APC by Schneider Electric · PDU

Easy Rack PDU 3P Metered Modbus register map

Default configuration

Protocol
Modbus TCP
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first

Register map

AddressCountNameTypeUnitScaleAccess
01
Version
High byte = firmware version, low byte = hardware version.
UInt16-1R
11
Phase A voltage
UInt16V0.1R
21
Phase A current
UInt16A0.01R
31
Phase A active power
UInt16W1R
41
Phase A reactive power
UInt16var1R
51
Phase A apparent power
UInt16VA1R
61
Phase A power factor
The document prints the unit of this row as '(Thousandths) %'.
UInt16%0.001R
72
Phase A energy
Occupies registers 7 and 8.
UInt32kWh0.001R
91
Phase B voltage
UInt16V0.1R
101
Phase B current
UInt16A0.01R
111
Phase B active power
UInt16W1R
121
Phase B reactive power
UInt16var1R
131
Phase B apparent power
UInt16VA1R
141
Phase B power factor
The document prints the unit of this row as '(Thousandths) %'.
UInt16%0.001R
152
Phase B energy
Occupies registers 15 and 16.
UInt32kWh0.001R
171
Phase C voltage
UInt16V0.1R
181
Phase C current
UInt16A0.01R
191
Phase C active power
UInt16W1R
201
Phase C reactive power
UInt16var1R
211
Phase C apparent power
UInt16VA1R
221
Phase C power factor
The document prints the unit of this row as '(Thousandths) %'.
UInt16%0.001R
232
Phase C energy
Occupies registers 23 and 24.
UInt32kWh0.001R
251
All phases active power
UInt16W1R
261
All phases reactive power
UInt16var1R
271
All phases apparent power
UInt16VA1R
281
All phases power factor
The document prints the unit of this row as '(Thousandths) %'.
UInt16%0.001R
292
All phases energy
Occupies registers 29 and 30.
UInt32kWh0.001R
311
Frequency
The document's unit cell for this row reads '(Thousandths) %'; the scale is thousandths, and hertz is the only reading that makes sense for a PDU frequency.
UInt16Hz0.001R
321
Temperature
UInt16°C0.1R
331
Humidity
UInt16%RH0.1R
341
Phase A voltage alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
351
Phase A current alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
361
Phase B voltage alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
371
Phase B current alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
381
Phase C voltage alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
391
Phase C current alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
401
Temperature alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
411
Humidity alarm status
0 = normal, 1 = higher than the high threshold, 2 = lower than the low threshold.
UInt16-1R
421
Hardware status
0 = error, 1 = normal. Bit 0 = EEPROM status, bit 1 = W25Q status, bit 2 = reserved, bit 3 = network status, bit 4 = temperature/humidity sensor status, bit 5 = metering module status.
Hex-1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

MIRROR-SOURCED. Schneider Electric does not serve this register map from se.com (its FAQ on Modbus support in rack PDUs only says to search the site for 'PDU Modbus'), so this seed is built from the widely mirrored copy of the vendor document 'Modbus Register Map: Easy Rack PDU 3P Metered', Schneider document 990-91441 (two pages), read from Sonepar's document host; SHA-256 06e68e6bd7fe4a36ebfb7be3533a7a1710a8c9bea7a59ae5a5b02cd376962362. The document's own notes govern the decoding: 16-bit values are big-endian, INT32/UINT32 put the most significant word at n+0, reads may use function code 3 or 4, writes function code 16 (or 6 for single registers), and 'Modbus over TCP is supported'. The 'Absolute Starting Register Number (Decimal)' column is the wire address (its own note: 0 equals Modicon register 40001), so the addresses here are zero-based. The document states no TCP port and no unit ID: port 502 and unit ID 1 are placeholders, and the PDU's configured Modbus address must be used instead. The output rows of every phase are metered per phase on this model; outlet-level metering is not part of this map. Reserved rows 0013h-001Ch are not seeded. The frequency and power-factor rows keep the document's scale (thousandths) although its unit cells read '(Thousandths) %' for both. Source: 'Modbus Register Map: Easy Rack PDU 3P Metered', 990-91441. Which units this map applies to: Schneider's FAQ FAQ000279078 lists the APC rack PDUs whose part numbers start with AP88XX, AP89XX, AP78XXB, AP79XXB, APDU99XX, APDU11XXXX, EPDU1XXXX or EPDU2XXXX as Modbus-capable, requires NMC2 firmware 6.x or later or NMC3, and states that NMC1 units and the APDU10XXXX series have no Modbus at all; the same FAQ points readers at the 'PDU Modbus' and 'Easy PDU Modbus' documents in Schneider's download portal instead of serving a link.