VAV-Compact volumetric flow controller (..MV-D3-MOD, ..HV24A-MOD) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
Low word first
Baud rate
38400
Parity
None
Data bits
8
Stop bits
2

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
01
Setpoint
Setpoint related to the position or to the volumetric flow, scaled between Vmin (register 105) and Vmax (register 106). Range 0...10000. Default 0.
UInt16%0.01RW
11
Override control
0 = none (default), 1 = open, 2 = close, 3 = min, 4 = mid, 5 = max, 6 = fast open, 7 = fast close. Fast open / fast close cycles increase mechanical load.
UInt16-1RW
21
Command
0 = none (default), 1 = adaption, 2 = test, 3 = sync, 4 = reset. After the command is sent the register returns to none; reset clears the malfunction and service information in register 104.
UInt16-1RW
31
Actuator type
0 = actuator not connected, 1 = air / water, 2 = VAV / EPIV, 3 = fire, 4 = energy valve, 5 = 6-way EPIV.
UInt16-1R
41
Relative position
Range 0...10000.
UInt16%0.01R
51
Absolute position
Degrees for actuators with rotary movement, millimetres for actuators with linear movement (the unit depends on the device).
UInt16°1R
61
Relative volumetric flow
Relative volumetric flow of Vnom. Range 0...10000.
UInt16%0.01R
71
Absolute volumetric flow
Range 0...Vnom.
UInt16m3/h1R
81
Sensor 1 value
Millivolts if sensor type 1 (register 107) is active, 0 / 1 if sensor type 1 is a switch. Range 0...65535.
UInt16mV1R
102
Absolute volumetric flow in the selected unit
32-bit value in the unit chosen by register 117, low word first (the document's own example: address x = low word, x+1 = high word, value = high * 65536 + low).
UInt32UnitSel0.001R
121
Analog setpoint
Setpoint in percent when the actuator is controlled by the analog signal.
UInt16%0.01R
991
Bus termination
0 = inactive (default), 1 = active: the 120 ohm bus termination is enabled.
UInt16-1R
1001
Series number, 1st part
Parts 1, 2 and 4 of the four-part series number are readable; the example 00839-31324-064-008 is read as 00839 / 31324 / 008.
UInt16-1R
1011
Series number, 2nd part
UInt16-1R
1021
Series number, 4th part
UInt16-1R
1031
Firmware version
Communication module firmware, e.g. 302 for version 3.02.
UInt16-1R
1041
Malfunction and service information
Bit-coded. Bit 1 mechanical travel increased, bit 2 actuator cannot move, bit 8 internal activity, bit 9 gear train disengaged (manual override pressed), bit 10 bus watchdog triggered.
Binary-1R
1051
Vmin
Lower flow limit, range 0...Vmax. Default 0.
UInt16%0.01RW
1061
Vmax
Upper flow limit, range Vmin...10000 and greater than 20 percent. Default 10000.
UInt16%0.01RW
1071
Sensor 1 type
0 = none (default), 1 = active / hybrid, 4 = switch. Restart the actuator after a change for correct sensor values.
UInt16-1RW
1081
Bus fail position
0 = none / last setpoint (default), 1 = fast close, 2 = fast open, 3 = mid position. Becomes active when the bus watchdog (register 109) expires.
UInt16-1RW
1091
Timeout for bus watchdog
0 = deactivated (default), range 0...3600 s. When a bus fail position is configured the document states a default of 120 s.
UInt16s1RW
1101
Nominal volumetric flow
UInt16m3/h1R
1122
Nominal volumetric flow in the selected unit
Vnom in the unit chosen by register 117, low word first.
UInt32UnitSel0.001R
1161
Control mode
0 = position control, 1 = flow control.
UInt16-1RW
1171
Unit selection flow
0 = m3/s, 1 = m3/h (default), 2 = l/s, 3 = l/min, 4 = l/h, 5 = gpm, 6 = cfm.
UInt16-1RW
1181
Setpoint source
0 = analog signal on wire 3, 1 = bus (default, setpoint from register 0).
UInt16-1RW

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: Belimo 'Modbus Interface Description - VAV-Compact, Volumetric flow compact control device', edition 2026-01 / V3.08, manufacturer date 01.12.2023 (belimo_Modbus-Register_VAV_V3_8_en-gb.pdf), read from Belimo's own regional mirror https://www.belimo.ro/mam/general-documents/system_integration/Modbus/belimo_Modbus-Register_VAV_V3_8_en-gb.pdf because www.belimo.com answers automated requests with HTTP 403; same MAM document and edition, the URL above is the canonical location. Applicable actuator types: ..MV-D3-MOD and ..HV24A-MOD. Factory Modbus settings from the document's 'Modbus RTU' block: 38400 Bd, transmission format 1-8-N-2 (8 data bits, no parity, 2 stop bits), address 1; 9600/19200/76800/115200 Bd and 1-8-N-1 / 1-8-E-1 / 1-8-O-1 are selectable, as are addresses 1...247. Addressing: the document prints both numberings - 'All data is arranged in a table and addressed by 1..n (Register No.) or 0..n-1 (Address)' - and every row carries both columns; the values stored here are the Address column (Register No. minus 1), hence zero_based. Word order: 32-bit values are 'little endian byte swap / LSW (Least Significant Word) first', so the low word sits at the lower Register No. and the two 32-bit rows (10 and 112) are read LowFirst; the document's worked example gives high word 19 at Register No. x+1 and low word 14551 at x, value = 19 * 65536 + 14551. Every value is an unsigned 16-bit integer and the document makes no distinction between data types, so all rows live in holding registers and FC 3/6/16 reach everything (FC 2/4 are alternatives). Left out: registers 9, 11, 111, 114 and 115, printed as '–' (reserved or the second half of a 32-bit pair); register 12 is entered read-only because its description table says R while the overview column shows 'R / W'. Scales are the document's plain multipliers (0.01 percent, 0.001 for the unit-selected 32-bit flows).