Diehl Metering · Heat meter
SHARKY 775 / SCYLAR INT 8 with Modbus RTU communication module Modbus register map
Serial device: in Modbus Connect, choose “Add to existing device” and pick the serial (RTU) device you created on your COM port.
Default configuration
- Protocol
- Modbus RTU over RS-485
- Unit ID
- 1
- Addressing
- 0-based
- Byte order
- Big endian
- Word order
- High word first
- Baud rate
- 9600
- Parity
- None
- Data bits
- 8
- Stop bits
- 1
To read this device over Modbus RTU in Modbus Connect:
- In Modbus Connect, add a serial (RTU) device on your COM port with the serial settings and unit ID shown above.
- Click Add to Modbus Connect (or open the downloaded JSON), choose “Add to existing device” and pick that serial device. Its registers, byte order and word order are added; the serial device keeps its own line settings.
The “Add device” tab creates a Modbus TCP device (IP address and port), so use it only when you reach this device through a Modbus RTU-to-TCP gateway set to the serial settings above.
Register map
| Address | Count | Name | Type | Unit | Scale | Access |
|---|---|---|---|---|---|---|
| 0 | 2 | Energy Register 30001 or 40001. Raw integer energy value; the engineering value is the raw value multiplied by the unit factor at address 2 and named by the unit ID at address 7. The document's worked example reads raw 12345 with factor 1 and unit ID 8 as 12345 MJ, and the float copy at address 8 reads 12345.0. | Int32 | - | 1 | R |
| 2 | 1 | Energy unit factor Multiplier applied to the integer energy value (document footnote 1); 1 in the worked example. | UInt16 | - | 1 | R |
| 7 | 1 | Energy unit ID Unit code from the module's codes-and-units table: 1 mWh, 2 Wh, 3 kWh, 4 MWh, 5 GWh, 6 J, 7 kJ, 8 MJ, 9 GJ, 10 cal, 11 kcal, 12 Mcal, 13 Gcal, 14 Btu, 15 kBtu, 16 MBtu, 17 GBtu. | UInt16 | - | 1 | R |
| 8 | 2 | Energy (float) IEEE-754 copy of the energy value, already in the unit given by the unit ID register. | Float32 | - | 1 | R |
| 10 | 2 | Volume Raw integer volume value, scaled by the unit factor at address 12 and named by the unit ID at address 17. | Int32 | - | 1 | R |
| 12 | 1 | Volume unit factor Multiplier applied to the integer volume value (document footnote 1). | UInt16 | - | 1 | R |
| 17 | 1 | Volume unit ID Unit code: 18 ml, 19 l, 20 m3, 21 mGal, 22 Gal, 23 kGal, 24 MGal, 25 ml/h, 26 l/h, 27 m3/h. | UInt16 | - | 1 | R |
| 18 | 2 | Volume (float) IEEE-754 copy of the volume value. | Float32 | - | 1 | R |
| 20 | 2 | Power Raw integer power value, scaled by the unit factor at address 22 and named by the unit ID at address 27. | Int32 | - | 1 | R |
| 22 | 1 | Power unit factor Multiplier applied to the integer power value (document footnote 1). | UInt16 | - | 1 | R |
| 27 | 1 | Power unit ID Unit code: 30 kGal/min, 31 MGal/min, 32 mW, 33 W, 34 kW, 35 MW, 36 GW. | UInt16 | - | 1 | R |
| 28 | 2 | Power (float) IEEE-754 copy of the power value. | Float32 | - | 1 | R |
| 30 | 2 | Flow Raw integer flow value, scaled by the unit factor at address 32 and named by the unit ID at address 37. | Int32 | - | 1 | R |
| 32 | 1 | Flow unit factor Multiplier applied to the integer flow value (document footnote 1). | UInt16 | - | 1 | R |
| 37 | 1 | Flow unit ID Unit code, from the same codes-and-units table as the other unit ID registers (e.g. 27 m3/h). | UInt16 | - | 1 | R |
| 38 | 2 | Flow (float) IEEE-754 copy of the flow value. | Float32 | - | 1 | R |
| 40 | 1 | Forward temperature Forward (start) temperature; Int16 with one decimal place, so the raw value is multiplied by 0.1 (document footnote 4). The unit ID register at address 45 names the unit (41 degC, 42 degF). | Int16 | - | 0.1 | R |
| 45 | 1 | Forward temperature unit ID Unit code: 41 degC, 42 degF. | UInt16 | - | 1 | R |
| 46 | 2 | Forward temperature (float) IEEE-754 copy of the forward temperature. | Float32 | - | 1 | R |
| 48 | 1 | Return temperature Return temperature; Int16 with one decimal place, so the raw value is multiplied by 0.1 (document footnote 4). The block prints value, unit name, unit ID and float, with no unit-factor register. | Int16 | - | 0.1 | R |
| 53 | 1 | Return temperature unit ID Unit code: 41 degC, 42 degF. | UInt16 | - | 1 | R |
| 54 | 2 | Return temperature (float) IEEE-754 copy of the return temperature. | Float32 | - | 1 | R |
| 56 | 1 | Temperature difference Temperature difference (forward minus return); Int16 with one decimal place, so the raw value is multiplied by 0.1 (document footnote 4). | Int16 | - | 0.1 | R |
| 61 | 1 | Temperature difference unit ID Unit code: 41 degC, 42 degF. | UInt16 | - | 1 | R |
| 62 | 2 | Temperature difference (float) IEEE-754 copy of the temperature difference. | Float32 | - | 1 | R |
| 64 | 2 | Tariff energy 1 Tariff register 1 energy, scaled by the unit factor at address 66 and named by the unit ID at address 71. | Int32 | - | 1 | R |
| 66 | 1 | Tariff energy 1 unit factor Multiplier applied to the tariff-1 energy value (document footnote 1). | UInt16 | - | 1 | R |
| 71 | 1 | Tariff energy 1 unit ID Unit code from the codes-and-units table. | UInt16 | - | 1 | R |
| 72 | 2 | Tariff energy 1 (float) IEEE-754 copy of tariff register 1 energy. | Float32 | - | 1 | R |
| 74 | 2 | Tariff volume 1 Tariff register 1 volume, scaled by the unit factor at address 76. | Int32 | - | 1 | R |
| 76 | 1 | Tariff volume 1 unit factor Multiplier applied to the tariff-1 volume value (document footnote 1). | UInt16 | - | 1 | R |
| 81 | 1 | Tariff volume 1 unit ID Unit code from the codes-and-units table. | UInt16 | - | 1 | R |
| 82 | 2 | Tariff volume 1 (float) IEEE-754 copy of tariff register 1 volume. | Float32 | - | 1 | R |
| 154 | 2 | Pulse input volume 2 Volume counted on pulse input 2, scaled by the unit factor at address 156. | Int32 | - | 1 | R |
| 156 | 1 | Pulse input volume 2 unit factor Multiplier applied to the pulse-input-2 volume (document footnote 1). | UInt16 | - | 1 | R |
| 161 | 1 | Pulse input volume 2 unit ID Unit code from the codes-and-units table. | UInt16 | - | 1 | R |
| 162 | 2 | Pulse input volume 2 (float) IEEE-754 copy of the pulse-input-2 volume. | Float32 | - | 1 | R |
| 164 | 1 | Error code Only one error is shown at a time, by priority. 0x0000 no error; 0x0100 no communication with the meter; 0x0008 basic parameter error in flash or RAM; 0x0004 defective primary voltage (mains unit) - supply from backup battery; 0x0028 hardware error of the ultrasonic measurement; 0x0050 temperature range exceeded; 0x0070 no meaningful ultrasonic signal / air in the measuring path; 0x0084 battery almost flat; 0x00B0 forward and return sensor reversed; 0x00D0 wrong direction of flow; 0x00F0 leakage detected; 0x0010 communication not possible (update rate too fast). | Hex | - | 1 | R |
| 165 | 2 | Heat meter serial number (fixed) Serial number of the heat meter as a 32-bit number. | UInt32 | - | 1 | R |
| 167 | 4 | Heat meter serial number (ASCII) Serial number of the heat meter as 8 ASCII characters. | Ascii | - | 1 | R |
| 171 | 1 | Periodical log 0 date - day Day of the newest periodical log entry. | UInt16 | - | 1 | R |
| 172 | 1 | Periodical log 0 date - month Month of the newest periodical log entry. | UInt16 | - | 1 | R |
| 173 | 1 | Periodical log 0 date - year Year of the newest periodical log entry. | UInt16 | - | 1 | R |
| 174 | 2 | Periodical log 0 energy Energy stored in the newest periodical log entry, scaled by the unit factor at address 176. | Int32 | - | 1 | R |
| 176 | 1 | Periodical log 0 energy unit factor Multiplier applied to the logged energy value (document footnote 1). | UInt16 | - | 1 | R |
| 181 | 1 | Periodical log 0 energy unit ID Unit code from the codes-and-units table. | UInt16 | - | 1 | R |
| 182 | 2 | Periodical log 0 energy (float) IEEE-754 copy of the logged energy value. | Float32 | - | 1 | R |
| 184 | 2 | Periodical log 0 volume Volume stored in the newest periodical log entry, scaled by the unit factor at address 186. | Int32 | - | 1 | R |
| 186 | 1 | Periodical log 0 volume unit factor Multiplier applied to the logged volume value (document footnote 1). | UInt16 | - | 1 | R |
| 191 | 1 | Periodical log 0 volume unit ID Unit code from the codes-and-units table. | UInt16 | - | 1 | R |
| 192 | 2 | Periodical log 0 volume (float) IEEE-754 copy of the logged volume value. | Float32 | - | 1 | R |
| 2000 | 2 | Module serial number Register 32001, serial number of the Modbus RTU module. | UInt32 | - | 1 | R |
| 2002 | 2 | Module model number Register 32003, model number of the Modbus RTU module. | UInt32 | - | 1 | R |
| 2004 | 1 | Module firmware version Register 32005, firmware version of the Modbus RTU module. | UInt16 | - | 1 | R |
Read this device live with Modbus Connect, free for Windows, macOS and Linux
Related guides
Notes
Source: Diehl Metering 'Modbus RTU Communication Module for SHARKY 775 and SCYLAR INT 8', 04/2019 revision (sections 6.1.1 automatic slave ID, 6.2.1 read-only registers, 6.2.2 configuration registers, 6.3 unit-ID table, 6.6 error codes). The delivered citation is the compteur-energie.com notice (SHA-256 69ba6576bc00968aec451f6757fc82bedaa5d7867f64b0d2868bb84d338a7de6), which now answers 403; this review re-read the same 04/2019 revision as served by armatec.com, SHA-256 4bd1202a917df035f16f35f896994b98a1f1d079d25045b0e5b8da88ff0e4cb5, and Diehl's 12/2023 edition, SHA-256 4b5bedca26488452419e5c7de3f0ff0f0f32d23127df9500ee559c444905b430, which carries the same map but defaults the update rate to 600 instead of the 04/2019 150, so the 04/2019 revision was used for register 1001's default. Factory frame from 6.2.2: slave ID default 0x0101, baud rate 9600, data bits 8, parity 'N' (78), stop bits 1. Addressing: the table prints both a Modicon reference (30001/40001) and a 0-based 'Modbus Address' column; the seed stores the latter, which is why it declares zero_based. The read-only block is served through both the input area (30001+) and the holding area (40001+), so it is seeded once, as input registers. Int32 values are multiplied by their unit-factor register (footnote 1); the three Int16 temperatures at 40/48/56 carry one decimal place and are scaled by 0.1 (footnote 4). No byte or word order is printed for the Int32/IEEE-754 values, so BigEndian + HighFirst is declared as the Modbus convention, with LowFirst as the fallback. Omitted on purpose: the 'Unit name' ASCII rows, Tariff energy/volume 2-4 and pulse input 1 (same block shape as tariff 1 and pulse input 2, which are seeded), and periodical logs 1-N (only log 0 is seeded).