VLT Micro Drive FC 51 Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
500001
Control word (FC profile)
Control word according to the FC profile; bit definitions in section 7.1.1 of the Modbus RTU operating instruction.
UInt16-1RW
500101
Bus reference (FC profile)
Speed reference written by the bus master. Scaling follows parameter 3-00/1-00 (reference/feedback unit).
Int16-1RW
502001
Status word (FC profile)
Status word according to the FC profile; bit definitions in section 7.1.1 of the Modbus RTU operating instruction.
UInt16-1R
502101
Main actual value (FC profile)
Main actual value sent with the status word; scaled according to parameter 3-00/1-00.
Int16-1R
30202
Minimum reference
Minimum reference for the drive, in the reference unit selected in 3-00.
Int32-0.001RW
30302
Maximum reference
Maximum reference for the drive, in the reference unit selected in 3-00.
Int32-0.001RW
31001
Preset reference
Preset reference 0, in percent of the reference range.
Int16%0.01RW
31101
Jog speed
Jog speed used by the Jog function.
UInt16Hz0.1RW
31201
Catch up/slow down value
Percentage value added to or subtracted from the actual reference.
Int16%0.01RW
31401
Preset relative reference
Relative reference in percent of the actual reference.
Int16%0.01RW
31501
Reference resource 1
Handling of the reference from resource 1; options are listed in the programming guide.
UInt16-1RW
31601
Reference resource 2
Handling of the reference from resource 2.
UInt16-1RW
31701
Reference resource 3
Handling of the reference from resource 3.
UInt16-1RW
34001
Ramp 1 type
0 = linear, 1 = S-ramp.
UInt16-1RW
34102
Ramp 1 ramp-up time
Acceleration time from 0 to rated motor speed for ramp 1.
UInt32s0.01RW
34202
Ramp 1 ramp-down time
Deceleration time from rated motor speed to 0 for ramp 1.
UInt32s0.01RW
35001
Ramp 2 type
0 = linear, 1 = S-ramp.
UInt16-1RW
35102
Ramp 2 ramp-up time
Acceleration time for ramp 2.
UInt32s0.01RW
35202
Ramp 2 ramp-down time
Deceleration time for ramp 2.
UInt32s0.01RW
38002
Jog ramp time
Ramp time used by the Jog function.
UInt32s0.01RW
38102
Quick-stop ramp time
Deceleration time used by the Quick Stop function.
UInt32s0.01RW
41001
Motor speed direction
0 = clockwise, 1 = counter-clockwise, 2 = both directions.
UInt16-1RW
41201
Motor speed low limit
Lowest allowed output frequency.
UInt16Hz0.1RW
41401
Motor speed high limit
Highest allowed output frequency.
UInt16Hz0.1RW
41601
Torque limit motor mode
Maximum torque in motor mode, in percent of rated torque.
UInt16%1RW
41701
Torque limit generator mode
Maximum torque in generator mode, in percent of rated torque.
UInt16%1RW
44001
Warning frequency low
Low limit of the frequency warning range.
UInt16Hz0.1RW
44101
Warning frequency high
High limit of the frequency warning range.
UInt16Hz0.1RW
45002
Warning current low
Low limit of the current warning range.
UInt32A0.01RW
45102
Warning current high
High limit of the current warning range.
UInt32A0.01RW
45402
Warning reference low
Low limit of the reference warning range.
Int32-0.001RW
45502
Warning reference high
High limit of the reference warning range.
Int32-0.001RW
45602
Warning feedback low
Low limit of the feedback warning range.
Int32-0.001RW
45702
Warning feedback high
High limit of the feedback warning range.
Int32-0.001RW
45801
Missing motor phase function
0 = off, 1 = on: trips when an output phase is missing.
UInt16-1RW
46101
Bypass speed from
Start of the frequency band the drive avoids (compressor/fan resonance).
UInt16Hz0.1RW
46301
Bypass speed to
End of the frequency band the drive avoids.
UInt16Hz0.1RW
51001
Terminal 18 digital input
Function of digital input terminal 18; factory default 8 = start.
UInt16-1RW
51101
Terminal 19 digital input
Function of digital input terminal 19; factory default 10 = reversing.
UInt16-1RW
51201
Terminal 27 digital input
Function of digital input terminal 27; factory default 1 = reset.
UInt16-1RW
51301
Terminal 29 digital input
Function of digital input terminal 29; factory default 14 = jog.
UInt16-1RW
51501
Terminal 33 digital input
Function of digital input terminal 33; factory default 16 = preset reference.
UInt16-1RW
54001
Function relay
Function of relay output 01/02.
UInt16-1RW
54101
On delay, relay
Delay before the relay output switches on.
UInt16s0.01RW
54201
Off delay, relay
Delay before the relay output switches off.
UInt16s0.01RW
61001
Terminal 53 low voltage
Low voltage value of the analog input on terminal 53.
UInt16V0.01RW
61101
Terminal 53 high voltage
High voltage value of the analog input on terminal 53.
UInt16V0.01RW
61201
Terminal 53 low current
Low current value of the analog input on terminal 53.
UInt16mA0.01RW
61301
Terminal 53 high current
High current value of the analog input on terminal 53.
UInt16mA0.01RW
61402
Terminal 53 low reference/feedback value
Reference value that corresponds to the terminal 53 low voltage/current.
Int32-0.001RW
61502
Terminal 53 high reference/feedback value
Reference value that corresponds to the terminal 53 high voltage/current.
Int32-0.001RW
61901
Terminal 53 mode
0 = voltage mode, 1 = current mode.
UInt16-1RW
62201
Terminal 60 low current
Low current value of the analog input on terminal 60.
UInt16mA0.01RW
62301
Terminal 60 high current
High current value of the analog input on terminal 60.
UInt16mA0.01RW
62402
Terminal 60 low reference/feedback value
Reference value that corresponds to the terminal 60 low current.
Int32-0.001RW
62502
Terminal 60 high reference/feedback value
Reference value that corresponds to the terminal 60 high current.
Int32-0.001RW
69001
Terminal 42 mode
0 = 0-20 mA, 1 = 4-20 mA.
UInt16-1RW
69101
Terminal 42 analog output
Signal to be shown on analog output terminal 42.
UInt16-1RW
69301
Terminal 42 output min scale
Minimum output value of terminal 42 in percent of the selected signal range.
UInt16%0.01RW
69401
Terminal 42 output max scale
Maximum output value of terminal 42 in percent of the selected signal range.
UInt16%0.01RW
80101
Control site
0 = digital and control word, 1 = digital only, 2 = control word only.
UInt16-1RW
80201
Control word source
0 = none, 1 = FC RS485.
UInt16-1RW
80301
Control word timeout time
Time before the control-word timeout function (8-04) acts.
UInt16s0.1RW
80401
Control word timeout function
0 = off, 1 = freeze output, 2 = stop, 3 = jogging, 4 = max speed, 5 = stop and trip.
UInt16-1RW
83001
Protocol
0 = FC, 2 = Modbus RTU. Factory default 0 (FC), so Modbus must be selected before the gateway can talk to the drive.
UInt16-1RW
83101
Address
Bus address, 1-247 for Modbus. Factory default 1, which is the unit ID this seed uses.
UInt16-1RW
83201
FC port baud rate
0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200, 4 = 38400 baud. Factory default 9600 for the FC protocol and 19200 when Modbus RTU is selected.
UInt16-1RW
83301
FC port parity / stop bits
0 = even parity, 1 stop bit (factory default); 1 = odd parity, 1 stop bit; 2 = no parity, 1 stop bit; 3 = no parity, 2 stop bits.
UInt16-1RW
83501
Minimum response delay
Minimum delay between request and response.
UInt16s0.001RW
83601
Maximum response delay
Maximum allowed delay between request and response; exceeding it causes a control-word timeout.
UInt16s0.001RW
89401
Bus feedback 1
Feedback value written over the bus.
Int16-1RW
160001
Control word (readout)
Latest valid control word received over the serial port.
UInt16-1R
160102
Reference [unit] (readout)
Total remote reference (sum of pulse, analog, preset, LCP, local bus and freeze reference).
Int32-0.001R
160201
Reference [%] (readout)
Total remote reference in percent.
Int16%0.1R
160301
Status word (readout)
Status word sent to the bus master.
UInt16-1R
160501
Main actual value [%] (readout)
Main actual value sent with the status word.
Int16%0.01R
160902
Custom readout
Customised readout from parameters 0-31/0-32.
Int32%0.01R
161001
Power [kW]
Output power in kW.
UInt16kW0.001R
161101
Power [hp]
Output power in hp.
UInt16hp0.001R
161201
Motor voltage
Motor phase voltage.
UInt16V1R
161301
Frequency
Output frequency.
UInt16Hz0.1R
161401
Motor current
Motor phase current.
UInt16A0.01R
161501
Frequency [%]
Output frequency as a percentage of 4-14 Motor Speed High Limit.
UInt16%0.1R
161801
Motor thermal
Calculated thermal motor load.
UInt16%1R
163001
DC-link voltage
DC-link voltage.
UInt16V1R
163401
Heat sink temperature
Heat sink temperature.
UInt16°C1R
163501
Inverter thermal
Calculated thermal load on the inverter.
UInt16%1R
163601
Inverter nominal current
Continuous nominal inverter current.
UInt16A0.01R
163701
Inverter maximum current
Intermittent maximum inverter current (150 %).
UInt16A0.01R
163801
SL controller state
Number of the active smart-logic state.
UInt16-1R
165001
External reference
Sum of all external references in percent.
Int16%0.1R
165101
Pulse reference
Pulse input converted to a reference in percent.
Int16%0.1R
165202
Feedback [unit]
Feedback value in the reference unit.
Int32-0.001R
166001
Digital input 18, 19, 27, 33
Bit field of the states of digital inputs 18, 19, 27 and 33.
UInt16-1R
166101
Digital input 29
State of digital input 29.
UInt16-1R
166201
Analog input 53 (V)
Analog input 53 in voltage mode.
UInt16V0.01R
166301
Analog input 53 (mA)
Analog input 53 in current mode.
UInt16mA0.01R
166401
Analog input 60
Analog input 60.
UInt16mA0.01R
166501
Analog output 42
Analog output 42.
UInt16mA0.01R
167101
Relay output [bin]
Bit field of the relay outputs.
UInt16-1R
168601
FC port REF 1
Latest reference received over the FC port.
Int16-1R
169002
Alarm word
Bit field of active alarms.
UInt32-1R
169202
Warning word
Bit field of active warnings.
UInt32-1R
169402
Extended status word
Extended status word.
UInt32-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

RS-485 device: reach it through a Modbus RTU-to-TCP gateway. The drive ships with the Danfoss FC protocol selected (8-30 = 0), so Modbus RTU (8-30 = 2) must be selected once. For Modbus the documented defaults are 8-32 = 19200 baud, 8-33 = even parity with 1 stop bit and 8-31 = address 1 - the 19200 8E1 block and unit ID this seed uses. Sources: Danfoss "VLT Micro Drive FC 51 Modbus RTU Operating Instruction" MG92B102 (https://files.danfoss.com/download/Drives/MG92B102.pdf), sections 4.1.12 (register addresses), 4.1.13 (parameter number x 10 = holding register; example 3-41 = register 3410), 5.1 and 5.2; names, types and conversion indices from the "VLT Micro Drive FC 51 Programming Guide" MG02C702 (https://files.danfoss.com/download/Drives/MG02C702.pdf), ch. 5.2 (-1 = 0.1, -2 = 0.01, -3 = 0.001). Addressing: the rows store the printed holding register numbers and the device is one_based, because 4.1.13 also states that register 3410 is addressed as 2809 (D51 hex) = 3409 in the data address field of the message. The four fixed FC-profile registers (50000 control word, 50010 reference, 50200 status word, 50210 main actual value) are a separate "Modbus Register Number" area with no worked frame: they are stored as printed, and a client must not apply the one_based offset to them. Their scale follows 3-00/1-00, so 50010/50210 carry no fixed factor. 32-bit parameters occupy two registers, high word first (HighFirst). Deliberate omissions: the coil map (16 control-word bits, 16 reference bits, status word, main actual value and coil 65 for EEPROM storage) - the operating instruction prints those numbers without saying whether they are zero- or one-based and its only coil example uses a different numbering, so the base cannot be settled; parameter groups 1-**, 2-**, 7-**, 13-**, 14-**, 15-** and 18-**, and the configuration-dependent PCD blocks 2810-2873 / 2910-2973.