Megarevo · Hybrid inverter

Megarevo R/REVO series hybrid energy-storage inverters (Hybrid Inverter Modbus Protocol V2.12) Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
125441
DSP Alarm 1
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125451
DSP Alarm 2
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125461
DSP Fault 1
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125471
DSP Fault 2
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125481
DSP state
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125491
ARM Alarm1
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125551
BMS Error word
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125561
BMS alarm2 word
bit field; the document's alarm/fault word tables decode the bits
UInt16-1R
125571
custom version
Factory customisation code, not a bit field: 0 = standard model (the sheet prints 'custom version', 0 for standard units). Non-standard LNA / L-battery units report their variant code here.
UInt16-1R
125601
Grid_A Voltage
UInt16V0.1R
125611
Grid_A Current
Sell to the grid as positive
Int16A0.1R
125621
Grid_A Power
Int16W1R
125631
Grid_B Voltage
UInt16V0.1R
125641
Grid_B Current
positive = discharging to the grid
Int16A0.1R
125651
Grid_B Power
Int16W1R
125661
Grid_C Voltage
UInt16V0.1R
125671
Grid_C Current
positive = discharging to the grid
Int16A0.1R
125681
Grid_C Power
Int16W1R
125691
Grid Freq
UInt16Hz0.01R
125701
INV Temperature
Int16°C1R
125711
inverter inside Temperature
Int16°C1R
125721
GridPortPower_A
Int16W1R
125731
GridPortPower_B
Int16W1R
125741
GridPortPower_C
Int16W1R
125761
Load_A Voltage
UInt16V0.1R
125771
Load_A Current
Int16A0.1R
125781
Load_A Power
Int16W1R
125791
Load_A Rate
UInt16%0.1R
125801
Load_B Voltage
UInt16V0.1R
125811
Load_B Current
Int16A0.1R
125821
Load_B Power
Int16W1R
125831
Load_B Rate
UInt16%0.1R
125841
Load_C Voltage/Load2 Voltage
Load2 applies to the G2S model only
UInt16V0.1R
125851
Load_C Current/Load2 Current
Load2 applies to the G2S model only
Int16A0.1R
125861
Load_C Power/Load2 Power
Load2 applies to the G2S model only
Int16W1R
125871
Load_C Rate
UInt16%0.1R
125881
Generator Freq
UInt16Hz0.01R
125891
Generator port voltage A
UInt16V0.1R
125901
Generator port voltage B
UInt16V0.1R
125911
Generator port voltage C
UInt16V0.1R
125921
PV1 Voltage
UInt16V0.1R
125931
PV1 Current
UInt16A0.1R
125941
PV1 Power
Int16W1R
125951
PV2 Voltage
UInt16V0.1R
125961
PV2 Current
UInt16A0.1R
125971
PV2 Power
Int16W1R
125981
PV3 Voltage
PV3 data is only supported on the US low-voltage, US high-voltage and G2 models
UInt16V0.1R
125991
PV3 Current
PV3 datas only supports LNA, H1, and G2 models
UInt16A0.1R
126001
PV3 Power
Int16W1R
126011
PV4 Voltage
PV4 data is only supported on the US low-voltage and US high-voltage models
UInt16V0.1R
126021
PV4 Current
PV4 data only support LNA, H1 models
UInt16A0.1R
126031
PV4 Power
Int16W1R
126041
PV Temp
UInt16°C1R
126051
BAT SOH(non-standard)
UInt16-0.01R
126061
BMS BAT Voltage
UInt16V0.1R
126071
BMS BAT Current
Int16A0.1R
126081
BAT Voltage
Int16V0.1R
126091
BAT Current
Charge is positive
Int16A0.1R
126101
BAT Current1
Int16A0.1R
126111
BAT Current2
Int16A0.1R
126121
BAT Current3
Int16A0.1R
126131
BAT SOC
UInt16-0.001R
126141
BAT Temperature
Int16°C0.1R
126151
BAT Charge Voltage
UInt16V0.1R
126161
BAT Charge Current Limite
UInt16A0.1R
126171
BAT DisCharge Current Limite
UInt16A0.1R
126181
BAT Power
Int16W1R
126191
BMS BAT Cell MaxVoltage
UInt16mV1R
126201
BMS BAT Cell MinVoltage
UInt16mV1R
126211
BMS BAT Cell MaxTemperature
Int16°C1R
126221
BMS BAT Cell MinTemperature
Int16°C1R
126231
Battery capacity(non-standard)
UInt16Ah1R
126241
P Bus voltage
UInt16V0.1R
126251
N Bus voltage
Int16V0.1R
126261
DCDC Temperature
Int16°C1R
126272
PV day energy
32-bit value, word order CD AB (low word first)
UInt32kWh0.001R
126292
Grid day energy
longCD AB
UInt32kWh0.001R
126312
Load day energy
longCD AB
Int32kWh0.001R
126332
PV month energy
longCD AB
UInt32kWh0.001R
126352
Grid month energy
longCD AB
UInt32kWh0.001R
126372
Load month energy
longCD AB
Int32kWh0.001R
126392
PV year energy
longCD AB
UInt32kWh0.001R
126412
Grid year energy
longCD AB
UInt32kWh0.001R
126432
Load year energy
longCD AB
Int32kWh0.001R
126452
PV total energy
longCD AB
UInt32kWh0.001R
126472
Grid total energy
longCD AB
UInt32kWh0.001R
126492
Load total energy
longCD AB
Int32kWh0.001R
126512
Purchasing day Energy
longCD AB
UInt32kWh0.001R
126532
Bat charge day Energy
longCD AB
UInt32kWh0.001R
126552
Bat discharge day Energy
longCD AB
UInt32kWh0.001R
126572
Purchasing month Energy
longCD AB
UInt32kWh0.001R
126592
Bat charge month Energy
longCD AB
UInt32kWh0.001R
126612
Bat discharge month Energy
longCD AB
UInt32kWh0.001R
126632
Purchasing year Energy
longCD AB
UInt32kWh0.001R
126652
Bat charge yerar Energy
longCD AB
UInt32kWh0.001R
126672
Bat discharge year Energy
longCD AB
UInt32kWh0.001R
126692
Purchasing total Energy
longCD AB
UInt32kWh0.001R
126712
Bat charge total Energy
longCD AB
UInt32kWh0.001R
126732
Bat discharge total Energy
longCD AB
UInt32kWh0.001R
126752
AC Solar day Energy
longCD AB
Int32kWh0.001R
126772
AC Solar month Energy
longCD AB
Int32kWh0.001R
126792
AC Solar year Energy
longCD AB
Int32kWh0.001R
126812
AC Solar total Energy
longCD AB
Int32kWh0.001R
126881
INV_A Voltage
UInt16V0.1R
126891
INV_A Current
Int16A0.1R
126901
INV_A Power
Int16W1R
126911
INV_B Voltage
UInt16V0.1R
126921
INV_B Current
Int16A0.1R
126931
INV_B Power
Int16W1R
126941
INV_C Voltage
UInt16V0.1R
126951
INV_C Current
Int16A0.1R
126961
INV_C Power
Int16W1R
126971
INV_A Freq
UInt16Hz0.01R
126981
INV_B Freq
UInt16Hz0.01R
126991
INV_C Freq
UInt16Hz0.01R
127001
leak current
UInt16mA1R
127011
Bus voltage
UInt16V0.1R
127041
Grid_A apparent Power
Int16VA1R
127051
Grid_B apparent Power
Int16VA1R
127061
Grid_C apparent Power
Int16VA1R
127071
Grid_A Reactive Power
Int16var1R
127081
Grid_B Reactive Power
Int16var1R
127091
Grid_C Reactive Power
Int16var1R
127101
HomeLoadP_A
Int16W1R
127111
HomeLoadP_B
Int16W1R
127121
HomeLoadP_C
Int16W1R
127131
HomeLoadP_Total
Int16W1R
127141
G100 STATE
UInt16-1R
127151
GridPortCurrent_A
Int16A0.1R
127161
GridPortCurrent_B
Int16A0.1R
127171
GridPortCurrent_C
Int16A0.1R
127301
Test word 1
UInt16-1R
127311
Test word 2
UInt16-1R
127321
Test word 3
UInt16-1R
127331
Test word 4
UInt16-1R
127361
ParLeadBatMinVolt
UInt16V0.1R
127371
ParLeadBatMaxVolt
UInt16V0.1R
127381
ParLeadBatChrgVolt
UInt16V0.1R
127391
ParallelStatus 1
see Alarm Table
UInt16-1R
127401
signed A EPS load power(LNA used)
Int16W1R
127411
signed B EPS load power(LNA used)
Int16W1R
127431
Grid Line volt
UInt16V0.1R
127491
Load_A Reactive Power
Int16var1R
127501
Load_B Reactive Power
Int16var1R
127511
Load_C Reactive Power
Int16var1R
127521
Generator port current A
Int16A0.1R
127531
Generator port current B
Int16A0.1R
127541
Generator port current C
Int16A0.1R
127551
Generator port power A
Int16W1R
127561
Generator port power B
Int16W1R
127571
Generator port power C
Int16W1R
127581
AC Couple Freq
UInt16Hz0.01R
127591
AC Couple CurrentL1
Int16A0.1R
127601
AC Couple PowerL1
Int16W1R
127611
AC Couple CurrentL2
Int16A0.1R
127621
AC Couple PowerL2
Int16W1R
127631
AC Couple CurrentL3
Int16A0.1R
127641
AC Couple PowerL3
Int16W1R
127651
AC Couple Total PowerL
negative = flowing into the inverter
Int16W1R
127681
parallel 3P grid voltage A
UInt16V0.1R
127691
parallel 3P grid current A
Int16A0.1R
127701
parallel 3P grid power A
Int16W1R
127711
parallel 3P grid voltage B
UInt16V0.1R
127721
parallel 3P grid current B
Int16A0.1R
127731
parallel 3P grid power B
Int16W1R
127741
parallel 3P grid voltage C
UInt16V0.1R
127751
parallel 3P grid current C
Int16A0.1R
127761
parallel 3P grid power C
Int16W1R
127771
parallel 3P grid Freq
UInt16Hz0.01R
127841
parallel 3P load voltage A
UInt16V0.1R
127851
parallel 3P load current A
Int16A0.1R
127861
parallel 3P load power A
Int16W1R
127871
parallel 3P load voltage B
UInt16V0.1R
127881
parallel 3P load current B
Int16A0.1R
127891
parallel 3P load power B
Int16W1R
127901
parallel 3P load voltage C
UInt16V0.1R
127911
parallel 3P load current C
Int16A0.1R
127921
parallel 3P load power C
Int16W1R
127931
parallel 3P load Freq
UInt16Hz0.01R
127961
MOSFET maximum temperature value
Non-standard model variants only (the sheet highlights the row); L battery
Int16°C1R
127971
Grid connection countdown
Non-standard model variants only (the sheet highlights the row)
UInt16s1R
127981
Generator status word
Non-standard model variants only (the sheet highlights the row); the sheet's alarm sheet decodes the bits
UInt16-1R
131681
Insulation resistance value (PV1 to ground)
UInt16Ω1R
131691
Insulation resistance value (PV2 to ground)
UInt16Ω1R
131701
Insulation resistance value (PV3 to ground)
UInt16Ω1R
131711
Insulation resistance value (PV4 to ground)
UInt16Ω1R
131721
Grid Status
Grid status word; the sheet repeats the Ω cell from the insulation rows above
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Megarevo "Hybrid Inverter_Modbus Protocol_V2.12.xlsx" (version record to 2025-02-17), the vendor protocol spreadsheet. Not on a download page: the copy read is the vendor file mirrored in the ha-solarman discussion of the protocol (https://github.com/user-attachments/files/23858912/Hybrid.Inverter_Modbus.Protocol_V2.12.xlsx, SHA-256 f748e86c41a81350b1d19496095513cfc88c6ac3f48ddca322ad42d8fed0f602) - MIRROR-SOURCED. Its "instructions" sheet fixes the transport: device address 1, standard Modbus, 9600 bps, 8 data bits, no parity, 1 stop bit. Seeded: every named row of the "Data" sheet's 0x3100-0x31FF telemetry block plus the insulation rows 0x3370-0x3374 - alarm/fault/state words, grid, load, generator, AC-couple, parallel, PV, battery and energy measurements. It prints 32-bit values as "long CD AB" and works 0x01 0x02 0x03 0x04 through as 0x03040102, so the seed declares LowFirst; 16-bit rows are unaffected. Its byte column is bytes, not registers (U16/S16 = 1 register, U32/S32 = 2), and its "rate" column fuses scale and unit (0.1V, 1W, 0.01HZ, 0.001kWh), which the seed stores. Not seeded, with reasons: the Reserve rows (0x3106-0x310A, 0x311F), the Debug/test-word rows (0x31B0-0x31B9, 0x32A0-0x32B3, 0x33B0-0x33C6), the status and external-meter rows 0x32C0-0x32F8 (no scale or unit is printed), the unnamed filler rows (0x31DE-0x31DF, 0x31EA-0x31EF, 0x31FA-0x31FB, 0x31FF), the "already occupied" range rows (0x3200-0x329F, 0x3300-0x337E), the 0x21xx rows outside the seeded block (0x2100/0x2101 battery-2 voltage and current, 0x21E0/0x21E1 communication error counters, 0x21F0-0x21F5 fan speeds) and the settings blocks (0x16A2, 0x22xx grid-code incl. 0x224E and 0x2282-0x228A, 0x34xx) plus the one writable 0x31xx row 0x31C6 US Grid type. Rows highlighted in yellow are the non-standard (LNA / L-battery) variants; they are seeded and say so, so a standard unit returns 0 or the invalid value. 0x310D is the factory customisation code, not a bit field.