5PX / 9PX / 9SX with Network-M2 (INDGW-M2) card Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
11
On battery
TRUE if the UPS is on battery.
Binary-1R
101
On bypass
TRUE if the UPS is on bypass.
Binary-1R
111
System normal
TRUE if the UPS is operating normally.
Binary-1R
161
UPS off
TRUE if the UPS is no longer supplying power to the load.
Binary-1R
321
Static position switch
TRUE if the static switch is on.
Binary-1R
331
Critical bus breaker
TRUE if the critical bus breaker is closed.
Binary-1R
341
Bypass breaker
TRUE if the bypass breaker is closed.
Binary-1R
351
Backfeed breaker
TRUE if the backfeed breaker is closed.
Binary-1R
361
Bypass input power
TRUE if the bypass input power is available.
Binary-1R
371
Maintenance isolation breaker (MIB)
TRUE if the MIB is closed.
Binary-1R
381
Maintenance bypass breaker (MBB)
TRUE if the MBB is closed.
Binary-1R
391
Maintenance bypass input (MBP)
TRUE if the MBP has input power.
Binary-1R
1121
Rectifier status
TRUE if the rectifier is on.
Binary-1R
1131
Rectifier input status
TRUE if rectifier input is present.
Binary-1R
1141
Bypass status
TRUE if bypass is on.
Binary-1R
1151
Bypass input status
TRUE if bypass input voltage is out of limits.
Binary-1R
1161
Input circuit breaker status (CB1)
TRUE if CB1 is closed.
Binary-1R
1171
Battery disconnect status
TRUE if the battery disconnect is closed.
Binary-1R
1181
Inverter disconnect status
TRUE if the UPS is online and the inverter is supplying power.
Binary-1R
1191
Inverter status
TRUE if the inverter is on.
Binary-1R
1201
UPM normal
TRUE if the UPM is normal.
Binary-1R
1211
UPM on battery
TRUE if the UPM is on battery.
Binary-1R
1221
UPM bypass (off line)
TRUE if the UPM is offline.
Binary-1R
1231
UPM notice
TRUE if there is a UPM warning advisory.
Binary-1R
1241
UPM alarm
TRUE if there is a UPM major alarm.
Binary-1R
2411
Emergency shutdown (EPO) command
TRUE if an emergency power-off command was issued.
Binary-1R
2491
Bypass not available
TRUE if the bypass input voltage is not available for transfer.
Binary-1R
2501
Rectifier breaker open
TRUE if the rectifier/charger breaker is open.
Binary-1R
2511
Battery contactor open
TRUE if the battery contactor/breaker is open.
Binary-1R
2521
Inverter contactor open
TRUE if the inverter output contactor/breaker is open.
Binary-1R
2531
Bypass breaker open
TRUE if the bypass breaker is open.
Binary-1R

Notes

UPS with the Eaton Gigabit Network Card (Network-M2 / INDGW-M2), which runs the Modbus/TCP server on port 502; the card is available for the 5PX, 9PX and 9SX families and for larger three-phase UPSs. Values come from the Eaton Master Modbus Register Map (document 164201391 Rev F): status bits are input status (function 02, 1xxxx numbering) and meters are input registers (function 04, 3xxxx numbering). Register numbers in this file are the supplier's 1-based register numbers, so register 1 is 30001 (wire address 0). All meter values are integers with the documented scale applied (/10 or /100). The master map is generic: the document warns that not all registers apply to all UPS models. This seed lists the core status bits and the output/input/battery meters; the bar-chart and service-only registers, the UPM 1-8 LED banks, the outlet/group alarm bits and the ESS/high-efficiency bit (input status register 4, which is 'Reserved' in Rev D of the master map and only appears as a named bit in the newer Rev F that is not publicly reachable) are left out.