Enapter · Hydrogen dryer

Dryer 4.1 (DRY 4.1) Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
21
Device version, upper
Firmware version major.
UInt16-1R
31
Device version, patch
Firmware version patch.
UInt16-1R
42
Device version, build
Firmware build ID.
UInt32-1R
10001
State
Current dryer state.
UInt16-1R
10011
Saved state
Saved dryer state.
UInt16-1R
10021
State flags
State flags as a bit field.
UInt16-1R
10032
Drying start
Drying cycle start time.
UInt32-1R
10052
Drying saved
Saved drying time.
UInt32-1R
10072
Drying passed
Time passed in the current drying cycle.
UInt32-1R
10092
Drying interval
Drying cycle interval.
UInt32-1R
10111
Error
Error flags as a bit field.
UInt16-1R
10121
Warning
Warning flags as a bit field.
UInt16-1R
10131
Error, extra
Extended error flags as a bit field.
UInt16-1R
10141
Warning, extra
Extended warning flags as a bit field.
UInt16-1R
10152
Current heap size
Current heap memory size in bytes.
UInt32B1R
10172
Minimum heap size
Minimum heap memory size in bytes.
UInt32B1R
10551
Digital inputs
Digital inputs as a bit field.
UInt16-1R
10561
Digital outputs
Digital outputs as a bit field.
UInt16-1R
10571
Fan F100 speed
UInt16rpm1R
10581
Fan F101 speed
UInt16rpm1R
10591
Fan F102 speed
UInt16rpm1R
10602
Temperature TT00
Float32°C1R
10622
Temperature TT01
Float32°C1R
10642
Input pressure PT00
Float32bar1R
10662
Output pressure PT01
Float32bar1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Register map of the Enapter Dryer 4.1 as published for firmware 4.0.0; Enapter versions this document per firmware release. The vendor states port 502 and, for the slave address, only that 'any Modbus address can be set, does not affect communication', so unit 1 is a placeholder, not a documented factory value. Addresses are the document's own register numbers. Unlike the EL 2.1 and EL 4.1 pages, this page carries no 'Modbus Data Model' paragraph defining its numbers as protocol addresses, but it uses the same Enapter numbering (holding register 0, input registers from 2), so the numbers are used unchanged as zero-based wire addresses; check one read against a known value before trusting the offset. Data is big-endian, high word first, and boolean fields are 16-bit registers where 0 is false. Configuration registers are written as a transaction: open with 4000, write, commit with 4001, then read the result at 4002. Left out because the format has no 64-bit type: holding 0 (system time), input 1019, 1023, 1027, 1031, 1035, 1039, 1043, 1047 and 1051 (state save count, reboot count, lifetime and the six start/stop timestamps). Source: Enapter device handbook, 'DRY 4.1 FW 4.0.0 Modbus TCP Communication Interface'.