ATMOS 41 Gen 2 (Modbus RTU enabled) Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
1-based
Byte order
Big endian
Word order
High word first
Baud rate
9600
Parity
Even
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
30012
Solar radiation
Average solar radiation since the last measurement. Register number 3001 in the vendor table; the PDU address is 3000 (see notes on addressing).
Float32W/m21R
30032
Total precipitation
Total combined rainfall from the dual rain gauges since the last measurement.
Float32mm1R
30052
Precipitation drop counter
Total rain drops detected by the drop counter since the last measurement (count, 0-65535).
Float32-1R
30072
Precipitation tip counter
Total precipitation tipping-spoon tips since the last measurement (count, 0-65535).
Float32-1R
30092
Precipitation electrical conductivity
Average precipitation basin bulk EC since the last measurement. Reads 0 if no tipping-spoon tips were detected since the last measurement.
Float32µS/cm1R
30112
Lightning strike count
Total lightning strikes since the last measurement (count, 0-65535).
Float32-1R
30132
Average lightning strike distance
Average strike distance from the sensor since the last measurement; 0 when no strikes were detected.
Float32km1R
30152
Wind speed
Average wind speed magnitude since the last measurement (0.00-60.00 m/s).
Float32m/s1R
30172
Wind direction
Average wind heading clockwise from north (0.0-359.9 deg) since the last measurement.
Float32°1R
30192
Gust wind speed
Maximum wind speed magnitude seen since the last measurement (0.00-60.00 m/s).
Float32m/s1R
30212
Air temperature
Average air temperature since the last measurement (-65.0 to 60.0 °C).
Float32°C1R
30232
Vapor pressure
Average vapor pressure since the last measurement (1.00-47.00 kPa).
Float32kPa1R
30252
Atmospheric pressure
Average atmospheric pressure since the last measurement (1.00-120.00 kPa).
Float32kPa1R
30272
Relative humidity
Average relative humidity since the last measurement as a fraction: 0.000-1.000, i.e. multiply by 100 for %. The vendor table gives the unit as '% / 100'.
Float32-1R
30292
Humidity sensor temperature
Average temperature of the relative-humidity sensor since the last measurement (-40.0 to 85.0 °C).
Float32°C1R
30312
Single-value orientation
Average sensor polar orientation since the last measurement (0.0-180.0 deg).
Float32°1R
30332
Minimum air temperature
Lowest air temperature seen since the last measurement (-65.0 to 60.0 °C).
Float32°C1R
30352
Maximum air temperature
Highest air temperature seen since the last measurement (-65.0 to 60.0 °C).
Float32°C1R
30372
North wind speed
Average wind speed from a northerly direction since the last measurement (-60.00 to 60.00 m/s).
Float32m/s1R
30392
East wind speed
Average wind speed from an easterly direction since the last measurement (-60.00 to 60.00 m/s).
Float32m/s1R
30412
X-direction orientation
Average sensor orientation in the X direction since the last measurement (-90.0 to 90.0 deg).
Float32°1R
30432
Y-direction orientation
Average sensor orientation in the Y direction since the last measurement (-90.0 to 90.0 deg).
Float32°1R
34011
Sensor type
Sensor type number; 88 for the ATMOS 41 Gen 2.
UInt16-1R
34022
Sensor numeric serial number
Numeric part of the serial number, i.e. the XXXXXXX in A41G2MXXXXXXX.
UInt32-1R
34041
Sensor firmware version
METER digital-sensor firmware version; divide by 100 for the version number (e.g. 608 = 6.08).
UInt16-1R
34051
Sensor build version
Firmware build/patch version. Appended to the firmware version it forms the full version (e.g. 16 appended to 6.08 is 6.08.16).
UInt16-1R
34061
Sensor hardware revision
Hardware revision number, indicating hardware version and capabilities.
UInt16-1R
34197
Sensor ASCII serial number
Full serial number as a 13-character ASCII string plus one null terminator (A41G2MXXXXXXX), packed into 7 registers.
Ascii-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Source: METER Group 'ATMOS 41 Gen 2 Integrator Guide', document 18036-03, edition 01.2025 — sensor description, Table 20 (Modbus communication configuration), section 'Data representation and registers', Table 23 (holding registers), Table 24 (input register measurement map, register numbers 3001-3044) and Table 25 (identity registers 3401-3425). The guide is the integration document for the Modbus RTU enabled variant of the ATMOS 41 Gen 2 all-in-one weather station (serial numbers A41G2M...); SDI-12-only units (serial A41G2...) do not serve this map. Addressed as printed: the guide states that registers are listed with their 1-based register number and that the address in a Modbus PDU is the register number minus 1, so the printed numbers are stored with addressing = one_based. 32-bit values are big-endian with the most significant word first (Table 22), hence byte_order BigEndian and word_order HighFirst. Factory frame from Table 20 and the text below it: 9600 baud, 8 data bits, even parity, 1 stop bit, server address 1. Note the reader semantics: a read of the measurement input registers resets the sensor's averaging counters/accumulators for all measurements, even the ones not read, which is why the guide recommends a single burst read of the whole 3001-3044 block. Deliberately omitted: the 3407-3418 model string (UTF-16 array, no Ascii encoding of UTF-16 in the app) and registers below 3001/above 3425 (none documented). Not seeded: the SDI-12 register view and the CR6 datalogger example, which are not part of the Modbus map. MIRROR-SOURCED: metergroup.com answers automated requests with HTTP 403, so the 18036-03 copy read here is the distributor mirror https://candh.co.kr/upload/1784693309_6.pdf (vendor document title/edition unchanged; sha256 94d5929806fc30fd4216eb67e2babda0352a873b7083aef7137cd016fb7c641d).