KATHREIN · EV charger

KWB AC35 / AC40 (ACxx(E) wallbox) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
0
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Mapping version
Header: decimal version of this register mapping, current version 0x0001.
UInt16-1R
18
Device number
Device number, format "620xxxxx(-yyyy)".
Ascii-1R
98
Device type
Device type, format "ACxx(E)".
Ascii-1R
178
Device serial number
Serial number, format "G0Rxxxxxxx".
Ascii-1R
251
Device info
Bit field. Bits 0-1 = power class (0x0001 = 11 kW, 0x0002 = 22 kW), bit 4 = cable/plug (0x0010 = plug, 0 = cable), bit 7 = Eichrecht (0x0080), bits 8-15 = relay capability (0x0100 L1, 0x0200 L2, 0x0400 L3, 0x1000 L1+L2, 0x2000 L1+L3, 0x4000 L2+L3, 0x8000 L1+L2+L3).
Binary-1R
261
Device line mapping
0 = L1-L2-L3 (default), 1 = L1-L3-L2 (invalid rotation), 2 = L2-L3-L1, 3 = L2-L1-L3 (invalid rotation), 4 = L3-L1-L2, 5 = L3-L2-L1 (invalid rotation).
UInt16-1R
482
Meter U1
Line 1 to neutral voltage.
Float32V1R
502
Meter U2
Line 2 to neutral voltage.
Float32V1R
522
Meter U3
Line 3 to neutral voltage.
Float32V1R
542
Meter I1
Line 1 current.
Float32A1R
562
Meter I2
Line 2 current.
Float32A1R
582
Meter I3
Line 3 current.
Float32A1R
602
Meter P1
Active power on line 1.
Float32W1R
622
Meter P2
Active power on line 2.
Float32W1R
642
Meter P3
Active power on line 3.
Float32W1R
662
Meter S1
Apparent power on line 1.
Float32VA1R
682
Meter S2
Apparent power on line 2.
Float32VA1R
702
Meter S3
Apparent power on line 3.
Float32VA1R
722
Meter Q1
Reactive power on line 1.
Float32VAr1R
742
Meter Q2
Reactive power on line 2.
Float32VAr1R
762
Meter Q3
Reactive power on line 3.
Float32VAr1R
782
Meter PF1
Power factor (cos phi) on line 1, 0.0 to 1.0.
Float32-1R
802
Meter PF2
Power factor (cos phi) on line 2, 0.0 to 1.0.
Float32-1R
822
Meter PF3
Power factor (cos phi) on line 3, 0.0 to 1.0.
Float32-1R
842
Meter P total
Total active power.
Float32W1R
862
Meter S total
Total apparent power.
Float32VA1R
882
Meter Q total
Total reactive power.
Float32VAr1R
902
Meter PF total
Total power factor (cos phi), 0.0 to 1.0.
Float32-1R
922
Meter W total
Total energy since production.
Float32kWh1R
942
Meter frequency
Line frequency.
Float32Hz1R
961
EVSE charging state
0 = idle, 1 = EV connected, 2 = authentication waiting, 3 = authentication confirmed, 4 = charging active, 5 = charging paused, 6 = charging completed, 7 = RFID pairing, 0xFFFF = error.
UInt16-1R
971
EVSE error state
Bit field: 0x0000 no error, 0x0001 relay welded, 0x0002 residual DC current detected (RCD), 0x0004 socket lock-detection error, 0x0008 charging overcurrent, 0x0010 CP-D ventilation not available, 0x0020 CP-E short circuit, 0x0040 CP-F loop broken, 0x0080 PP error (short circuit), 0x8000 internal error.
Binary-1R
981
EVSE PP state
Plug variant: 0 = cable not connected (then 13, 20, 32, 63 A and 0xFFFF error follow the PP resistor); cable variant: 0 = fixed cable mounted.
UInt16-1R
991
EVSE CP state
0 = A (EV not detected, standby), 1 = B (EV detected, ready to charge), 2 = C (EV charging), 3 = D (EV charging with fan), 4 = E (CP short circuit), 5 = F (EVSE not available, CP = -12 VDC); any other value is undefined or an error.
UInt16-1R
1001
EVSE relay state
Bit field: 0x0000 relay off, 0x0001 L1 active, 0x0002 L2 active, 0x0004 L3 active.
Binary-1R
1011
EVSE granted current
Charging current granted per line, related to the CP signal: 0 or 6000 to 32000 mA.
UInt16mA1R
1021
EVSE granted power
Granted charging power, power sum of all active lines, related to the CP signal: 1380 to 22080 W at 230 VAC depending on power class and active relays.
UInt16W1R
1032
Charging duration
Duration of the current charging session.
UInt32s1R
1052
Charging energy
Energy of the current charging session.
UInt32Wh1R
1601
EMS control register
0x8000 enables EMS control; default 0x0000 (EMS control disabled).
UInt16-1RW
1611
EMS setpoint relay matrix
Lines to switch, according to the relay capability: 0x0001 line 1, 0x0002 line 2 (reserved for future use), 0x0004 line 3 (reserved for future use); default 0x0007 (three lines). Used together with the charging current setpoint.
Binary-1RW
1621
EMS setpoint charging current
0 pauses charging, 6000 to 32000 sets the current in mA, 0xFFFF cancels charging; default is the maximum current of the power class.
UInt16mA1RW
1631
EMS timeout period
0 = timeout deactivated, greater than 0 = timeout active; each setpoint write resets the timer; default 0.
UInt16s1RW
1641
EMS timeout fallback pattern
Lines that are used when the timeout expires: 0x0001 line 1, 0x0002 line 2, 0x0004 line 3; default 0x0007. Unsupported lines are ignored.
Binary-1RW
1651
EMS timeout fallback current
Fallback charging current when the timeout expires: 0 or 6000 to 32000 mA; default 6000.
UInt16mA1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: "KATHREIN-Wallbox - ModBus-Server - Register-Mapping", release version 1.3, release date 04.11.2024, the register mapping the KATHREIN wallbox business publishes together with its wallbox documentation; the PDF is served from the Amperfied download area (https://www.amperfied.de/wp-content/uploads/2025/06/Modbus-Server.pdf), which now runs the KATHREIN wallbox downloads, and the product page given as supplier_url is KATHREIN's own. The document fixes the transport: a Modbus TCP server on port 502 (IEC 61158 / IEC 61784-2 CPF 15/1), big-endian integers and words, only holding registers, function codes 0x03 (read multiple), 0x06 (write single) and 0x10 (write multiple); "At the moment, the Unit-ID is ignored, but 0x00 (Broadcast) is recommended", which is the unit ID recorded here. The register table starts at 0x0000, so the addresses below are the vendor's hex addresses as decimals and are declared zero_based. The Modbus server is disabled by factory default and has to be enabled in the easyOperate configuration panel. The device is the ACxx(E) family (device type register 0x0009), sold as KWB AC35 (11 kW) and KWB AC40 (22 kW). Left out on purpose: the local timestamp 0x001B (UINT64 over four registers - this schema has no 64-bit integer type), the reserved block 0x001F, the tariff registers 0x006B, 0x006C and 0x006D (marked "reserved for future use" in the document) and the reserved block 0x006E. The unit column of the PDF is set as its own right-hand column; every unit in this file was paired with its row by word coordinates, because plain text extraction shifts that column by several rows.