ECL Comfort 296 / 310 (ECL 210 via RS-485) Modbus register map

Download JSONSupplier documentationSuggest an edit

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
351
ECL software version
Two bytes: major.minor (257 = 0x0101 = version 1.01).
UInt16-1R
381
Modbus network address
Valid range 1-247, factory default 1. A change takes effect immediately.
UInt16-1RW
10241
Sum alarms 17-32
Bit field of alarms 17-32; bit set = alarm active.
UInt16-1R
10251
Sum alarms 1-16
Bit field of alarms 1-16; bit set = alarm active.
UInt16-1R
20611
Application type number
Application key the controller runs (e.g. 230, 266), which determines the sensor assignment.
UInt16-1R
20621
Application type sub number
Sub number of the installed application key. The guide reads the application name and version from PNU 2060-2063: 2060 = prefix (an ASCII letter, e.g. 65 = 'A'), 2061 = type number, 2062 = sub number, 2063 = version (major.minor in the two bytes).
UInt16-1R
20991
Production week and year
High byte = years since 2000, low byte = production week.
UInt16-1R
42011
Circuit 1 mode
Operating mode of circuit 1: 0 = manual operation, 1 = scheduled operation, 2 = constant comfort temperature, 3 = constant setback temperature, 4 = frost protection/standby, 5 = active cooling (A232 only). The guide places the circuit modes on PNU 4201-4206 (circuit 1-6) and states that manual mode applies to all circuits; it does not list a separate controller-wide mode PNU.
UInt16-1RW
42021
Circuit 2 mode
Operating mode of circuit 2, same codes as circuit 1; circuit 3 mode is 4203, circuit 4 mode 4204, and so on up to circuit 6 at 4206.
UInt16-1RW
42111
Circuit 1 status
Operating status of circuit 1: 0 = setback, 2 = pre-comfort, 3 = comfort, 5 = pre-setback, 6 and above = holiday states (see the guide's 'Mode and status' table). The operating status is read as 0 (setback) when the mode code is larger than 3.
UInt16-1R
42121
Circuit 2 status
Operating status of circuit 2, same codes as circuit 1; circuit 3 status is 4213, circuit 4 status 4214, and so on.
UInt16-1R
102011
Raw sensor 1
Uncorrected input value of hardware sensor input 1, before any application scaling.
Int16°C0.01R
102021
Raw sensor 2
Int16°C0.01R
102031
Raw sensor 3
Int16°C0.01R
102041
Raw sensor 4
Int16°C0.01R
103991
SCADA timeout
Minutes after which the SCADA overwrites below expire and the controller returns to its own values; 1-720.
UInt16min1RW
104001
SCADA outdoor temperature
Outdoor temperature injected by SCADA; -60 to 60 °C. Must be written periodically, otherwise it expires after the SCADA timeout.
Int16°C0.01RW
104011
SCADA heat offset 1
Parallel shift of heating circuit 1, -50 to 50 K; circuits 2-4 use 10402-10404. Must be written periodically.
Int16K0.1RW
104051
SCADA boiler control 1
DHW tank charging request: 0 = off, 1 = stop, 2 = start. Circuits 2-4 use 10406-10408.
UInt16-1RW
111751
Circuit 1 heat curve slope
Weather-compensation slope (heat curve); read-only per the guide, writable in some applications
Int16-0.1R
111801
Circuit 1 comfort room setpoint
Int16°C0.1RW
111811
Circuit 1 saving room setpoint
Int16°C0.1RW
111901
Comfort DHW setpoint
Int16°C0.1RW
111911
Saving DHW setpoint
Int16°C0.1RW
112011
Circuit 1, sensor S1
Measured value of the sensor the application assigns to S1 of circuit 1 (typically the flow temperature). Which physical sensor that is depends on the application key.
Int16°C0.01R
112021
Circuit 1, sensor S2
Int16°C0.01R
112031
Circuit 1, sensor S3
Int16°C0.01R
112041
Circuit 1, sensor S4
Int16°C0.01R
112051
Circuit 1, sensor S5
Int16°C0.01R
112061
Circuit 1, sensor S6
Int16°C0.01R
112071
Circuit 1, sensor S7
Int16°C0.01R
112081
Circuit 1, sensor S8
Int16°C0.01R
112091
Circuit 1, sensor S9
Int16°C0.01R
112101
Circuit 1, sensor S10
Int16°C0.01R
112511
Circuit 1, S1 sensor reference
Desired value / setpoint used for sensor S1 of circuit 1.
Int16°C0.01R
112521
Circuit 1, S2 sensor reference
Int16°C0.01R
112531
Circuit 1, S3 sensor reference
Int16°C0.01R
112541
Circuit 1, S4 sensor reference
Int16°C0.01R

Notes

Source: Danfoss Climate Solutions, "ECL Comfort 210/296/310, communication description" (operating guide AQ074886472234, English, 2026.05 edition). The ECL Comfort 296 and 310 are Modbus servers on TCP port 502 with default address 1 (range 1-247, settable in PNU 38); only public function codes 03 (read holding), 04 (read input) and 06 (write single) are supported, and the guide's own examples read both a setpoint and a sensor with function code 03, so the complete map is listed as holding registers, the ADU is limited to 240 bytes and a request may span at most 123 parameters. The register address is the PNU minus one (the guide's example: PNU 11180 is at address 11179), so the PNU numbers from the parameter list are used one_based here. Every value is a signed or unsigned 16-bit integer; the guide's Scale column is applied above (100 = 0.01, 10 = 0.1). The controller model is defined by the application key installed (PNU 2060-2063 report prefix, type number, sub number and version), and the application decides which sensor S1-S10 is what, which PNUs exist and whether a heat curve is present, so the sensor rows are intentionally described by their application-level names. PNU ranges: circuit modes 4201-4206 and circuit statuses 4211-4216 (circuit 1 = 4201/4211, as the guide's 'Mode and status' section states); the guide lists no controller-wide mode or status PNU, so none is included. Circuit 1 parameters are 11xxx, circuit 2 (DHW) 12xxx, and 1000 is added per further circuit. The circuit 1 heat curve slope (PNU 11175) uses the guide's scale 10 (= 1.0) and is listed as read-only, because the guide marks it read-only while some applications allow writing it. Reading non-existing parameters returns a Modbus exception instead of a value.