WS500-UMB / WS600-UMB (compact weather station) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Identification
High byte = WS type (2, 3, 4, 5, 6 = WS200/300/400/500/600), low byte = software version.
UInt16-1R
11
Device status
UInt16-1R
21
Sensor status 1
Air temperature buffer, air temperature, dew point buffer, dew point - 4 status bits each; see the status table in section 19.7.3.3.
UInt16-1R
31
Sensor status 2
Relative humidity buffer, relative humidity, absolute humidity buffer, absolute humidity.
UInt16-1R
41
Sensor status 3
Mixing ratio buffer, mixing ratio, air pressure buffer, air pressure.
UInt16-1R
51
Sensor status 4
Wind, wind buffer, precipitation, compass.
UInt16-1R
61
Sensor status 5
Global radiation buffer, global radiation, leaf wetness buffer, leaf wetness.
UInt16-1R
71
Sensor status 6
External temperature.
UInt16-1R
91
Diagnostic run time
In 10 s steps.
UInt16s10R
101
Relative humidity (act.)
Int16%0.1R
111
Relative humidity (min.)
Int16%0.1R
121
Relative humidity (max.)
Int16%0.1R
131
Relative humidity (avg.)
Int16%0.1R
141
Relative air pressure (act.)
Int16hPa0.1R
151
Relative air pressure (min.)
Int16hPa0.1R
161
Relative air pressure (max.)
Int16hPa0.1R
171
Relative air pressure (avg.)
Int16hPa0.1R
181
Wind direction (act.)
Int16°0.1R
191
Wind direction (min.)
Int16°0.1R
201
Wind direction (max.)
Int16°0.1R
211
Wind direction (vct.)
Int16°0.1R
221
Wind direction fast
Int16°0.1R
231
Wind direction, compass corrected
Int16°0.1R
241
Compass
Int16°0.1R
251
Precipitation type
Int16-1R
261
Wind measurement quality
Int16-1R
271
Global radiation (UMB channel 900)
Int16W/m20.1R
281
Global radiation (UMB channel 920)
Int16W/m20.1R
291
Global radiation (UMB channel 940)
Int16W/m20.1R
301
Global radiation (UMB channel 960)
Int16W/m20.1R
311
Air temperature °C (act.)
Int16°C0.1R
321
Air temperature °C (min.)
Int16°C0.1R
331
Air temperature °C (max.)
Int16°C0.1R
341
Air temperature °C (avg.)
Int16°C0.1R
351
Dew point °C (act.)
Int16°C0.1R
361
Dew point °C (min.)
Int16°C0.1R
371
Dew point °C (max.)
Int16°C0.1R
381
Dew point °C (avg.)
Int16°C0.1R
391
Wind chill temperature °C
Int16°C0.1R
401
Heating temperature wind °C
Int16°C0.1R
411
Heating temperature R2S °C
Int16°C0.1R
421
Wind speed m/s (act.)
Int16m/s0.1R
431
Wind speed m/s (min.)
Int16m/s0.1R
441
Wind speed m/s (max.)
Int16m/s0.1R
451
Wind speed m/s (avg.)
Int16m/s0.1R
461
Wind speed m/s (vct.)
Int16m/s0.1R
471
Wind speed fast m/s
Int16m/s0.1R
481
Precipitation absolute
Unsigned, limited to 655.34 mm.
UInt16mm0.01R
491
Precipitation differential
Unsigned, limited to 100.00 mm.
UInt16mm0.01R
501
Precipitation intensity
Unsigned, limited to 200.00 mm/h.
UInt16mm/h0.01R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above. Source: G. Lufft Mess- und Regeltechnik "Operating Instructions - Compact Weather Station WS200-UMB / WS300-UMB / WS400-UMB / WS500-UMB / WS600-UMB", manual v2.2, section 19.7 "Communication in Modbus Mode" - 19.7.1 (communication parameters), 19.7.2 (addressing), 19.7.3.3 function 0x04 with the input-register assignment table (registers 0-124), and section 10.1 "Factory Settings". Factory serial settings: 19200 bps, 8 data bits, even parity, 1 stop bit - selecting MODBUS-RTU in the UMB Config Tool preselects exactly these parameters, and the factory setting of the interface speed is 19200 with device ID 1; the Modbus address equals the UMB device ID (factory setting 1, valid range 1...247). Every measurement is a 16-bit integer with the scaling factor of the table applied ("Factor 10" = x0.1), and 65535 / 32767 mean "erroneous or not available" - use the sensor status registers to see which channel is missing on a given WS type (the register assignment itself is identical across the WS family). This seed lists the status block, the values independent of the unit system and the metric values up to register 50; the imperial-unit block (51-70) repeats the same quantities in °F/mph/in and the "further values" block (absolute humidity, mixing ratio, absolute air pressure, km/h and knots wind speeds, wet bulb temperature, enthalpy, air density, leaf wetness) are documented in the same table but are not repeated here. The writable holding registers of function 0x03 (local altitude, compass deviation, averaging intervals, heating modes, rain and station reset) are documented in section 19.7.3.1.