All devices

Siemens · EV charger

VersiCharge AC series wallbox Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
2
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
38400
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
05
Manufacturer
Manufacturer name as ASCII.
Ascii-1R
52
Production date
Word 1 = year (YYYY), word 2 = month and day (MMDD); derived from the serial number.
UInt32-1R
75
Serial number
Product serial number.
Ascii-1R
1210
MLFB
Product catalog number.
Ascii-1R
221
Platform type
1 = residential, 2 = commercial, 3 = ERK.
UInt16-1R
241
Number of outlets
1 = one outlet, 2 = two outlets.
UInt16-1R
251
Outlet type
Outlet hardware: 0 = left socket type 2, 1 = left cable with type 2 plug (7 m), 2 = left socket with shutters type 2 (France), 3 = left cable with type 1 plug (7 m), 4 = left cable with GB/T plug (6 m), 5 = front SAE J1772 (20 ft), 6 = front SAE J1772 (25 ft), 7 = right socket type 2, 8 = right cable with type 2 plug (7 m), 9 = right type 2 cover with shutter and E-plug, 10 = right cable with type 1 plug (7 m), 11 = right type 2 cover with shutter and F-plug, 12 = right type 2 cover with shutter only, 13 = reserve, 14 = left and right socket type 2, 15 = left and right cable with type 2 plug (7 m), 16 = left and right type 2 cover (France), 17 = left and right cable with type 1 plug (7 m), 18 = left and right cable with GB/T plug, 19 = CCS1/J1772 (25 ft), 20/21 = reserve, 22 = blocked.
UInt16-1R
261
Delay button status
Charging delay set with the button on the charger: 0 = no delay, 1 = 2 h, 2 = 4 h, 3 = 6 h, 4 = 8 h. Read-only in the -AL revision (RO, FC 03).
UInt16-1R
271
Connectivity
0 = not commissioned, 1 = Wi-Fi, 2 = cellular, 3 = Ethernet.
UInt16-1R
281
Rated current
Maximum rated current configured in the system configuration, 6 to 80 A.
UInt16A1R
291
Installation current
Installation current from the DIP switch, 6 to 80 A; the effective limit is the minimum of this value and the rated current.
UInt16A1R
301
Meter type
0 = no metering, 1 = basic, 2 = ANSI, 3 = MID, 4 = integrated MID meter, 5 = Eichrecht-conform meter, 7 = CMC meter, 9 = onboard CMC, 25 = blocked.
UInt16-1R
315
Firmware version
Firmware version, for example 2.118.
Ascii-1R
365
Maintenance version
MO version, for example 4.3.5.
Ascii-1R
411
Modbus table version
Version of this Modbus table, 1, 2, 3, 4, ...
UInt16-1R
791
RFID activation status
0 = RFID authorization disabled, 1 = RFID authorization enabled.
UInt16-1RW
16021
PCBA temperature
Board temperature.
Int16°C1R
16331
Max charging current, sum
Maximum charging current for all phases together. The document encodes two scales in this register: values <= 100 are interpreted as A, values > 100 as 0.01 A (raw 1632 means 16.32 A). This schema applies one factor per row, so the row keeps factor 1 and values above 100 have to be divided by 100 by hand.
UInt16A1RW
16421
Charger type
The document titles this row "Charger" and marks it RO (FC 03): 0 = 1-phase charger, 1 = 3-phase charger.
UInt16-1R
16471
Charging current L1
Actual RMS current of phase 1.
UInt16A1R
16481
Charging current L2
Actual RMS current of phase 2.
UInt16A1R
16491
Charging current L3
Actual RMS current of phase 3.
UInt16A1R
16501
Charging current, sum
Actual RMS current of all phases.
UInt16A1R
16511
Charging voltage L1-N
Actual RMS voltage of phase 1 to neutral.
UInt16V1R
16521
Charging voltage L2-N
Actual RMS voltage of phase 2 to neutral.
UInt16V1R
16531
Charging voltage L3-N
Actual RMS voltage of phase 3 to neutral.
UInt16V1R
16601
Fallback current, sum
Current applied when the Modbus connection is lost, 0 or 6 to 80 A.
UInt16A1RW
16611
Fallback time
Time span between the loss of the Modbus connection and the fallback current, 0 or 60 to 600 s.
UInt16s1RW
16621
Charging power L1
Active power of phase 1.
UInt16W1R
16631
Charging power L2
Active power of phase 2.
UInt16W1R
16641
Charging power L3
Active power of phase 3.
UInt16W1R
16651
Charging power, sum
Active power of all phases.
UInt16W1R
16701
Apparent power L1
Apparent power of phase 1.
UInt16VA1R
16711
Apparent power L2
Apparent power of phase 2.
UInt16VA1R
16721
Apparent power L3
Apparent power of phase 3.
UInt16VA1R
16731
Apparent power, sum
Apparent power of all phases.
UInt16VA1R
16741
Reactive power L1
Reactive power of phase 1, signed (Int16) in the document. The document's unit column reads "reactive volt-amperes".
Int16var1R
16751
Reactive power L2
Reactive power of phase 2, signed (Int16) in the document.
Int16var1R
16761
Reactive power L3
Reactive power of phase 3, signed (Int16) in the document.
Int16var1R
16771
Reactive power, sum
Reactive power of all phases.
UInt16var1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Siemens AG, "VERSICHARGE AC SERIES - ModBus Map", document A5E52200882-AL, 02/2025, valid for firmware V2.136.14 or higher, published on the Siemens support page given as supplier_url. Page 1 fixes the transport: Modbus RTU 38400 bit/s, 8 data bits, even parity, 1 stop bit, default device address 2, and a Modbus TCP server on port 502 that cannot be changed; this seed records the RTU path (the same registers answer over TCP). Only holding registers are used: every row is read with FC 03, writable rows take FC 06 / FC 16. Addressing: the table prints each register as external 4xxxx number and as internal address; the internal column is the wire address (40001 = 0), which is what this file lists with zero_based. Two rows of the earlier -AA revision are not in -AL and are not seeded: 23 (time zone) and 1629 (pause). Row 1642 is read-only in -AL ("Charger": 0 = 1-phase charger, 1 = 3-phase charger) and row 26 (delay button status) is read-only as well. Row 1633 carries two scales: values <= 100 are A, values > 100 are 0.01 A; one factor per row is possible here, so 1633 keeps factor 1 and its description carries the rule. Left out on purpose: the RFID card write block 80-86, the whitelist 87-337 and the admin whitelist, the BUFFER blocks (42-78, 355-404, 1604-1628), the power-factor rows 1666-1669 and the real-energy group 1692-1693, both of which -AL does tabulate (factor 0,001 and no unit on the power factors; a clean Uint32 Watthours row for the energy), so leaving them out is a deliberate scope choice, not a documentation gap. Units are the document's own words ("Amp", "Volt", "Watt", "Second", "volt-amps", "reactive volt-amperes"); the factor column only holds 1 or 0,1, so the rows included here have scale 1. The unit column is right-aligned and its cells sit one row off from 1647 in plain text, so rows were paired with their units by word coordinates.