BITZER · Refrigeration controller

CM-RC-01 compressor control module (IQ module) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
48
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
1001
Capacity setpoint
Active capacity setpoint. Transmitted with scale 100 (12.3 % = 123).
Int16%0.01R
1011
Actual capacity
Average capacity delivered. Transmitted with scale 100.
Int16%0.01R
1021
Control word
Active control word.
UInt16-1R
1031
Status word
Operation status word.
UInt16-1R
111001
Number of active alarms
Number of active alarms.
UInt16-1R
111011
Number of uncleared listed alarms
Number of listed alarms that have not yet been cleared.
UInt16-1R
111021
Highest alarm state
0 = Clear, 1 = Inactive, 2 = Active, 3 = Set.
UInt16-1R
111031
Highest alarm severity
0 = None, 1 = Log, 2 = Event, 4 = Info, 8 = Warning, 16 = Critical, 32 = Fault.
UInt16-1R
111041
Waiting for external reset
0 = No, 1 = Yes. Set when the module is locked and waiting for an external reset command or restart.
UInt16-1R
111051
Required alarm reset level
0 = NA, 1 = Auto, 2 = Timer, 3 = Extern, 4 = Restart.
UInt16-1R
112011
Highest ranked alarm code
Code of the highest ranked active alarm.
UInt16-1R
112021
Second highest ranked alarm code
Code of the second highest ranked active alarm.
UInt16-1R
120011
Suction pressure
Suction pressure. Transmitted with scale 100.
Int16bar(a)0.01R
120021
Discharge pressure
Discharge pressure. Transmitted with scale 100.
Int16bar(a)0.01R
120031
Evaporating temperature (SST)
Calculated saturated suction temperature. Transmitted with scale 10.
Int16°C0.1R
120041
Condensing temperature (SDT)
Calculated saturated discharge temperature. Transmitted with scale 10.
Int16°C0.1R
120051
Envelope status
0 = Stopped, 1 = Starting, 2 = Running, 3 = Stopping, 4 = Warning - inside envelope, 5 = Critical - outside envelope, 6 = Fault.
UInt16-1R
120061
Envelope zone
0 = Inside, 1 = SST Low / SDT Low, 2 = SST Low, 3 = SST Low / SDT High, 4 = SDT High, 5 = SST High / SDT High, 6 = SST High, 7 = SST High / SDT Low, 8 = SDT Low.
UInt16-1R
120101
Discharge temperature
Discharge gas temperature. Transmitted with scale 10.
Int16°C0.1R
120111
AUX temperature
Auxiliary temperature input. Transmitted with scale 10.
Int16°C0.1R
120221
High pressure switch
0 = Off, 1 = On.
UInt16-1R
120231
Crankcase oil heater
0 = Off, 1 = On.
UInt16-1R
120251
Oil sensor 1
0 = Off, 1 = On.
UInt16-1R
120261
Oil sensor 2
0 = Off, 1 = On.
UInt16-1R
120271
Motor start requested
0 = Off, 1 = On.
UInt16-1R
120281
Head cooling fan
0 = Off, 1 = On.
UInt16-1R
120291
Liquid injection cooling valve
0 = Off, 1 = On.
UInt16-1R
120301
Compressor start unloading valve
0 = Off, 1 = On.
UInt16-1R
120311
Capacity control valve CR-1
0 = Off, 1 = On.
UInt16-1R
120321
Capacity control valve CR-2
0 = Off, 1 = On.
UInt16-1R
120331
Capacity control valve CR-3
0 = Off, 1 = On.
UInt16-1R
130011
Motor overheat thermistor resistance
PTC thermistor resistance of the motor overheat protection.
UInt16Ohm1R
130021
Estimated motor power consumption
Estimated motor power. Transmitted with scale 10.
UInt16kW0.1R
130031
Motor drive frequency
Motor drive frequency (speed). Transmitted with scale 10.
UInt16Hz0.1R
130061
Motor start contactor 1
0 = Off, 1 = On.
UInt16-1R
130071
Motor start contactor 2
0 = Off, 1 = On.
UInt16-1R
140001
System operating state
0 = CONFIG, 1 = INPUT, 2 = STARTUP, 3 = READY, 4 = SUSPEND, 5 = SERVICE, 6 = PRODUCTION.
UInt16-1R
151501
Control output current
Control output current. Transmitted with scale 100.
Int16A0.01R
159901
Operation LED state
0 = OFF, 1 = ON, 2 = SLOW_SHORT, 3 = SLOW_MED, 4 = SLOW_LONG, 5 = FAST_SHORT, 6 = FAST_MED, 7 = FAST_LONG.
UInt16-1R
159911
Warning LED state
0 = OFF, 1 = ON, 2 = SLOW_SHORT, 3 = SLOW_MED, 4 = SLOW_LONG, 5 = FAST_SHORT, 6 = FAST_MED, 7 = FAST_LONG.
UInt16-1R
159921
Fault LED state
0 = OFF, 1 = ON, 2 = SLOW_SHORT, 3 = SLOW_MED, 4 = SLOW_LONG, 5 = FAST_SHORT, 6 = FAST_MED, 7 = FAST_LONG.
UInt16-1R
159931
Communication LED state
0 = OFF, 1 = ON, 2 = SLOW_SHORT, 3 = SLOW_MED, 4 = SLOW_LONG, 5 = FAST_SHORT, 6 = FAST_MED, 7 = FAST_LONG.
UInt16-1R
203001
Serial control source
0 = None, 1 = COM1 (Modbus).
UInt16-1R
203011
Serial control timeout function
0 = None, 1 = Stop, 2 = Fault.
UInt16-1R
203021
Serial control timeout time
Serial control timeout time, default 60 s.
UInt16s1R
221001
Refrigerant selection
0 = NONE, 1 = R134a, 2 = R404A, 3 = R507A, 4 = R407C, 5 = R22, 6 = R407A, 7 = R407F, 9 = R448A, 10 = R449A, 11 = R450A, 12 = R513A, 13 = R1234yf, 14 = R1234ze.
UInt16-1R
223001
Mains supply voltage specification
Mains supply voltage specification (single phase).
UInt16V1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: BITZER "Reference guide - Compressor Control Module CM-RC-01", document version 3.0, sections 10.2 and 10.3 (http://cis.bitzer.ru/files/File/IQ-Products/CM-RC-01.pdf, BITZER's own Russian documentation server). The guide states that the numbers in section 10.3 are Modbus register numbers, not indexes, so they are one-based register numbers and the PDU address is one less; every input register can also be read as a holding register. Factory serial settings from section 10.2.1: address 48, 19200 bps, 8 data bits, even parity, 1 stop bit. Scale 100 / scale 10 values are transmitted as 100x / 10x the engineering value, hence scale factors 0.01 / 0.1. The module is reached over RS-485 through a Modbus RTU-to-TCP gateway. Only 16-bit points are listed: the file leaves out the 32-bit counter pairs (device and compressor operating hours, start count) because their word order is not stated unambiguously in the extracted table. COM1 configuration registers are listed read/write because the module allows changing them over Modbus, although the factory values above are the ones to start from.