Schneider Electric · EV charger

EVlink Pro AC / Charge Pro Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
255
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
11
EV state
0 = state E (0 V), 1 = state F, not available (-12 V), 2 = A1 available, not ready (12 V), 3 = B1 EV connected, not ready (9 V), 4 = C1 charging, stop requested by EVSE (6 V), 5 = D1 charging with ventilation required, stop requested by EVSE (3 V), 6 = A2 available, ready (12 V PWM), 7 = B2 EV connected, ready (9 V PWM), 8 = C2 charging (6 V PWM), 9 = D2 charging with ventilation required (3 V PWM), 10 = control pilot wire invalid, 11 = control pilot wire symmetric, fault on the control circuit.
UInt16-1R
1501
OCPP status
0 = init, 1 = available, 2 = preparing, 3 = charging, 4 = suspended EV, 5 = suspended EVSE, 6 = finishing, 7 = reserved, 8 = unavailable, 9 = faulted.
UInt16-1R
11501
EV presence
0 = EV not present, 1 = EV present. Updated only when not charging.
UInt16-1R
12121
Global release version, major
UInt16-1R
12131
Global release version, minor
UInt16-1R
12141
Global release version, build
UInt16-1R
29992
Current phase 1
Float32A1R
30012
Current phase 2
Float32A1R
30032
Current phase 3
Float32A1R
30092
Current phase, average
Float32A1R
30272
Voltage phase 1
Float32V1R
30292
Voltage phase 2
Float32V1R
30312
Voltage phase 3
Float32V1R
30352
Voltage phase, average
Float32V1R
30532
Active power phase 1
Float32kW1R
30552
Active power phase 2
Float32kW1R
30572
Active power phase 3
Float32kW1R
30592
Active power, total
Float32kW1R
30752
Apparent power, total
Float32kVA1R
30832
Power factor
Float32-1R
31092
Frequency
Float32Hz1R
40001
Lifebit
Communication watchdog. The charging station sets it to 1, the client resets it to 0; writing 2 deactivates the lifebit. When activated, communication counts as lost if the lifebit is not refreshed within the configured timeout.
UInt16-1RW
40011
Set command
3 = stop charge, 7 = suspend charge, 8 = restart charge, 9 = reboot, 40 = set available, 41 = set unavailable. The station resets the register to 0 afterwards and reports errors in 4002.
UInt16-1RW
40022
Command status
Status of the previous remote command.
UInt32-1R
40041
Set point
Remote energy management setpoint in amps, 0 to 32 A; 99 means no charge in progress. A setpoint change is applied within 15 s.
UInt16A1RW
40051
Degraded set point, single phase
Setpoint applied when the Modbus communication is lost, configured via eSetup. The guide's table marks 4005/4006 read-only, while its text says they are written by the external system; access is RW here to match the text.
UInt16A1RW
40061
Degraded set point, three phase
Setpoint applied when the Modbus communication is lost, configured via eSetup; see the note on 4005.
UInt16A1RW
40072
Contactor charging time
Duration since the contactor closed.
UInt32s1R
40092
Session charging time
Duration since the transaction started.
UInt32s1R
40111
Last stop cause
0 = none, 1 = emergency stop, 2 = EV disconnected, 3 = hard reset, 4 = local, 5 = other, 6 = power loss, 7 = reboot, 8 = remote, 9 = soft reset, 10 = unlock command, 11 = de-authorized.
UInt16-1R
40122
Session energy
Consumed energy during the charging session in Wh.
UInt32kWh0.001R
40202
Error group bitfield
Currently raised error groups, one bit per group.
UInt32-1R
40222
Error code bitfield
Currently raised error codes, one bit per error.
UInt32-1R
40241
Last event 0: event code
UInt16-1R
40251
Last event 0: start time
UInt16s1R
40261
Last event 0: end time
UInt16s1R
40271
Last event 1: event code
UInt16-1R
40281
Last event 1: start time
UInt16s1R
40291
Last event 1: end time
UInt16s1R
40301
Last event 2: event code
UInt16-1R
40311
Last event 2: start time
UInt16s1R
40321
Last event 2: end time
UInt16s1R
40331
Last event 3: event code
UInt16-1R
40341
Last event 3: start time
UInt16s1R
40351
Last event 3: end time
UInt16s1R
404010
EVSE model
Two characters per register.
Ascii-1R
406010
EVSE commercial reference
Two characters per register.
Ascii-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Schneider Electric, "EVlink Pro AC - Modbus Connectivity Guide", GEX1969300-04 (06/2023), chapter "Registers" plus the chapters "Supported Commands", "Lifebit" and "EVlink Pro AC Modbus Interface". The guide states that the table lists the registers accessible to the client "on base 0" and that the server ID is 255; its data-format chapter defines SINT32/UINT32 as high word first, so this file uses zero-based addressing with high word first. The PDF was read from a mirror of the vendor document (devicelib.my-gekko.com); the reference and revision are the vendor's own. The guide's section on the Modbus interface says the external system writes the degraded setpoints 4005/4006, so those two rows are RW here even though the register table marks the whole block read-only -- the seed follows the descriptive text and says so in the row descriptions. Left out: "Energy Active TOT" (3203) and "Energy Reactive TOT" (3219), both int64 in the guide, because the app has no 64-bit integer type; session energy (4012, uint32) carries the same value for a charging session. evcc's charger/schneider-v3.go drives the same addresses with function codes 03/06, which is how the table is to be read.