Algodue Elettronica · Energy meter

UEM45 / UEM100 / UEMCT / UEMRGW / UEM2L / UEM4L Modbus register map

Default configuration

Protocol
RS485
Port
502
Unit ID
1
Addressing
0-based
Byte order
Big endian
Word order
High word first
Baud rate
19200
Parity
None
Data bits
8
Stop bits
1

This device has an RS-485 interface. Reach it through a Modbus RTU-to-TCP gateway, configured with the factory serial settings above.

Register map

AddressCountNameTypeUnitScaleAccess
40962
Phase 1 to neutral voltage
Float32V1R
40982
Phase 2 to neutral voltage
Float32V1R
41002
Phase 3 to neutral voltage
Float32V1R
41022
Phase 1 to phase 2 voltage
Float32V1R
41042
Phase 2 to phase 3 voltage
Float32V1R
41062
Phase 3 to phase 1 voltage
Float32V1R
41082
Phase to phase voltage average
Float32V1R
41102
Phase 1 current
Float32A1R
41122
Phase 2 current
Float32A1R
41142
Phase 3 current
Float32A1R
41162
Neutral current (calculated)
Float32A1R
41182
Phase currents average
Float32A1R
41202
Phase 1 power factor
Float32-1R
41222
Phase 2 power factor
Float32-1R
41242
Phase 3 power factor
Float32-1R
41262
System power factor
Float32-1R
41282
Phase 1 active power
Float32W1R
41302
Phase 2 active power
Float32W1R
41322
Phase 3 active power
Float32W1R
41342
System active power
Float32W1R
41362
Phase 1 apparent power
Float32VA1R
41382
Phase 2 apparent power
Float32VA1R
41402
Phase 3 apparent power
Float32VA1R
41422
System apparent power
Float32VA1R
41442
Phase 1 reactive power
Float32var1R
41462
Phase 2 reactive power
Float32var1R
41482
Phase 3 reactive power
Float32var1R
41502
System reactive power
Float32var1R
41522
System frequency
Float32Hz1R
41562
Phase to neutral voltage average
Float32V1R
41582
Phase currents sum
Float32A1R
41602
Phase 1 to neutral voltage THD
Float32%1R
41622
Phase 2 to neutral voltage THD
Float32%1R
41642
Phase 3 to neutral voltage THD
Float32%1R
41682
Phase 1 to phase 2 voltage THD
Float32%1R
41702
Phase 2 to phase 3 voltage THD
Float32%1R
41762
Phase 1 current THD
Float32%1R
41782
Phase 2 current THD
Float32%1R
41802
Phase 3 current THD
Float32%1R
41842
Phase 1 voltage-current angle
Float32deg1R
41862
Phase 2 voltage-current angle
Float32deg1R
41882
Phase 3 voltage-current angle
Float32deg1R
41902
Phase voltage-current angles average
Float32deg1R
42442
Phase 1 current demand
Float32A1R
42462
Phase 2 current demand
Float32A1R
42482
Phase 3 current demand
Float32A1R
42502
Neutral current demand
Float32A1R
42562
System active power demand
Float32W1R
42582
System apparent power demand
Float32VA1R
42602
System reactive power demand
Float32var1R
42622
Phase 1 current demand MAX
Float32A1R
42642
Phase 2 current demand MAX
Float32A1R
42662
Phase 3 current demand MAX
Float32A1R
42682
Neutral current demand MAX
Float32A1R
42742
System active power demand MAX
Float32W1R
42762
System apparent power demand MAX
Float32VA1R
42782
System reactive power demand MAX
Float32var1R
43522
Phase 1 imported active energy
Float32Wh1R
43542
Phase 2 imported active energy
Float32Wh1R
43562
Phase 3 imported active energy
Float32Wh1R
43582
System imported active energy
Float32Wh1R
43602
Phase 1 exported active energy
Float32Wh1R
43622
Phase 2 exported active energy
Float32Wh1R
43642
Phase 3 exported active energy
Float32Wh1R
43662
System exported active energy
Float32Wh1R
44322
Phase 1 imported reactive energy
Float32varh1R
44342
Phase 2 imported reactive energy
Float32varh1R
44362
Phase 3 imported reactive energy
Float32varh1R
44382
Phase 1 exported reactive energy
Float32varh1R
44402
Phase 2 exported reactive energy
Float32varh1R
44422
Phase 3 exported reactive energy
Float32varh1R
44442
System imported reactive energy
Float32varh1R
44462
System exported reactive energy
Float32varh1R
44482
System apparent energy
Float32VAh1R
44502
Measure hour counter
The manual's IEEE column gives 0.1h as the unit of this counter.
Float32h0.1R
51202
System imported active energy, partial
Float32Wh1R
51222
System exported active energy, partial
Float32Wh1R
51302
System apparent energy, partial
Float32VAh1R
51362
System imported reactive energy, partial
Float32varh1R
51382
System exported reactive energy, partial
Float32varh1R
51402
System active energy balance (import - export)
Float32Wh1R
51502
System reactive energy balance (import - export)
Float32varh1R

Read this device live with Modbus Connect, free for Windows, macOS and Linux

Related guides

Notes

Sources: Algodue 'MODBUS Communication Protocol for energy meters with integrated RS485 interface - UEM45, UEM100, UEMCT, UEMRGW, UEM2L, UEM4L series', PROTOCOL MANUAL Ed2505, section 6 'READING Registers (Function code $03)' - https://www.algodue.com/wp-content/uploads/2025/10/NEW-UEM_MODBUS-protocol.pdf - and the UEM2L/UEM4L multilingual manual, wiring chapter 'Default value: 19200 bps' - https://www.algodue.com/wp-content/uploads/2026/05/UEM2L_UEM4L_MultilingualManual.pdf . The protocol manual states each meter is 'preset with a default slave address (01)' and fixes the RTU frame as '1 Start, 8 Bit, None, 1 Stop (8N1)'; the installation manual gives the factory speed, 19200 bps. Only the manual's IEEE-754 float bank is used: the parallel integer bank stores power in three 16-bit registers (24-bit values) that the app's register types cannot express. The float addresses are the manual's IEEE column, used as wire addresses, and the manual's worked conversion example (45AACC00h = 5465.5) shows the high word first, hence HighFirst. Float-bank values are already in engineering units (the 0.001 column belongs to the integer bank), so no scale is applied except on the hour counter. Deliberate omissions: the 24-bit integer bank, the minimum/MAX rows (the model columns mark them N/A for most variants), the phase-rotation and serial/model/status words, the channel 2-4 blocks (multi-load meters repeat the same layout at 4000h/6000h/8000h), the tariff counter blocks and every writable setup register.