All devices

Hitachi · VFD

WJ200 (also SJ200, Modbus RTU on RS-485) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
11
Operation command
1 = run, 0 = stop. Valid when the run command source A002 = 03 (Modbus).
Binary-1RW
21
Rotation direction command
1 = reverse rotation, 0 = forward rotation. Valid when A002 = 03.
Binary-1RW
31
External trip (EXT)
1 = trip.
Binary-1RW
41
Trip reset (RS)
1 = reset the trip.
Binary-1RW
71
Intelligent input terminal [1]
1 = ON, 0 = OFF, for intelligent input terminal 1. The physical terminal state has priority over this coil.
Binary-1RW
81
Intelligent input terminal [2]
1 = ON, 0 = OFF, for intelligent input terminal 2. The physical terminal state has priority over this coil.
Binary-1RW
91
Intelligent input terminal [3]
1 = ON, 0 = OFF, for intelligent input terminal 3. The physical terminal state has priority over this coil.
Binary-1RW
101
Intelligent input terminal [4]
1 = ON, 0 = OFF, for intelligent input terminal 4. The physical terminal state has priority over this coil.
Binary-1RW
111
Intelligent input terminal [5]
1 = ON, 0 = OFF, for intelligent input terminal 5. The physical terminal state has priority over this coil.
Binary-1RW
121
Intelligent input terminal [6]
1 = ON, 0 = OFF, for intelligent input terminal 6. The physical terminal state has priority over this coil.
Binary-1RW
131
Intelligent input terminal [7]
1 = ON, 0 = OFF, for intelligent input terminal 7. The physical terminal state has priority over this coil.
Binary-1RW
151
Operation status
1 = run, 0 = stop; interlocked to monitor d003.
Binary-1R
161
Rotation direction
1 = reverse rotation, 0 = forward rotation; interlocked to monitor d003.
Binary-1R
171
Inverter ready
1 = ready, 0 = not ready.
Binary-1R
191
RUN (running)
The register table prints 1 = tripping, 0 = normal for this RUN item; quoted as printed.
Binary-1R
201
FA1 (constant-speed reached)
1 = ON, 0 = OFF.
Binary-1R
211
FA2 (set frequency overreached)
1 = ON, 0 = OFF.
Binary-1R
221
OL (overload advance notice 1)
1 = ON, 0 = OFF.
Binary-1R
231
OD (output deviation for PID control)
1 = ON, 0 = OFF.
Binary-1R
241
AL (alarm signal)
1 = ON, 0 = OFF.
Binary-1R
251
FA3 (set frequency reached)
1 = ON, 0 = OFF.
Binary-1R
261
OTQ (over-torque)
1 = ON, 0 = OFF.
Binary-1R
281
UV (undervoltage)
1 = ON, 0 = OFF.
Binary-1R
291
TRQ (torque limited)
1 = ON, 0 = OFF.
Binary-1R
301
RNT (operation time over)
1 = ON, 0 = OFF.
Binary-1R
311
ONT (plug-in time over)
1 = ON, 0 = OFF.
Binary-1R
321
THM (thermal alarm signal)
1 = ON, 0 = OFF.
Binary-1R
381
BRK (brake release)
1 = ON, 0 = OFF.
Binary-1R
391
BER (brake error)
1 = ON, 0 = OFF.
Binary-1R
401
ZS (0 Hz detection signal)
1 = ON, 0 = OFF.
Binary-1R
411
DSE (speed deviation maximum)
1 = ON, 0 = OFF.
Binary-1R
421
POK (positioning completed)
1 = ON, 0 = OFF.
Binary-1R
431
FA4 (set frequency overreached 2)
1 = ON, 0 = OFF.
Binary-1R
441
FA5 (set frequency reached 2)
1 = ON, 0 = OFF.
Binary-1R
451
OL2 (overload advance notice 2)
1 = ON, 0 = OFF.
Binary-1R
461
Odc (analog O disconnection detection)
1 = ON, 0 = OFF.
Binary-1R
471
OIDc (analog OI disconnection detection)
1 = ON, 0 = OFF.
Binary-1R
501
FBV (PID feedback comparison)
1 = ON, 0 = OFF.
Binary-1R
511
NDc (communication train disconnection)
1 = ON, 0 = OFF.
Binary-1R
521
LOG1 (logical operation result 1)
1 = ON, 0 = OFF.
Binary-1R
531
LOG2 (logical operation result 2)
1 = ON, 0 = OFF.
Binary-1R
541
LOG3 (logical operation result 3)
1 = ON, 0 = OFF.
Binary-1R
581
WAC (capacitor life warning)
1 = ON, 0 = OFF.
Binary-1R
591
WAF (cooling-fan speed drop)
1 = ON, 0 = OFF.
Binary-1R
601
FR (starting contact signal)
1 = ON, 0 = OFF.
Binary-1R
611
OHF (heat sink overheat warning)
1 = ON, 0 = OFF.
Binary-1R
621
LOC (low-current indication signal)
1 = ON, 0 = OFF.
Binary-1R
631
M01 (general output 1)
1 = ON, 0 = OFF.
Binary-1R
641
M02 (general output 2)
1 = ON, 0 = OFF.
Binary-1R
651
M03 (general output 3)
1 = ON, 0 = OFF.
Binary-1R
691
IRDY (inverter ready)
1 = ON, 0 = OFF.
Binary-1R
701
FWR (forward rotation)
1 = ON, 0 = OFF.
Binary-1R
711
RVR (reverse rotation)
1 = ON, 0 = OFF.
Binary-1R
721
MJA (major failure)
1 = ON, 0 = OFF.
Binary-1R
731
Data writing in progress
1 = writing in progress, 0 = normal status.
Binary-1R
741
CRC error
1 = error detected, 0 = no error. The flag is retained until an error reset command is given.
Binary-1R
751
Overrun
1 = error detected, 0 = no error.
Binary-1R
761
Framing error
1 = error detected, 0 = no error.
Binary-1R
771
Parity error
1 = error detected, 0 = no error.
Binary-1R
781
Sum check error
1 = error detected, 0 = no error.
Binary-1R
801
WCO (window comparator O)
1 = ON, 0 = OFF.
Binary-1R
811
WCOI (window comparator OI)
1 = ON, 0 = OFF.
Binary-1R
831
OPDc (option disconnection)
1 = ON, 0 = OFF.
Binary-1R
841
FREF (FQ command source)
1 = operator, 0 = others.
Binary-1R
851
REF (RUN command source)
1 = operator, 0 = others.
Binary-1R
861
SETM (2nd motor selected)
1 = 2nd motor selected, 0 = 1st motor selected.
Binary-1R
881
EDM (gate suppress monitor)
1 = ON, 0 = OFF.
Binary-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway. The factory serial settings are C071 = 05 (9600 bps), C072 = 1 (slave address), C074 = 00 (no parity) and C075 = 1 (1 stop bit), 8 data bits fixed, which is the 9600 8N1 block above and the unit ID this seed uses. Source: Hitachi "WJ200 Series Inverter Instruction Manual" NT325X, Appendix B "ModBus Network Communications" (https://www.hitachi-iesa.com/sites/default/files/inverter-pdf/WJ200_Instruction_NT325X_0.pdf), B-24/B-25 ModBus Coil List, B-30/B-31 (iii) List of registers (monitoring), B-31 (iv) List of registers, B-31/B-32 (v) List of registers (function modes), and the C071-C078 parameter registers on B-43. Addressing: the manual calls its numbers "the network register address offset", so they are stored unchanged as zero-based wire addresses (coil 0001h is the first offset, register 1001h is the d001 monitor high word). 32-bit monitors occupy two consecutive registers, high word first, which is why the device declares HighFirst. Coils the manual marks R are read-only status bits and are listed with access R; the control coils (operation, rotation direction, external trip, trip reset, intelligent inputs) are R/W. Deliberate omissions: the trip-history block (0011h-004Eh: six trip records with factor, frequency, current, voltage and run time) and the parameter groups B, C and D beyond the communication parameters shown are not transcribed; the manual prints those as a further ~250 register pairs whose per-row resolution column repeats without adding monitoring value. Reserved and inaccessible rows are omitted.