All devices

Etrel · EV charger

INCH / INCH Duo Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Connector 1 status
0 = unknown, 1 = available, 2 = preparing (unauthorized/disconnected), 3 = preparing (waiting for EV), 4 = charging, 5 = charging paused by EV, 6 = charging paused by EVSE, 7 = finishing, 8 = faulted, 9 = unpausing charging, 10 = unavailable, 11 = reserved.
Int16-1R
11
Connector 1 measured vehicle number of phases
0 = three phases, 1 = single phase (L1), 2 = single phase (L2), 3 = single phase (L3), 4 = unknown, 5 = two phases.
Int16-1R
22
Connector 1 EV max phase current
Float32A1R
42
Connector 1 target current from power management or Modbus
Float32A1R
62
Connector 1 frequency
Float32Hz1R
82
Connector 1 voltage L1-N
Float32V1R
102
Connector 1 voltage L2-N
Float32V1R
122
Connector 1 voltage L3-N
Float32V1R
142
Connector 1 current L1
Float32A1R
162
Connector 1 current L2
Float32A1R
182
Connector 1 current L3
Float32A1R
202
Connector 1 active power L1
Float32kW1R
222
Connector 1 active power L2
Float32kW1R
242
Connector 1 active power L3
Float32kW1R
262
Connector 1 active power, total
Float32kW1R
282
Connector 1 power factor
Float32-1R
302
Connector 1 energy of running session
Total imported active energy in the running charging session.
Float32kWh1R
442
Connector 1 EV max power
Maximum power detected in the running charging session.
Float32kW1R
462
Connector 1 EV planned energy
Energy planned to be delivered in the running charging session.
Float32kWh1R
531
Connector 1 selected charging mode
1 = fast mode, 2 = smart mode.
Int16-1R
5410
Connector 1 RFID UID of last session
Ascii-1R
1001
Connector 2 status
INCH Duo only. Same enumeration as connector 1.
Int16-1R
1011
Connector 2 measured vehicle number of phases
INCH Duo only. Same enumeration as connector 1.
Int16-1R
1022
Connector 2 EV max phase current
Float32A1R
1042
Connector 2 target current from power management or Modbus
Float32A1R
1062
Connector 2 frequency
Float32Hz1R
1082
Connector 2 voltage L1-N
Float32V1R
1102
Connector 2 voltage L2-N
Float32V1R
1122
Connector 2 voltage L3-N
Float32V1R
1142
Connector 2 current L1
Float32A1R
1162
Connector 2 current L2
Float32A1R
1182
Connector 2 current L3
Float32A1R
1202
Connector 2 active power L1
Float32kW1R
1222
Connector 2 active power L2
Float32kW1R
1242
Connector 2 active power L3
Float32kW1R
1262
Connector 2 active power, total
Float32kW1R
1282
Connector 2 power factor
Float32-1R
1302
Connector 2 energy of running session
Float32kWh1R
1442
Connector 2 EV max power
Float32kW1R
1462
Connector 2 EV planned energy
Float32kWh1R
1531
Connector 2 selected charging mode
1 = fast mode, 2 = smart mode.
Int16-1R
15410
Connector 2 RFID UID of last session
Ascii-1R
99010
Charger serial number
Ascii-1R
100010
Charger model
Ascii-1R
10105
Charger hardware version
Ascii-1R
10155
Charger software version
Ascii-1R
10202
Charger number of connectors
Int32-1R
10221
Connector 1 connector type
1 = socket type 2, 2 = cable type 2, 3 = socket household, 4 = unknown.
Int16-1R
10231
Connector 1 number of phases
0 = three phases, 1 = single phase (L1), 2 = single phase (L2), 3 = single phase (L3), 4 = unknown, 5 = two phases.
Int16-1R
10241
Connector 1 L1 connected to phase
1 = L1, 2 = L2, 3 = L3.
Int16-1R
10251
Connector 1 L2 connected to phase
1 = L1, 2 = L2, 3 = L3.
Int16-1R
10261
Connector 1 L3 connected to phase
1 = L1, 2 = L2, 3 = L3.
Int16-1R
10282
Connector 1 custom max current
Float32A1R
11221
Connector 2 connector type
INCH Duo only. 1 = socket type 2, 2 = cable type 2, 3 = socket household, 4 = unknown.
Int16-1R
11231
Connector 2 number of phases
INCH Duo only.
Int16-1R
11241
Connector 2 L1 connected to phase
INCH Duo only. 1 = L1, 2 = L2, 3 = L3.
Int16-1R
11251
Connector 2 L2 connected to phase
INCH Duo only. 1 = L1, 2 = L2, 3 = L3.
Int16-1R
11261
Connector 2 L3 connected to phase
INCH Duo only. 1 = L1, 2 = L2, 3 = L3.
Int16-1R
11282
Connector 2 custom max current
Float32A1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Etrel, "INCH and DUO SmartHome Modbus TCP Registers master SPECIFICATIONS - V6.0 - 072025_02.xlsx" (sheets 'ReadRegisters', 'Write registers' and 'Enumerations'), the vendor register list attached to "Modbus Communication with INCH products" in the Etrel Knowledge Centre (etrel.atlassian.net, page 3485665834) and downloadable without a login. The document states that the register numbers are the actual address values placed in the messages (not Modicon names) and that all values are big-endian, so this file uses zero-based addressing with high word first. Reading uses function code 04 on port 502, writing uses function code 16 (the write table is a separate list, so those entries are marked W); the vendor lists the unit identifier as free (the charger answers on the configured one, evcc uses 1). Connector 2 registers exist on the INCH Duo; on a single-connector INCH they are simply absent. Left out on purpose: the 64-bit rows the document defines -- running session duration (32), running session departure time (36), running session ID (40) and the lifetime meter value (48, int64 mWh) -- because the app has no 64-bit integer type, and the same rows' 32-bit counterparts do not exist. The building-load-guard and power-cluster blocks at 2000+ live on the second Modbus socket (port 503) and are not part of this device map.