SDM630MCT (CT-operated three-phase DIN meter) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
Phase 1 line to neutral volts
Float32V1R
22
Phase 2 line to neutral volts
Float32V1R
42
Phase 3 line to neutral volts
Float32V1R
62
Phase 1 current
Float32A1R
82
Phase 2 current
Float32A1R
102
Phase 3 current
Float32A1R
122
Phase 1 active power
Float32W1R
142
Phase 2 active power
Float32W1R
162
Phase 3 active power
Float32W1R
182
Phase 1 apparent power
Float32VA1R
202
Phase 2 apparent power
Float32VA1R
222
Phase 3 apparent power
Float32VA1R
242
Phase 1 reactive power
Float32VAr1R
262
Phase 2 reactive power
Float32VAr1R
282
Phase 3 reactive power
Float32VAr1R
302
Phase 1 power factor
Sign shows the direction of the current: positive = forward, negative = reverse.
Float32-1R
322
Phase 2 power factor
Float32-1R
342
Phase 3 power factor
Float32-1R
362
Phase 1 phase angle
Float32degrees1R
382
Phase 2 phase angle
Float32degrees1R
402
Phase 3 phase angle
Float32degrees1R
422
Average line to neutral volts
Float32V1R
462
Average line current
Float32A1R
482
Sum of line currents
Float32A1R
522
Total system power
Float32W1R
562
Total system voltamps
Float32VA1R
602
Total system VAr
Float32VAr1R
622
Total system power factor
Float32-1R
662
Total system phase angle
Float32degrees1R
702
Frequency of supply voltages
Float32Hz1R
722
Total import kWh
Float32kWh1R
742
Total export kWh
Float32kWh1R
762
Total import kVArh
Float32kVArh1R
782
Total export kVArh
Float32kVArh1R
802
Total VAh
Float32kVAh1R
822
Ah
Float32Ah1R
842
Total system power demand
Power sum demand, calculated as import - export.
Float32W1R
862
Maximum total system power demand
Float32W1R
1002
Total system VA demand
Float32VA1R
1022
Maximum total system VA demand
Float32VA1R
1042
Neutral current demand
Float32A1R
1062
Maximum neutral current demand
Float32A1R
1082
Total system reactive power demand
Float32VAr1R
1102
Maximum total system reactive power demand
Float32VAr1R
2002
Line 1 to line 2 volts
Float32V1R
2022
Line 2 to line 3 volts
Float32V1R
2042
Line 3 to line 1 volts
Float32V1R
2062
Average line to line volts
Float32V1R
2242
Neutral current
Float32A1R
2342
Phase 1 L/N volts THD
Float32%1R
2362
Phase 2 L/N volts THD
Float32%1R
2382
Phase 3 L/N volts THD
Float32%1R
2402
Phase 1 current THD
Float32%1R
2422
Phase 2 current THD
Float32%1R
2442
Phase 3 current THD
Float32%1R
2482
Average line to neutral volts THD
Float32%1R
2502
Average line current THD
Float32%1R
2542
Total system power factor, phase angle form
The vendor table labels this row "Total system power factor (1)" but gives degrees as the unit.
Float32degrees1R
2582
Phase 1 current demand
Float32A1R
2602
Phase 2 current demand
Float32A1R
2622
Phase 3 current demand
Float32A1R
2642
Maximum phase 1 current demand
Float32A1R
2662
Maximum phase 2 current demand
Float32A1R
2682
Maximum phase 3 current demand
Float32A1R
3342
Line 1 to line 2 volts THD
Float32%1R
3362
Line 2 to line 3 volts THD
Float32%1R
3382
Line 3 to line 1 volts THD
Float32%1R
3402
Average line to line volts THD
Float32%1R
3422
Total kWh (import + export)
Float32kWh1R
3442
Total kVArh (import + export)
Float32kVArh1R
3462
L1 import kWh
Float32kWh1R
3482
L2 import kWh
Float32kWh1R
3502
L3 import kWh
Float32kWh1R
3522
L1 export kWh
Float32kWh1R
3542
L2 export kWh
Float32kWh1R
3562
L3 export kWh
Float32kWh1R
3582
L1 total kWh
Float32kWh1R
3602
L2 total kWh
Float32kWh1R
3622
L3 total kWh
Float32kWh1R
3642
L1 import kVArh
Float32kVArh1R
3662
L2 import kVArh
Float32kVArh1R
3682
L3 import kVArh
Float32kVArh1R
3702
L1 export kVArh
Float32kVArh1R
3722
L2 export kVArh
Float32kVArh1R
3742
L3 export kVArh
Float32kVArh1R
3762
L1 total kVArh
Float32kVArh1R
3782
L2 total kVArh
Float32kVArh1R
3802
L3 total kVArh
Float32kVArh1R
3842
Resettable total active energy
Float32kWh1R
3862
Resettable total reactive energy
Float32kVArh1R
3882
Resettable import active energy
Float32kWh1R
3902
Resettable export active energy
Float32kWh1R
3922
Resettable import reactive energy
Float32kVArh1R
3942
Resettable export reactive energy
Float32kVArh1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway using the factory serial settings above. Source: Eastron "SDM630MCT Series - MODBUS Protocol", V1.7, section 1.2.1 (input registers, table 1.2.1) and section 1.3.1 (holding register parameters, table 1.3.1), published at https://eastroneurope.com/images/uploads/products/protocol/SDM630MCT_MODBUS_Protocol_V1.7.pdf . The document numbers the measurements as 30001... and each 4-byte parameter as 40001...; its "Modbus Protocol Start Address Hex" column is the wire address and is used here unchanged (e.g. 30001 = 0x0000 = 0, 40001 = 0x0000 = 0). All measured values and all setup parameters are IEEE-754 single precision floats (high word first), measurements read with function code 04 and settings with function code 03/16. Factory serial settings from the holding-register table: 9600 baud (register 40029 = 0x1C = 28, value 2 = 9600 is the documented default), one stop bit and no parity (register 40019 = 0x12 = 18, value 0 is the documented default), Modbus node address 1 (register 40021 = 0x14 = 20, value 1 is the documented default) and 8 data bits per section 1.1. This is the CT-operated SDM630 variant with its own map; the direct-connected SDM630-Modbus is a separate seed. Registers that the table leaves out (reserved ranges) are not listed.