ET-7060 (and PET-7060 / ET-7260 / PET-7260) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Digital output 0 value
0 = relay off, 1 = relay on, for output channel 0.
Binary-1RW
11
Digital output 1 value
0 = relay off, 1 = relay on, for output channel 1.
Binary-1RW
21
Digital output 2 value
0 = relay off, 1 = relay on, for output channel 2.
Binary-1RW
31
Digital output 3 value
0 = relay off, 1 = relay on, for output channel 3.
Binary-1RW
41
Digital output 4 value
0 = relay off, 1 = relay on, for output channel 4.
Binary-1RW
51
Digital output 5 value
0 = relay off, 1 = relay on, for output channel 5.
Binary-1RW
641
Digital input 0 value
0 = off, 1 = on. The same state is also available in the discrete-input area at 10000 + channel.
Binary-1R
651
Digital input 1 value
0 = off, 1 = on. The same state is also available in the discrete-input area at 10000 + channel.
Binary-1R
661
Digital input 2 value
0 = off, 1 = on. The same state is also available in the discrete-input area at 10000 + channel.
Binary-1R
671
Digital input 3 value
0 = off, 1 = on. The same state is also available in the discrete-input area at 10000 + channel.
Binary-1R
681
Digital input 4 value
0 = off, 1 = on. The same state is also available in the discrete-input area at 10000 + channel.
Binary-1R
691
Digital input 5 value
0 = off, 1 = on. The same state is also available in the discrete-input area at 10000 + channel.
Binary-1R
1501
Enable/disable digital input latch function
0 = latch function off (factory default), 1 = on.
Binary-1RW
1511
Enable/disable counter of digital input 0
0 = counter off (factory default), 1 = counter on for DI channel 0.
Binary-1RW
1521
Enable/disable counter of digital input 1
0 = counter off (factory default), 1 = counter on for DI channel 1.
Binary-1RW
1531
Enable/disable counter of digital input 2
0 = counter off (factory default), 1 = counter on for DI channel 2.
Binary-1RW
1541
Enable/disable counter of digital input 3
0 = counter off (factory default), 1 = counter on for DI channel 3.
Binary-1RW
1551
Enable/disable counter of digital input 4
0 = counter off (factory default), 1 = counter on for DI channel 4.
Binary-1RW
1561
Enable/disable counter of digital input 5
0 = counter off (factory default), 1 = counter on for DI channel 5.
Binary-1RW
2351
Enable digital output 0 power-on value
0 = not used (factory default), 1 = relay 0 takes its stored power-on value after reset.
Binary-1RW
2361
Enable digital output 1 power-on value
0 = not used (factory default), 1 = relay 1 takes its stored power-on value after reset.
Binary-1RW
2371
Enable digital output 2 power-on value
0 = not used (factory default), 1 = relay 2 takes its stored power-on value after reset.
Binary-1RW
2381
Enable digital output 3 power-on value
0 = not used (factory default), 1 = relay 3 takes its stored power-on value after reset.
Binary-1RW
2391
Enable digital output 4 power-on value
0 = not used (factory default), 1 = relay 4 takes its stored power-on value after reset.
Binary-1RW
2401
Enable digital output 5 power-on value
0 = not used (factory default), 1 = relay 5 takes its stored power-on value after reset.
Binary-1RW
2671
Enable digital output 0 safe value
0 = not used (factory default), 1 = relay 0 takes its stored safe value when communication is lost.
Binary-1RW
2681
Enable digital output 1 safe value
0 = not used (factory default), 1 = relay 1 takes its stored safe value when communication is lost.
Binary-1RW
2691
Enable digital output 2 safe value
0 = not used (factory default), 1 = relay 2 takes its stored safe value when communication is lost.
Binary-1RW
2701
Enable digital output 3 safe value
0 = not used (factory default), 1 = relay 3 takes its stored safe value when communication is lost.
Binary-1RW
2711
Enable digital output 4 safe value
0 = not used (factory default), 1 = relay 4 takes its stored safe value when communication is lost.
Binary-1RW
2721
Enable digital output 5 safe value
0 = not used (factory default), 1 = relay 5 takes its stored safe value when communication is lost.
Binary-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Ethernet remote I/O with a built-in Modbus/TCP server on port 502. The ET-7060 has 6 wet-contact digital inputs with 32-bit counters and 6 relay outputs. Source: ICP DAS "ET-7x00/PET-7x00 Series Register Table", version 1.1.5, April 2025 (https://www.icpdas.com/en/download/file.php?num=4226), section "ET-7060/PET-7060/ET-7260/PET-7260", Modbus Register Table pages 116-117. Addressing: the table prints each row as a decimal 5-digit Modbus reference and as a hexadecimal offset that agree (coil 00064 = 0x0040, input register 30016 = 0x0010, holding register 40271 = 0x010F), so the seed stores the hexadecimal offsets as zero-based wire addresses. Unit identifier 1 is the factory value of the module's Modbus NetID register (40271), which the table states as factory value 1. Deliberate omissions: the coils the vendor types "W" only (clear historical max/min, clear counter, reset, reboot, save power-on/safe values, save counter presets) are not listed because the coil area in this schema carries only R or RW entries; the enabling coils and the preset holding registers that operate them are listed. The 6 32-bit DI counters (input registers 30016-30027) and their 6 32-bit presets (holding registers 40050-40061) are omitted: the register table types each as two registers but states no word order, and the user manual only says that "each counter consists of two address values, the Low word, and the High word", which does not settle which word the device sends first. With no 32-bit value left in this seed, no word order is claimed - the declared HighFirst is the schema default.