In-Situ · Water quality sensor

Level TROLL 400 / 500 / 700 / 700H (Modbus PLC interface) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
372
Pressure
Measured value of parameter 2; 32-bit float, big-endian. Factory default unit is PSI (unit ID 17); the unit is set through the unit register at address 40.
Float32PSI1R
391
Pressure data quality
0 = no errors or warnings, 3 = error reading the parameter.
UInt16-1R
401
Pressure units
Unit ID for the pressure parameter: 17 = PSI (factory default), 19 = kPa, 20 = bar, 21 = mbar, 22 = mmHg, 23 = inHg, 24 = cmH2O, 25 = inH2O.
UInt16-1RW
411
Pressure parameter ID
Parameter ID = 2.
UInt16-1R
422
Pressure offline sentinel value
Value returned on error or when the parameter is unavailable; factory default 0.0.
Float32PSI1RW
452
Temperature
Measured value of parameter 1; 32-bit float, big-endian. Factory default unit is °C (unit ID 1); the unit is set through the register at address 48.
Float32°C1R
471
Temperature data quality
0 = no errors or warnings, 3 = error reading the parameter.
UInt16-1R
481
Temperature units
Unit ID for the temperature parameter: 1 = °C (factory default), 2 = °F.
UInt16-1RW
491
Temperature parameter ID
Parameter ID = 1.
UInt16-1R
502
Temperature offline sentinel value
Value returned on error or when the parameter is unavailable; factory default 0.0.
Float32°C1RW
532
Depth / Level
Measured value of parameter 3 (depth) or 4/5 (level, depth to water / surface elevation, enabled in VuSitu), which share this starting register. Factory default unit is feet (unit ID 38); the unit is set through the register at address 56.
Float32ft1R
551
Depth / Level data quality
0 = no errors or warnings, 3 = error reading the parameter.
UInt16-1R
561
Depth / Level units
Unit ID for the depth/level parameter: 38 = feet (factory default), 33 = mm, 34 = cm, 35 = m, 37 = inches.
UInt16-1RW
571
Depth / Level parameter ID
Parameter ID: 3 = depth, 4 = level (depth to water), 5 = level (surface elevation).
UInt16-1R
582
Depth / Level offline sentinel value
Value returned on error or when the parameter is unavailable; factory default 0.0.
Float32ft1RW
90001
Device ID
30 = Level TROLL 400, 1 = Level TROLL 500, 2 = Level TROLL 700 / 700H, 3 = Baro TROLL.
UInt16-1R
90012
Device serial number
32-bit serial number.
UInt32-1R
90061
Firmware version
For example 100 = firmware 1.00.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: In-Situ 'Level TROLL 400, 500, 700, and 700H Operator's Manual', part number 0052212, document revision 2024-23-01 ((c) In-Situ 2023), vendor-hosted PDF at the URL above (opened 7 Nov 2026): section 'Modbus PLC Interface' (page 47 onwards) and Appendices A (parameter numbers and locations) and B (unit IDs). Factory serial settings from the Modbus PLC Interface chapter: Modbus RTU, 1 start bit, 19200 baud, 8 data bits, even parity, 1 stop bit, default device address 1. Addressing: the manual prints a 'Holding Register Number' next to a 'Holding Register Address' that is exactly one lower (device ID 9001 / 9000, temperature 0046 / 0045, pressure 0038 / 0037, depth 0054 / 0053), states that some PLCs need 40000 added to the register number, and its worked example adds the block offsets to the register number before subtracting one - the numbers are decimal (pressure block 38-44, temperature 46-52, depth 54-60), and the addresses are stored unchanged as zero-based wire addresses (37, 45, 53). Every parameter block is 7 registers long: value (2 registers, big-endian float), data quality (1), unit ID (1), parameter ID (1), offline sentinel value (2). All rows are holding registers and the manual states that each register is a holding register. Default units come from Appendix A (temperature 1 = °C, pressure 17 = PSI, depth/level 38 = feet) and are writable through the unit-ID registers. Operating notes from the same chapter: the instrument must be woken with a carriage return (0x0D) or any Modbus command, one second must pass before the next command, and the default end-of-session timeout is 5 seconds (longer after a VuSitu session), so readings must be requested before it expires. Not claimed: the Baro TROLL variant's parameter set and the SDI-12 side of the device.