EVAPCO · Cooling tower

eco-Air controller with AC fan motors (adiabatic coolers, fluid coolers and refrigerant condensers) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
163842
Setpoint #1 temperature
Primary process temperature setpoint used when no alternate setpoint is active.
Float32-1RW
163862
Setpoint #2 temperature
Alternate process temperature setpoint, activated by the scheduler, ambient temperature or a digital input.
Float32-1RW
163881
Maximum allowed fan speed
Maximum allowable fan speed, 0 to 100 %.
Int16%1RW
163891
Quiet operation maximum fan speed
Maximum allowable fan speed while quiet operation is active, 0 to 100 %.
Int16%1RW
163901
Energy savings fan speed
Fan speed above which the pre-cooling system activates, 0 to 100 %.
Int16%1RW
163911
Minimum allowed fan speed
Minimum allowable fan speed, 0 to 100 %.
Int16%1RW
163932
Proportional temperature regulation band
Temperature band between minimum and maximum fan speed for proportional fan control, 0.0 to 30.0.
Float32-1RW
163952
PID controller gain
Proportional gain constant of the PID fan-speed controller, 0.0 to 10.0.
Float32-1RW
163971
PID controller Ti term
PID integral term, 0 to 999 s.
Int16s1RW
163981
PID controller Td term
PID derivative term, 0 to 999 s.
Int16s1RW
163992
Setpoint #2 ambient temperature trigger
Ambient temperature below which control switches to setpoint #2, -100.0 to 200.0.
Float32-1RW
164012
Setpoint #2 ambient trigger differential
Temperature differential added to the setpoint #2 ambient trigger before control returns to setpoint #1, 0.0 to 20.0.
Float32-1RW
164191
Condenser refrigerant type
1=R22, 2=R134a, 3=R404A, 4=R407C, 5=R410A, 6=R407A, 7=R407F, 8=R290, 9=R507A, 10=R717 (NH3), 11=R723, 12=R1234ze, 13=R744 (CO2), 14=R448A, 15=R427A, 16=R450A, 17=R513A, 18=R449A, 19=R1234yf, 20=R454B, 21=R454C, 22=R455A, 23=R434A, 24=R422A, 25=R32, 26=R452B, 27=R452A, 28=Custom.
Int16-1RW
164212
Low temperature pre-cooling system lockout
Minimum ambient temperature at which the pre-cooling system may operate, -9,999.0 to 9,999.0.
Float32-1RW
164232
Low temperature differential for pre-cooling lockout
Ambient temperature offset added to the lockout temperature, 0.0 to 20.0.
Float32-1RW
164251
Stage #1 increase time setpoint
Seconds the process temperature must stay above setpoint before stage 1 activates, 0 to 32,767.
Int16s1RW
164261
Stage #1 decrease time setpoint
Seconds the process temperature must stay below setpoint before stage 1 deactivates, 0 to 32,767.
Int16s1RW
164271
Stage #2-4 increase time setpoint
Seconds the process temperature must stay above setpoint before stages 2-4 activate, 0 to 32,767.
Int16s1RW
164281
Stage #2-4 decrease time setpoint
Seconds the process temperature must stay below setpoint before stages 2-4 deactivate, 0 to 32,767.
Int16s1RW
164292
Stage #1 ambient temperature switch point
Minimum ambient temperature above which stage 1 may operate, -999.9 to 999.9.
Float32-1RW
164312
Stage #2 ambient temperature switch point
Minimum ambient temperature above which stage 2 may operate, -999.9 to 999.9.
Float32-1RW
164332
Stage #3 ambient temperature switch point
Minimum ambient temperature above which stage 3 may operate, -999.9 to 999.9.
Float32-1RW
164352
Stage #4 ambient temperature switch point
Minimum ambient temperature above which stage 4 may operate, -999.9 to 999.9.
Float32-1RW
164381
Stage #1 minimum run time
Minimum time stage 1 stays active before it may turn off, 0 to 32,767 s.
Int16s1RW
164391
Stage #2 minimum run time
Minimum time stage 2 stays active before it may turn off, 0 to 32,767 s.
Int16s1RW
164401
Stage #3 minimum run time
Minimum time stage 3 stays active before it may turn off, 0 to 32,767 s.
Int16s1RW
164411
Stage #4 minimum run time
Minimum time stage 4 stays active before it may turn off, 0 to 32,767 s.
Int16s1RW
164431
Pre-cooling flush period
Minutes the flushing routine runs, 0 to 9,999.
Int16min1RW
164441
Pre-cooling drying period
Minutes the pre-cooling pads are dried after a flush, 0 to 9,999.
Int16min1RW
164452
Pre-cooling flush fan speed
Fan speed used during a flushing cycle, 0.0 to 100.0 %.
Float32%1RW
164481
Source for fan speed control
1 = analog input, 2 = communication (see register 409158).
Int16-1RW
164492
Signal failure ambient trigger
When fan-speed control comes from the analog input, decides whether a signal failure falls back to the high or low default fan speed, -100.0 to 200.0.
Float32-1RW
164511
Signal failure high default fan speed
Fan speed used when the analog input is lost and the ambient temperature is above the trigger, 0 to 100 %.
Int16%1RW
164521
Signal failure low default fan speed
Fan speed used when the analog input is lost and the ambient temperature is below the trigger, 0 to 100 %.
Int16%1RW
89611
Actual unit state
1 = unit on and operational, 2 = off by alarm, 4 = off via BMS, 6 = off via digital input, 7 = switched off locally, 8 = manual fan-speed mode.
Int16-1R
89622
Process temperature
Outlet temperature of the process fluid; on condenser applications a saturated value calculated from the condensing pressure.
Float32-1R
89642
Ambient temperature
Temperature read by the ambient sensor.
Float32-1R
89661
Reference fan speed
Fan speed the controller is requesting, 0 to 100 %.
Int16%1R
89672
Current active temperature setpoint
Setpoint the eco-Air unit is currently maintaining.
Float32-1R
89692
Inlet pressure
Inlet pressure from the pressure-sensor input.
Float32psig/bar1R
91581
Remote fan speed reference (communication)
Fan speed reference when remote fan speed is enabled and the source is communications; value is x10, 1000 = 100.0 %.
Int16%0.1RW
91592
Remote fan speed reference (analog input)
Fan speed reference derived from the analog input, 0.0 to 100.0 %.
Float32%1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: EVAPCO "Controller User's Manual - Addendum, Communications Guide AC Motor Edition", COMM24AC-E_1025, October 2025 (https://www.evapco.eu/sites/evapco.eu/files/2025-12/EVAPCO%20eco-Air%20Communications%20Guide%20AC%20Motor%20COMM24AC-E_1025.pdf), with the factory communication defaults from the "EVAPCO Controller User's Manual" dated 5/10/2022, Table 23 (https://www.evapco.com/sites/evapco.com/files/2022-05/Controller%20Users%20Manual_edited_5_10_22.pdf): Modbus RTU, node address 1, 19200 bps, even parity, 1 stop bit, 8 data bits (Modbus RTU). The guide publishes holding registers as six-digit 4xxxxx references (e.g. 416384), i.e. a 4 followed by the five-digit one-based register number, so this file stores the register number (16384) and declares one_based addressing. Rows ending in ',nn' in the source are single bits inside a holding register and are not modelled. 32-bit runtime counters are also left out because the document does not state their word order. The source's Units column renders as '0°' for temperature rows without saying °C or °F, so those rows carry no units and use whatever temperature scale the controller is configured for; fan speeds and percentages are %. Values are transmitted in engineering units, with the one documented exception of register 409158, which is x10.