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
801
ECU shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
811
ECU communication failure alarm shutdown
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
881
ECU warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R
891
GSM communication failure warning
1 = active, 0 = inactive (function code 01 mapping).
Binary-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Diesel genset controller with an RS-485 port: reach it through a Modbus RTU-to-TCP gateway. Factory serial settings: 9600 bps (parameter 106 RS485 Baud Rate, factory value 2 = 9600 bps in the user manual), 8 data bits, no parity, 2 stop bits (the protocol document's data-frame table), slave address 1 (parameter 61 Module Address, factory value 1). Sources: SmartGen "HGM6100-4G Genset Controller Communication Protocol" (https://www.smartgen.cn/yun/data/download/HGM6100-4G_Protocol_en.pdf), Table 20 Function Code 01H coil map (pages 11-13) and Table 21 Function Code 03H register map (pages 14-16); serial defaults and the display units of the measured items from "HGM6100N Series Genset Controller User Manual" (https://www.smartgen.cn/yun/data/download/HGM6110N_6120N_6110NC_6120NC_6110CAN_6120CAN_en.pdf), parameter list page 20-23. Addressing: both tables list plain decimal addresses starting at 0000, and the protocol examples address "starting address 0000", so the numbers are stored unchanged as zero-based wire addresses (0010 is register 10, not 16). Scaling: the protocol table marks the scaled values in its Description column, *10 becomes 0.1 and *100 becomes 0.01; unscaled values keep 1. 32-bit values are listed as a single item with a byte count of 4 and store high word first. Deliberate omissions: the vendor's write-command coil table (Table 22, addresses 0000H-0006H for remote start/stop/auto/manual and the C/O keys) is not listed because it reuses the same coil addresses as the read-only status map and the coil area here carries only R/RW entries, so it cannot be expressed without inventing a separate address space. Reserved rows are omitted. The accumulated-fuel-consumption, SCM-temperature, controller-model, controller-time and GPS/MCUID rows (0068-0078 and 0087-0116) are left out: the vendor PDF's byte-count and address columns for that block are misprinted (e.g. "84Bytes" for the day field), so those rows cannot be transcribed reliably.