  "spec_version": 1,
  "slug": "in-situ-aqua-troll-500-600",
  "manufacturer": "In-Situ",
  "model": "Aqua TROLL 500 / 600 multiparameter sonde (Modbus PLC interface)",
  "category": "Water quality sensor",
  "supplier_url": "https://in-situ.com/pub/media/support/documents/Aqua_TROLL_500_Manual.pdf",
  "default_configuration": {
    "protocol": "modbus_rtu",
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst",
    "native_interface": "rs485",
    "serial": {
      "baud_rate": 19200,
      "parity": "Even",
      "data_bits": 8,
      "stop_bits": 1
    }
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 5450,
      "count": 2,
      "name": "Temperature",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 1, holding register number 5451 (address 5450), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). The block tail is listed below as rows 5452-5456 of this seed; the other parameters repeat the same five registers at their own address + 2. Default unit: °C (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5452,
      "count": 1,
      "name": "Data quality ID, temperature block",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Offset +2 of the temperature parameter block (5450). Value 0 means there are no errors or warnings."
    },
    {
      "address": 5453,
      "count": 1,
      "name": "Unit ID, temperature block",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Offset +3 of the parameter block: unit ID of the returned value, marked writable (R/W) in the block table although its Type column prints 'float' for this single-register row (the unit IDs are integers). Appendix C lists the IDs (1 = °C, 2 = °F, 3 = K, 17 = PSI, ... 65 = µS/cm, 145 = pH, 162 = mV, 177 = % saturation, 194 = NTU, 257 = RFU)."
    },
    {
      "address": 5454,
      "count": 1,
      "name": "Parameter ID, temperature block",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Offset +4 of the parameter block: the parameter ID this block belongs to (1 for temperature)."
    },
    {
      "address": 5455,
      "count": 2,
      "name": "Off-line sentinel value, temperature block",
      "data_type": "Float32",
      "units": "°C",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Offset +5 of the parameter block (2 registers): the value returned on error or when the parameter is not available. Marked R/W in the block table, so the sentinel can be written. The default sentinel is 0.0."
    },
    {
      "address": 5457,
      "count": 2,
      "name": "Pressure",
      "data_type": "Float32",
      "units": "psi",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 2, holding register number 5458 (address 5457), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: psi (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5464,
      "count": 2,
      "name": "Depth",
      "data_type": "Float32",
      "units": "ft",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 3, holding register number 5465 (address 5464), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: ft (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5471,
      "count": 2,
      "name": "Level, depth to water",
      "data_type": "Float32",
      "units": "ft",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 4, holding register number 5472 (address 5471), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: ft (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5478,
      "count": 2,
      "name": "Level, surface elevation",
      "data_type": "Float32",
      "units": "ft",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 5, holding register number 5479 (address 5478), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: ft (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5506,
      "count": 2,
      "name": "Actual conductivity",
      "data_type": "Float32",
      "units": "µS/cm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 9, holding register number 5507 (address 5506), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: µS/cm (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5513,
      "count": 2,
      "name": "Specific conductivity",
      "data_type": "Float32",
      "units": "µS/cm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 10, holding register number 5514 (address 5513), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: µS/cm (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5520,
      "count": 2,
      "name": "Resistivity",
      "data_type": "Float32",
      "units": "ohm·cm",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 11, holding register number 5521 (address 5520), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: ohm·cm (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5527,
      "count": 2,
      "name": "Salinity",
      "data_type": "Float32",
      "units": "PSU",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 12, holding register number 5528 (address 5527), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: PSU (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5534,
      "count": 2,
      "name": "Total dissolved solids",
      "data_type": "Float32",
      "units": "ppt",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 13, holding register number 5535 (address 5534), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: ppt (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5541,
      "count": 2,
      "name": "Density of water",
      "data_type": "Float32",
      "units": "g/cm³",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 14, holding register number 5542 (address 5541), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: g/cm³ (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5555,
      "count": 2,
      "name": "Barometric pressure",
      "data_type": "Float32",
      "units": "mmHg",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 16, holding register number 5556 (address 5555), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mmHg (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5562,
      "count": 2,
      "name": "pH",
      "data_type": "Float32",
      "units": "pH",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 17, holding register number 5563 (address 5562), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: pH (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5569,
      "count": 2,
      "name": "pH mV",
      "data_type": "Float32",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 18, holding register number 5570 (address 5569), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mV (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5576,
      "count": 2,
      "name": "ORP",
      "data_type": "Float32",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 19, holding register number 5577 (address 5576), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mV (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5583,
      "count": 2,
      "name": "Dissolved oxygen concentration",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 20, holding register number 5584 (address 5583), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5590,
      "count": 2,
      "name": "Dissolved oxygen, % saturation",
      "data_type": "Float32",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 21, holding register number 5591 (address 5590), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: % (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5611,
      "count": 2,
      "name": "Chloride (Cl-)",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 24, holding register number 5612 (address 5611), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5618,
      "count": 2,
      "name": "Turbidity",
      "data_type": "Float32",
      "units": "NTU",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 25, holding register number 5619 (address 5618), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: NTU (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5653,
      "count": 2,
      "name": "Oxygen partial pressure",
      "data_type": "Float32",
      "units": "torr",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 30, holding register number 5654 (address 5653), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: torr (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5660,
      "count": 2,
      "name": "Total suspended solids",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 31, holding register number 5661 (address 5660), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5667,
      "count": 2,
      "name": "External voltage",
      "data_type": "Float32",
      "units": "V",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 32, holding register number 5668 (address 5667), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: V (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5674,
      "count": 2,
      "name": "Battery capacity (remaining)",
      "data_type": "Float32",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 33, holding register number 5675 (address 5674), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: % (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5681,
      "count": 2,
      "name": "Rhodamine WT concentration",
      "data_type": "Float32",
      "units": "µg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 34, holding register number 5682 (address 5681), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: µg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5688,
      "count": 2,
      "name": "Rhodamine WT fluorescence intensity",
      "data_type": "Float32",
      "units": "RFU",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 35, holding register number 5689 (address 5688), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: RFU (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5695,
      "count": 2,
      "name": "Chloride (Cl-) mV",
      "data_type": "Float32",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 36, holding register number 5696 (address 5695), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mV (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5702,
      "count": 2,
      "name": "Nitrate as nitrogen (NO3 as N) concentration",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 37, holding register number 5703 (address 5702), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5716,
      "count": 2,
      "name": "Ammonium as nitrogen (NH4 as N) concentration",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 39, holding register number 5717 (address 5716), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5723,
      "count": 2,
      "name": "Ammonium (NH4) mV",
      "data_type": "Float32",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 40, holding register number 5724 (address 5723), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). The manual's default-units cell for this row prints mg/L although the parameter is an mV electrode reading; the row keeps mV and records the discrepancy. Default unit: mV (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5730,
      "count": 2,
      "name": "Ammonia as nitrogen (NH3 as N) concentration",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 41, holding register number 5731 (address 5730), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5737,
      "count": 2,
      "name": "Total ammonia as nitrogen (NH3 as N) concentration",
      "data_type": "Float32",
      "units": "mg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 42, holding register number 5738 (address 5737), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5779,
      "count": 2,
      "name": "Eh",
      "data_type": "Float32",
      "units": "mV",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 48, holding register number 5780 (address 5779), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: mV (the unit follows the unit-ID register of the block). The manual's default-units cell prints '162 = mg/L' here, the same abbreviation slip as the Ammonium mV row: unit ID 162 is mV in Appendix C."
    },
    {
      "address": 5786,
      "count": 2,
      "name": "Velocity",
      "data_type": "Float32",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 49, holding register number 5787 (address 5786), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). The default-units cell of the manual prints µg/L for this row, which cannot be a velocity unit (the unit column of that page drifts); no unit is claimed here."
    },
    {
      "address": 5793,
      "count": 2,
      "name": "Chlorophyll-a concentration",
      "data_type": "Float32",
      "units": "µg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 50, holding register number 5794 (address 5793), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: µg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5800,
      "count": 2,
      "name": "Chlorophyll-a fluorescence intensity",
      "data_type": "Float32",
      "units": "RFU",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 51, holding register number 5801 (address 5800), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: RFU (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5821,
      "count": 2,
      "name": "Blue green algae - phycocyanin concentration",
      "data_type": "Float32",
      "units": "µg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 54, holding register number 5822 (address 5821), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: µg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5828,
      "count": 2,
      "name": "Blue green algae - phycocyanin fluorescence intensity",
      "data_type": "Float32",
      "units": "RFU",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 55, holding register number 5829 (address 5828), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: RFU (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5849,
      "count": 2,
      "name": "Blue green algae - phycoerythrin concentration",
      "data_type": "Float32",
      "units": "µg/L",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 58, holding register number 5850 (address 5849), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: µg/L (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 5856,
      "count": 2,
      "name": "Blue green algae - phycoerythrin fluorescence intensity",
      "data_type": "Float32",
      "units": "RFU",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Parameter ID 59, holding register number 5857 (address 5856), 32-bit IEEE-754 float, high word at the lower address. Every parameter starts a 7-register block: value at +0 (2 registers), data-quality ID at +2, unit ID at +3, parameter ID at +4, off-line sentinel value at +5 (2 registers). Default unit: RFU (the unit follows the unit-ID register of the block)."
    },
    {
      "address": 6983,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 1-16",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 1 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6984,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 17-32",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 2 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6985,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 33-48",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 3 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6986,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 49-64",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 4 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6987,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 65-80",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 5 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6988,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 81-96",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 6 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6989,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 97-112",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 7 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6990,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 113-128",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 8 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6991,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 129-144",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 9 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6992,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 145-160",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 10 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6993,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 161-176",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 11 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6994,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 177-192",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 12 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6995,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 193-208",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 13 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    },
    {
      "address": 6996,
      "count": 1,
      "name": "Parameter availability bitmap, bits for parameter IDs 209-219",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Part 14 of the 14-register sensor-discovery block that starts at register number 6984 (address 6983). Reading the block makes the sonde scan its sensor ports and update its parameter map; a set bit means that parameter ID is available."
    }
  ],
  "combined_registers": [],
  "notes": "Source: In-Situ 'Aqua TROLL 500 Operator's Manual', part number 0096400, vendor-hosted PDF at https://in-situ.com/pub/media/support/documents/Aqua_TROLL_500_Manual.pdf (SHA-256 a61485d06e4d496dbd6da50ae14ade1ee8fe5ea254f53b16761a98e5f93b663c), chapter 'Modbus PLC Interface' (pages 35-37) and Appendices A 'Sensor Discovery', B 'Parameter Numbers and Locations' and C 'Unit IDs'; the Aqua TROLL 600 manual carries the same chapter. Setup frame from 'Programming the PLC', with the instrument reset to factory defaults first: Modbus RTU, 1 start bit, 19200 baud, 8 data bits, even parity, 1 stop bit, and the device address set to 1 - the manual prints no factory slave address of its own. Addressing: Appendix B prints a 'Holding Register Number' and a 'Holding Register Address' one lower (5451 / 5450), and the chapter notes that some PLCs use the number and others the address, so the address column is stored as the wire address ('zero_based'). Word order: every measurement is a 32-bit IEEE-754 float with the high word at the lower address (BigEndian + HighFirst). Firmware 1.71 or later is required, and a measurement sequence should begin with the 14-register discovery block at register 6984 so the sonde rescans its ports; it is seeded as rows 6983-6996. An unavailable parameter returns the block's sentinel value instead of an exception. Parameter IDs are fixed, so these addresses hold for any sensor set and the discovery block reports which are populated. Default units apply until the unit-ID register is changed. Three rows whose default-units cell disagrees with the parameter are explained in their own text: Velocity (prints ug/L), Ammonium (NH4) mV (prints mg/L) and Eh (prints '162 = mg/L', where 162 is mV). Appendix B also prints register number 5894 for Chlorophyll-a, while its own address column (5793) and formula (ID 50 -> 5794) agree on 5794, so address 5793 is stored."
}