SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus register map

Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.

Default configuration

Protocol
Modbus RTU over RS-485
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
None
Data bits
8
Stop bits
1

To read this device over Modbus RTU in Modbus Connect:

  1. In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
  2. Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.

The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
02
Energy
Register 30001 or 40001. Raw integer energy value; the engineering value is the raw value multiplied by the unit factor at address 2 and named by the unit ID at address 7. The document's worked example reads raw 12345 with factor 1 and unit ID 8 as 12345 MJ, and the float copy at address 8 reads 12345.0.
Int32-1R
21
Energy unit factor
Multiplier applied to the integer energy value (document footnote 1); 1 in the worked example.
UInt16-1R
71
Energy unit ID
Unit code from the module's codes-and-units table: 1 mWh, 2 Wh, 3 kWh, 4 MWh, 5 GWh, 6 J, 7 kJ, 8 MJ, 9 GJ, 10 cal, 11 kcal, 12 Mcal, 13 Gcal, 14 Btu, 15 kBtu, 16 MBtu, 17 GBtu.
UInt16-1R
82
Energy (float)
IEEE-754 copy of the energy value, already in the unit given by the unit ID register.
Float32-1R
102
Volume
Raw integer volume value, scaled by the unit factor at address 12 and named by the unit ID at address 17.
Int32-1R
121
Volume unit factor
Multiplier applied to the integer volume value (document footnote 1).
UInt16-1R
171
Volume unit ID
Unit code: 18 ml, 19 l, 20 m3, 21 mGal, 22 Gal, 23 kGal, 24 MGal, 25 ml/h, 26 l/h, 27 m3/h.
UInt16-1R
182
Volume (float)
IEEE-754 copy of the volume value.
Float32-1R
202
Power
Raw integer power value, scaled by the unit factor at address 22 and named by the unit ID at address 27.
Int32-1R
221
Power unit factor
Multiplier applied to the integer power value (document footnote 1).
UInt16-1R
271
Power unit ID
Unit code: 30 kGal/min, 31 MGal/min, 32 mW, 33 W, 34 kW, 35 MW, 36 GW.
UInt16-1R
282
Power (float)
IEEE-754 copy of the power value.
Float32-1R
302
Flow
Raw integer flow value, scaled by the unit factor at address 32 and named by the unit ID at address 37.
Int32-1R
321
Flow unit factor
Multiplier applied to the integer flow value (document footnote 1).
UInt16-1R
371
Flow unit ID
Unit code, from the same codes-and-units table as the other unit ID registers (e.g. 27 m3/h).
UInt16-1R
382
Flow (float)
IEEE-754 copy of the flow value.
Float32-1R
401
Forward temperature
Forward (start) temperature; Int16 with one decimal place, so the raw value is multiplied by 0.1 (document footnote 4). The unit ID register at address 45 names the unit (41 degC, 42 degF).
Int16-0.1R
451
Forward temperature unit ID
Unit code: 41 degC, 42 degF.
UInt16-1R
462
Forward temperature (float)
IEEE-754 copy of the forward temperature.
Float32-1R
481
Return temperature
Return temperature; Int16 with one decimal place, so the raw value is multiplied by 0.1 (document footnote 4). The block prints value, unit name, unit ID and float, with no unit-factor register.
Int16-0.1R
531
Return temperature unit ID
Unit code: 41 degC, 42 degF.
UInt16-1R
542
Return temperature (float)
IEEE-754 copy of the return temperature.
Float32-1R
561
Temperature difference
Temperature difference (forward minus return); Int16 with one decimal place, so the raw value is multiplied by 0.1 (document footnote 4).
Int16-0.1R
611
Temperature difference unit ID
Unit code: 41 degC, 42 degF.
UInt16-1R
622
Temperature difference (float)
IEEE-754 copy of the temperature difference.
Float32-1R
642
Tariff energy 1
Tariff register 1 energy, scaled by the unit factor at address 66 and named by the unit ID at address 71.
Int32-1R
661
Tariff energy 1 unit factor
Multiplier applied to the tariff-1 energy value (document footnote 1).
UInt16-1R
711
Tariff energy 1 unit ID
Unit code from the codes-and-units table.
UInt16-1R
722
Tariff energy 1 (float)
IEEE-754 copy of tariff register 1 energy.
Float32-1R
742
Tariff volume 1
Tariff register 1 volume, scaled by the unit factor at address 76.
Int32-1R
761
Tariff volume 1 unit factor
Multiplier applied to the tariff-1 volume value (document footnote 1).
UInt16-1R
811
Tariff volume 1 unit ID
Unit code from the codes-and-units table.
UInt16-1R
822
Tariff volume 1 (float)
IEEE-754 copy of tariff register 1 volume.
Float32-1R
1542
Pulse input volume 2
Volume counted on pulse input 2, scaled by the unit factor at address 156.
Int32-1R
1561
Pulse input volume 2 unit factor
Multiplier applied to the pulse-input-2 volume (document footnote 1).
UInt16-1R
1611
Pulse input volume 2 unit ID
Unit code from the codes-and-units table.
UInt16-1R
1622
Pulse input volume 2 (float)
IEEE-754 copy of the pulse-input-2 volume.
Float32-1R
1641
Error code
Only one error is shown at a time, by priority. 0x0000 no error; 0x0100 no communication with the meter; 0x0008 basic parameter error in flash or RAM; 0x0004 defective primary voltage (mains unit) - supply from backup battery; 0x0028 hardware error of the ultrasonic measurement; 0x0050 temperature range exceeded; 0x0070 no meaningful ultrasonic signal / air in the measuring path; 0x0084 battery almost flat; 0x00B0 forward and return sensor reversed; 0x00D0 wrong direction of flow; 0x00F0 leakage detected; 0x0010 communication not possible (update rate too fast).
Hex-1R
1652
Heat meter serial number (fixed)
Serial number of the heat meter as a 32-bit number.
UInt32-1R
1674
Heat meter serial number (ASCII)
Serial number of the heat meter as 8 ASCII characters.
Ascii-1R
1711
Periodical log 0 date - day
Day of the newest periodical log entry.
UInt16-1R
1721
Periodical log 0 date - month
Month of the newest periodical log entry.
UInt16-1R
1731
Periodical log 0 date - year
Year of the newest periodical log entry.
UInt16-1R
1742
Periodical log 0 energy
Energy stored in the newest periodical log entry, scaled by the unit factor at address 176.
Int32-1R
1761
Periodical log 0 energy unit factor
Multiplier applied to the logged energy value (document footnote 1).
UInt16-1R
1811
Periodical log 0 energy unit ID
Unit code from the codes-and-units table.
UInt16-1R
1822
Periodical log 0 energy (float)
IEEE-754 copy of the logged energy value.
Float32-1R
1842
Periodical log 0 volume
Volume stored in the newest periodical log entry, scaled by the unit factor at address 186.
Int32-1R
1861
Periodical log 0 volume unit factor
Multiplier applied to the logged volume value (document footnote 1).
UInt16-1R
1911
Periodical log 0 volume unit ID
Unit code from the codes-and-units table.
UInt16-1R
1922
Periodical log 0 volume (float)
IEEE-754 copy of the logged volume value.
Float32-1R
20002
Module serial number
Register 32001, serial number of the Modbus RTU module.
UInt32-1R
20022
Module model number
Register 32003, model number of the Modbus RTU module.
UInt32-1R
20041
Module firmware version
Register 32005, firmware version of the Modbus RTU module.
UInt16-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Diehl Metering 'Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8', 04/2019 revision (sections 6.1.1 automatic slave ID, 6.2.1 read-only registers, 6.2.2 configuration registers, 6.3 unit-ID table, 6.6 error codes). The delivered citation is the compteur-energie.com notice (SHA-256 69ba6576bc00968aec451f6757fc82bedaa5d7867f64b0d2868bb84d338a7de6), which now answers 403; this review re-read the same 04/2019 revision as served by armatec.com, SHA-256 4bd1202a917df035f16f35f896994b98a1f1d079d25045b0e5b8da88ff0e4cb5, and Diehl's 12/2023 edition, SHA-256 4b5bedca26488452419e5c7de3f0ff0f0f32d23127df9500ee559c444905b430, which carries the same map but defaults the update rate to 600 instead of the 04/2019 150, so the 04/2019 revision was used for register 1001's default. Factory frame from 6.2.2: slave ID default 0x0101, baud rate 9600, data bits 8, parity 'N' (78), stop bits 1. Addressing: the table prints both a Modicon reference (30001/40001) and a 0-based 'Modbus Address' column; the seed stores the latter, which is why it declares zero_based. The read-only block is served through both the input area (30001+) and the holding area (40001+), so it is seeded once, as input registers. Int32 values are multiplied by their unit-factor register (footnote 1); the three Int16 temperatures at 40/48/56 carry one decimal place and are scaled by 0.1 (footnote 4). No byte or word order is printed for the Int32/IEEE-754 values, so BigEndian + HighFirst is declared as the Modbus convention, with LowFirst as the fallback. Omitted on purpose: the 'Unit name' ASCII rows, Tariff energy/volume 2-4 and pulse input 1 (same block shape as tariff 1 and pulse input 2, which are seeded), and periodical logs 1-N (only log 0 is seeded).