ProMinent · Dosing pump
gamma/ XL (GXLa) solenoid metering pump, control option 'M' (Modbus RTU) Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 20
- Addressing
- 1-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 19200
- Parity
- Even
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 63 | 2 | Modbus endianness pattern Read-only register 63 of the 'Modbus' block: the pump stores the pattern 0xAABBCCDD here so a master can determine the endianness of the Modbus access. The document prints no byte or word order for its 32-bit values, so the seed declares BigEndian + HighFirst and this register is the documented way to verify it on site. | UInt32 | - | 1 | R |
| 1000 | 2 | Status register Bits 2-4 = operating mode (0 stop, 1 manual, 2 contact, 3 batch, 4 analogue), 5 error present, 6 warnings present, 7 manually stopped, 8 stopped, 9 priming, 10 auxiliary operation, 11 pause, 12 field bus mode, 13 metering monitor enabled, 14 batch memory active, 15 calibrated, 16 relay 1 present, 17 relay 2 present, 18 analogue output present, 19 diaphragm rupture option, 20 concentration calculation active, 22 cavitation detected, 23 air in the dosing head, 24 back pressure too high, 25 back pressure too low, 26 bleeding; bits 0, 1, 21 and 27-31 are reserved. | UInt32 | - | 1 | R |
| 1002 | 2 | Error flags (1st register) Bit 0 configuration data error (system), 1 power input too low, 2 power input too high, 3 level error, 4 diaphragm rupture, 5 metering monitor error, 6 position determination error, 7 temperature too high, 8 initialisation error (system), 9 drive error, 10 invalid metering parameter, 11 overpressure, 12 overcurrent, 13 undervoltage, 14 air in the head, 15 bleeding unsuccessful, 16 overflow batch memory, 17 input current smaller than limit, 18 input current larger than limit, 19 negative pressure, 20 no pump-to-module connection, 21 no pump-to-master connection, 22 internal CAN bus error. | UInt32 | - | 1 | R |
| 1004 | 2 | Error flags (2nd register) The document prints bits 0-31 as reserved for this register. | UInt32 | - | 1 | R |
| 1006 | 2 | Warning flags Warning bit field, beginning with bit 0 = level warning. | UInt32 | - | 1 | R |
| 1008 | 1 | Actual stroke rate Range 1 to the maximum possible stroke rate. | UInt16 | strokes/h | 1 | R |
| 1009 | 2 | Actual stroke length Stroke length actually applied, 1-100 %. | Float32 | % | 1 | R |
| 1011 | 1 | Maximum possible stroke rate Determined by the device context, e.g. the set suction stroke. | UInt16 | strokes/h | 1 | R |
| 1018 | 2 | Actual capacity Actual feed rate; the unit depends on the dosing head fitted and the device context. | Float32 | - | 1 | R |
| 1020 | 2 | Maximum possible capacity Determined by the dosing head fitted and the device context. | Float32 | - | 1 | R |
| 1024 | 2 | Actual concentration If the actual concentration is >= 0.1 % it is displayed in %, otherwise in ppm. | Float32 | % | 1 | R |
| 1026 | 2 | Switch-on counter Number of previous power-ups. | UInt32 | - | 1 | R |
| 1028 | 2 | Total operating time Total operating time in hours, range 0 to (2^32-1)/3600 h. | UInt32 | h | 1 | R |
| 1030 | 2 | Total stroke counter Total number of strokes, range 0 to 2^32-1. | UInt32 | strokes | 1 | R |
| 1034 | 2 | Total metering quantity Total metered volume in litres. | Float32 | l | 1 | R |
| 1038 | 2 | Remaining strokes Strokes remaining in the current batch or contact cycle. | UInt32 | strokes | 1 | R |
| 1040 | 2 | Remaining metering quantity Metered volume remaining in the current batch or contact cycle. | Float32 | l | 1 | R |
| 1042 | 2 | Metering quantity of last stroke Volume of the last stroke; the unit depends on the dosing head and the device context. | Float32 | - | 1 | R |
| 1044 | 2 | Medium system pressure Back pressure at the dosing head, 0.0 bar to the operating pressure. | Float32 | bar | 1 | R |
| 1046 | 1 | Liquid level monitoring Level reported by the level switch / suction lance, 0-100 %. | UInt16 | % | 1 | R |
| 1201 | 2 | Target stroke length Target stroke length, 1-100 %. | Float32 | % | 1 | RW |
| 1203 | 1 | Target stroke rate Target stroke rate, 1 to the maximum possible stroke rate. | UInt16 | strokes/h | 1 | RW |
| 1211 | 2 | Target capacity Target feed rate; the unit depends on the dosing head fitted and the device context. | Float32 | - | 1 | RW |
| 1215 | 2 | Metering volume per batch Batch-mode set-point; the value range is controlled by the metering volume settings. | Float32 | - | 1 | RW |
| 1217 | 1 | Metering time for batch Batch-mode metering time; min/max values are controlled by the batch settings. | UInt16 | s | 1 | RW |
| 1221 | 2 | Metering volume per contact Contact-mode set-point. | Float32 | - | 1 | RW |
| 1226 | 2 | Desired final concentration Target concentration for concentration mode, 0.01-100000 ppm. | Float32 | ppm | 1 | RW |
| 1233 | 1 | Priming duration Priming time, 1-60 s. | UInt16 | s | 1 | RW |
| 1235 | 1 | Trigger a batch/contact cycle Writing a Modbus message with this register number and the user data pattern given in the document triggers a batch or contact cycle, depending on the operating mode. | UInt16 | - | 1 | RW |
| 1236 | 1 | Delete error requiring acknowledgement Writing a Modbus message with this register number and user data pattern 0x5555 resets all errors that require acknowledgement. | UInt16 | - | 1 | RW |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: ProMinent 'Supplementary Operating Instructions for Modbus RTU' for the solenoid metering pumps gamma/ XL, GXLa, document 981604 (BA G-061 09-19, 'ErgBA Optionen Komm GXLa'), chapter 2 - sections 2.4 (operating menu defaults), 2.5.1 (telegram structure), 2.10.1-2.10.2 (device identification and Modbus registers) and 2.10.5/2.10.6 (current and target operating parameters); vendor-hosted at prominent.de, SHA-256 6475d9b21c475cb150911d6fe7f417617eb343ff435637e2dc0e581cb903f909. Factory frame: the document's default-settings box says the pump is delivered with bus address 20 and 19200 baud, and its telegram table (Tab. 25) fixes the characters at 1 start bit, 8 data bits, 1 parity bit 'even' and 1 stop bit, with 19200 as the preset data rate. Addressing: the register tables number their rows 1, 3, 4, 9 ... 1000, 1002 ... with no wire-address column and no frame example, so the seed declares one_based (register number minus one), the same reading the library applied to the Sentera maps; the inference is recorded here rather than hidden. The document prints no byte or word order for its FLOAT32/UINT32 values - instead register 63 stores the pattern 0xAABBCCDD so the master can determine it - so BigEndian + HighFirst is declared as the Modbus convention and register 63 is seeded to verify it. Omitted on purpose: every row the document types UINT8, BOOLEAN or Enum (1234, 1225, 1228-1232, the Modbus module settings 50-56 and 1200 start/stop) because this schema has no 8-bit type; the advanced-configuration and accessories/debug blocks; and the device-identification/production-data blocks 1-33 and 200-526, whose strings and production data are identity rather than process values.