All devices

HMS Networks (Intesis) · Protocol gateway

INMBSSAM001R100 – Samsung NASA units to Modbus RTU interface Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
AC unit on/off
0 = off, 1 = on.
UInt16-1RW
11
AC unit mode
0 = Auto, 1 = Heat, 2 = Dry, 3 = Fan, 4 = Cool; the available values depend on the indoor unit.
UInt16-1RW
21
AC unit fan speed
0 = Auto, 1 = Low, 2 = Mid, 3 = High, 4 = Turbo.
UInt16-1RW
31
AC unit up/down vane position
0 = swing off (auto), 10 = swing on.
UInt16-1RW
41
AC unit temperature setpoint
-32768 = initialization value; cooling 18..30 °C (raw 180..300 at the factory degC x10 setting), heating 16..30 °C, 65..86 °F.
Int16°C0.1RW
51
AC unit temperature reference
-32768 = initialization value; -41..38 °C.
Int16°C0.1R
61
Window contact
0 = closed (default), 1 = open.
UInt16-1RW
71
Gateway disablement
0 = INMBSSAM001R100 enabled (default), 1 = disabled. Stored in non-volatile memory.
UInt16-1RW
81
AC remote control disablement
0 = remote controller enabled (default), 1 = disabled. Stored in non-volatile memory.
UInt16-1RW
91
AC unit operation time
0..65535 hours, counts the time the indoor unit is in the 'On' state.
UInt16h1RW
101
AC unit alarm status
0 = no alarm condition, 1 = alarm condition.
UInt16-1R
111
Error code
0 = no error; 65535 (= -1) = communication error between gateway and AC indoor unit; any other value is listed in the manual's error-code table.
UInt16-1R
131
'Open Window' switch-off timeout
0..30 minutes; factory setting 30.
UInt16min1RW
141
Modbus RTU baud rate
2400 / 4800 / 9600 (default) / 19200 / 38400 / 57600 / 76800 / 115200 bps.
UInt16-1R
151
Modbus slave address
1..63.
UInt16-1R
221
Indoor unit ambient temperature from external sensor
-32768 = no external sensor value; otherwise a temperature supplied from the Modbus side.
Int16°C0.1RW
231
AC real temperature setpoint
Current setpoint in the indoor unit; equals register 4 when no external temperature is provided; 16..31 °C.
Int16°C0.1R
261
AC unit left/right vane position
0 = swing off (auto), 10 = swing on.
UInt16-1RW
401
Window contact on/off disablement
0 = the window contact is not disabling on/off (default), 1 = it is.
UInt16-1R
431
Filter reset
Write 1 to reset the filter sign.
UInt16-1W
441
Filter status
0 = ok, 1 = filter cleaning required.
UInt16-1R
491
Device ID
0x2E00.
UInt16-1R
501
Software version
Gateway firmware version.
UInt16-1R
661
Return path temperature
-32768 = initialization value; the range is specific to the indoor unit.
Int16°C0.1R
671
Number of indoor units connected
Indoor units on the same remote-control bus.
UInt16-1R
681
Internal indoor-unit array index reported
Position in the gateway's internal array of the indoor unit whose status is currently reported.
UInt16-1RW
691
Indoor unit address reported
Address of the indoor unit that reports its status on the remote-control bus.
UInt16-1R
971
Block periodic sendings
0 = non-blocked (default), 1 = blocked.
UInt16-1RW
991
Reset / reboot device
Write 1 to reset the gateway.
UInt16-1W

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: HMS Networks / Intesis user manual 'INMBSSAM001R100 (Samsung NASA) Samsung NASA units to Modbus RTU interface', r1.4, section 4.2 'Modbus Registers' (4.2.1 control and status, 4.2.2 configuration). The gateway is Modbus RTU (RS-485) and exposes its own fixed holding-register map that mirrors the indoor unit; reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above (9600 bps, 8-N-2, Modbus server address 1; the gateway auto-detects 8-N-1 and 8-N-2). All registers are 16-bit unsigned holding registers, big-endian. The addresses in this file are the manual's base-0 'protocol addresses' (the manual also prints a base-1 'PLC address', which is always this address + 1). Temperature registers are signed 16-bit and their magnitude follows the gateway's DIP switches (degC x1, degC x10 or degF), so the 0.1 scale factors below assume the factory default degC x10; with the x1 setting the readings are whole degrees. This file covers the NASA variant of the Samsung gateway; the older non-NASA order code INMBSSAM001R000 has its own manual and a different indoor-unit addressing block. Registers 68/69 report which indoor unit on the remote-control bus the gateway is currently reporting status for.