  "spec_version": 1,
  "slug": "bluetti-ep2000",
  "manufacturer": "BLUETTI",
  "model": "EnergyPro 2000 (EP2000, EBOX)",
  "category": "Home battery",
  "supplier_url": "https://www.bluetti.com/products/ep2000",
  "default_configuration": {
    "protocol": "modbus_tcp",
    "port": 502,
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "LowFirst"
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 50001,
      "count": 1,
      "name": "Number of Inverters",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50002,
      "count": 2,
      "name": "AC Load Power (Total)",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50004,
      "count": 2,
      "name": "PV Power (Total)",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50006,
      "count": 2,
      "name": "Grid Power (Total)",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed 32-bit value, as the sheet's type column is int. The sheet prints no sign convention for the totals row; the vendor repository's issue #12 measures this total as the sum of the three phase magnitudes (17725 W for phases of -6525, -6671 and -4521 W), so import and export cannot be told apart in it. It is the power at the unit's own grid port, not at the meter's grid connection."
    },
    {
      "address": 50008,
      "count": 2,
      "name": "Inverter Power (Total)",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed 32-bit value, as the sheet's type column is int."
    },
    {
      "address": 50010,
      "count": 2,
      "name": "PV to AC Load Power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50012,
      "count": 2,
      "name": "AC Load Energy (Total)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Total energy delivered to the AC loads, 0.1 kWh per count. The vendor repository's issue #12 reports this and the other 50012-50020 totals as always 0 on the EP2000 units measured; the counters are filled over Bluetooth only after a request."
    },
    {
      "address": 50014,
      "count": 2,
      "name": "PV Charging Energy (Total)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Reads 0 on the EP2000 units measured (vendor repository issue #12); see 50012."
    },
    {
      "address": 50016,
      "count": 2,
      "name": "Grid Charging Energy (Total)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Reads 0 on the EP2000 units measured (vendor repository issue #12); see 50012."
    },
    {
      "address": 50018,
      "count": 2,
      "name": "Feed-in Grid Energy",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Reads 0 on the EP2000 units measured (vendor repository issue #12); see 50012."
    },
    {
      "address": 50020,
      "count": 2,
      "name": "PV to AC Load Energy",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Reads 0 on the EP2000 units measured (vendor repository issue #12); see 50012."
    },
    {
      "address": 50022,
      "count": 1,
      "name": "Inverter Operating Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging, 6 = inverter fault, 7 = abnormal off-grid. Values as printed in the vendor sheet."
    },
    {
      "address": 50032,
      "count": 16,
      "name": "Manufacturer information",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50048,
      "count": 2,
      "name": "Grid-port reactive power (sum)",
      "data_type": "Int32",
      "units": "var",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50050,
      "count": 2,
      "name": "Grid-port apparent power (sum)",
      "data_type": "Int32",
      "units": "VA",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50052,
      "count": 2,
      "name": "Battery power",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed 32-bit value. The sheet prints no sign convention for this row."
    },
    {
      "address": 50200,
      "count": 6,
      "name": "Inverter Type",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50214,
      "count": 1,
      "name": "Grid Access Frequency",
      "data_type": "UInt16",
      "units": "Hz",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50215,
      "count": 2,
      "name": "Grid Charging Power (Single)",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50217,
      "count": 2,
      "name": "AC Load Power (Single)",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50219,
      "count": 2,
      "name": "PV Charging Power (Single)",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50221,
      "count": 2,
      "name": "PV to AC Load Power (Single)",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50223,
      "count": 2,
      "name": "Grid Charging Energy (Single)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Per-inverter counter; reads 0 on the EP2000 units measured (vendor repository issue #12)."
    },
    {
      "address": 50225,
      "count": 2,
      "name": "Feed-in Grid Energy (Single)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Per-inverter counter; reads 0 on the EP2000 units measured (vendor repository issue #12)."
    },
    {
      "address": 50227,
      "count": 2,
      "name": "AC Load Energy (Single)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Per-inverter counter; reads 0 on the EP2000 units measured (vendor repository issue #12)."
    },
    {
      "address": 50229,
      "count": 2,
      "name": "PV Charging Energy (Single)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Per-inverter counter; reads 0 on the EP2000 units measured (vendor repository issue #12)."
    },
    {
      "address": 50231,
      "count": 2,
      "name": "PV to AC Load Energy (Single)",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "Per-inverter counter; reads 0 on the EP2000 units measured (vendor repository issue #12)."
    },
    {
      "address": 50234,
      "count": 1,
      "name": "System Phase Number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50236,
      "count": 1,
      "name": "Grid1 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50237,
      "count": 1,
      "name": "Grid1 Current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50239,
      "count": 1,
      "name": "Grid2 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50240,
      "count": 1,
      "name": "Grid2 Current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50242,
      "count": 1,
      "name": "Grid3 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50243,
      "count": 1,
      "name": "Grid3 Current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50244,
      "count": 1,
      "name": "AC System Phase Number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50245,
      "count": 1,
      "name": "AC Load1 Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50246,
      "count": 1,
      "name": "AC Load1 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50247,
      "count": 1,
      "name": "AC Load1 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50248,
      "count": 1,
      "name": "AC Load2 Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50249,
      "count": 1,
      "name": "AC Load2 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50250,
      "count": 1,
      "name": "AC Load2 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50251,
      "count": 1,
      "name": "AC Load3 Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50252,
      "count": 1,
      "name": "AC Load3 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50253,
      "count": 1,
      "name": "AC Load3 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50254,
      "count": 1,
      "name": "Inverter System Phase Number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50255,
      "count": 1,
      "name": "Inverter1 Operation Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging."
    },
    {
      "address": 50256,
      "count": 1,
      "name": "Inverter1 Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50257,
      "count": 1,
      "name": "Inverter1 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50258,
      "count": 1,
      "name": "Inverter1 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50259,
      "count": 1,
      "name": "Inverter2 Operation Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging."
    },
    {
      "address": 50260,
      "count": 1,
      "name": "Inverter2 Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50261,
      "count": 1,
      "name": "Inverter2 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50262,
      "count": 1,
      "name": "Inverter2 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50263,
      "count": 1,
      "name": "Inverter3 Operation Status",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = stop, 1 = off-grid operation, 2 = grid-connected load, 3 = grid-connected operation, 4 = grid-connected charging, 5 = grid-connected discharging."
    },
    {
      "address": 50264,
      "count": 1,
      "name": "Inverter3 Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50265,
      "count": 1,
      "name": "Inverter3 Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50266,
      "count": 1,
      "name": "Inverter3 Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50267,
      "count": 1,
      "name": "PV Total Number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Bit 0-3 = number of DC PV inputs, bit 4-7 = number of AC PV inputs."
    },
    {
      "address": 50268,
      "count": 1,
      "name": "PV1 Type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them"
    },
    {
      "address": 50269,
      "count": 1,
      "name": "PV1 Input Power",
      "data_type": "UInt16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50270,
      "count": 1,
      "name": "PV1 Input Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50271,
      "count": 1,
      "name": "PV1 Input Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 50272,
      "count": 1,
      "name": "PV2 Type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. The EP2000 has two DC MPPT inputs, reported as PV1 and PV2: the slots from PV3 up read junk on measured units, and AC-coupled solar is not reported here at all (vendor repository issues #12 and #145)."
    },
    {
      "address": 50276,
      "count": 1,
      "name": "PV3 Type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. The EP2000 has two DC MPPT inputs, reported as PV1 and PV2: the slots from PV3 up read junk on measured units, and AC-coupled solar is not reported here at all (vendor repository issues #12 and #145)."
    },
    {
      "address": 50280,
      "count": 1,
      "name": "PV4 Type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. The EP2000 has two DC MPPT inputs, reported as PV1 and PV2: the slots from PV3 up read junk on measured units, and AC-coupled solar is not reported here at all (vendor repository issues #12 and #145)."
    },
    {
      "address": 50284,
      "count": 1,
      "name": "PV5 Type",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "0 = reserve, 1 = CAR, 2 = adapter, 3 = other; 100 = DC PV and 101 = AC PV on the models that report them. The EP2000 has two DC MPPT inputs, reported as PV1 and PV2: the slots from PV3 up read junk on measured units, and AC-coupled solar is not reported here at all (vendor repository issues #12 and #145)."
    },
    {
      "address": 50400,
      "count": 2,
      "name": "Hardware version",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "ASCII. Reads empty on every EP2000 measured, like the rest of the 50400-50410 block (vendor repository issue #12)."
    },
    {
      "address": 50402,
      "count": 1,
      "name": "Active power",
      "data_type": "Int16",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Reads 0 on every EP2000 measured, like the rest of its block (vendor repository issue #12)."
    },
    {
      "address": 50403,
      "count": 1,
      "name": "Reactive power",
      "data_type": "Int16",
      "units": "var",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Reads 0 on every EP2000 measured, like the rest of its block (vendor repository issue #12)."
    },
    {
      "address": 51002,
      "count": 1,
      "name": "Total Pack Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51003,
      "count": 1,
      "name": "Total Pack Current",
      "data_type": "UInt16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51009,
      "count": 2,
      "name": "Maximum energy storage capacity (Wh)",
      "data_type": "UInt32",
      "units": "Wh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51011,
      "count": 2,
      "name": "Maximum energy storage capacity (Ah)",
      "data_type": "UInt32",
      "units": "Ah",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51013,
      "count": 1,
      "name": "Rated battery voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51014,
      "count": 2,
      "name": "Maximum charge rate into the storage system",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51016,
      "count": 2,
      "name": "Maximum discharge rate out of the storage system",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51200,
      "count": 6,
      "name": "Pack Type",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51210,
      "count": 1,
      "name": "Total Pack Software Number",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51219,
      "count": 1,
      "name": "Pack Voltage",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51220,
      "count": 1,
      "name": "Pack Current",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R",
      "description": "The sheet types the pack current as unsigned, but two EP2000 systems and a third unit read it signed: 62 while charging (6.2 A) and 65518 while discharging (-1.8 A) at 0.1 A a count (vendor repository issue #12). The community register file still declares it unsigned; the measurement is followed here."
    },
    {
      "address": 51221,
      "count": 1,
      "name": "Pack SOC",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51222,
      "count": 1,
      "name": "Pack SOH",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51223,
      "count": 1,
      "name": "Pack Cycle Count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51224,
      "count": 1,
      "name": "Pack Average Temperature",
      "data_type": "Int16",
      "units": "°C",
      "scale_factor": 1,
      "offset": -40,
      "access": "R",
      "description": "Degrees Celsius plus 40: a measured unit read 58 at the same moment as 18 °C in the app and on a thermal camera, and the sheet's own -40 to 160 range fits that encoding (vendor repository issues #12 and #145). The offset applies the -40."
    },
    {
      "address": 51234,
      "count": 1,
      "name": "Pack Total Cell Count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51235,
      "count": 1,
      "name": "Pack Total NTC Count",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51236,
      "count": 2,
      "name": "Pack Total Charging Energy",
      "data_type": "UInt32",
      "units": "Wh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51238,
      "count": 2,
      "name": "Pack Total Discharging Energy",
      "data_type": "UInt32",
      "units": "Wh",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 51248,
      "count": 1,
      "name": "Pack Estimated Full Charge Time",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Minutes. On measured units this estimate and its discharge counterpart 51249 always read the same value, charging or discharging (vendor repository issue #12)."
    },
    {
      "address": 51249,
      "count": 1,
      "name": "Pack Estimated Full Discharge Time",
      "data_type": "UInt16",
      "units": "min",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Minutes. Reads the same value as 51248 on measured units."
    },
    {
      "address": 53001,
      "count": 6,
      "name": "IoT Model",
      "data_type": "Ascii",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 57001,
      "count": 1,
      "name": "AC load output switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = off, 1 = on."
    },
    {
      "address": 57009,
      "count": 1,
      "name": "AC grid charging switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = off, 1 = on."
    },
    {
      "address": 57010,
      "count": 1,
      "name": "AC grid feed-in switch",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = off, 1 = on."
    },
    {
      "address": 57016,
      "count": 1,
      "name": "Battery empty SOC threshold",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Discharging stops at this state of charge. The sheet prints 0 to 100, in percent, as the valid range."
    },
    {
      "address": 57017,
      "count": 1,
      "name": "Battery full SOC threshold",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Charging stops at this state of charge. The sheet prints 0 to 100, in percent, as the valid range."
    },
    {
      "address": 57030,
      "count": 1,
      "name": "Remote control (EMS control)",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Bits 0-3 are the remote-control enable: 6 = remote control enabled, 4 = remote control disabled so the unit follows its own control; the sheet prints 4 and 6 as the valid values and bits 4-15 as reserved. This is the master switch for the targets below. Writing any of them is untested on hardware: the community profile keeps this whole control block read-only until each register has been written on a unit of its own, and behind the VPP option (which is also what opens port 502 on this model, see notes) an aggregator may overwrite what is set here."
    },
    {
      "address": 57032,
      "count": 2,
      "name": "Active power target, phase A",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed active power target for phase A, in W: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57034,
      "count": 2,
      "name": "Active power target, phase B",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed active power target for phase B, in W: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. This row alone also carries the sheet's further remark \"dark: reserved\", and the whole 57034-57053 block is shaded dark. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57036,
      "count": 2,
      "name": "Active power target, phase C",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed active power target for phase C, in W: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57038,
      "count": 2,
      "name": "Reactive power target, phase A",
      "data_type": "Int32",
      "units": "var",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed reactive power target for phase A, in var: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57040,
      "count": 2,
      "name": "Reactive power target, phase B",
      "data_type": "Int32",
      "units": "var",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed reactive power target for phase B, in var: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57042,
      "count": 2,
      "name": "Reactive power target, phase C",
      "data_type": "Int32",
      "units": "var",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed reactive power target for phase C, in var: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57044,
      "count": 2,
      "name": "Apparent power target, phase A",
      "data_type": "Int32",
      "units": "VA",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed apparent power target for phase A, in VA: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57046,
      "count": 2,
      "name": "Apparent power target, phase B",
      "data_type": "Int32",
      "units": "VA",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed apparent power target for phase B, in VA: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57048,
      "count": 2,
      "name": "Apparent power target, phase C",
      "data_type": "Int32",
      "units": "VA",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Signed apparent power target for phase C, in VA: the sheet's remark for this block reads feed-in to the grid is positive, charging is negative, 0xFFFFFFFF = invalid. The sheet lists this register read/write but prints no value range for it, so the write is left out here and the row is read-only."
    },
    {
      "address": 57050,
      "count": 1,
      "name": "Active power output level (% of rated)",
      "data_type": "Int16",
      "units": "% of Wmax",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Setpoint as a percentage of maximum rated active power, with feed-in positive and charging negative; the sheet prints -100 to 100 as the valid range. Untested on hardware, see 57030."
    }
  ],
  "combined_registers": [],
  "notes": "Register map from BLUETTI's open Modbus TCP list, bluetti-official/bluetti-modbus-tcp-slave at commit cee4c98e: doc/Bluetti-Open-Modbus-TCP-register-list.xlsx (SHA-256 aa7687c5be29c605d03aef1957b5f79ee52000debe564a4d1038d9efce0a1371), sheet \"EBOX\", retrieved 2026-11-23. Its README gives the transport: Modbus TCP slave, address 1 by default, port from the web page (502 in the example). On the EP2000 that page has no such switch: the VPP option in the BLUETTI app opens port 502 (bluetti-community/hassio-bluetti-modbus issue #145, 2026-10-02), and VPP also lets an aggregator charge and discharge the battery. Function 3 at the sheet's addresses; its unit column is the scale. 32-bit values are LITTLE word first: the workbook states \"Register Data principle: Little-end storage; Modbus Protocol transmission principle: Big-end transmission\", and bluetti-community/bluetti-modbus, the HA library, decodes multi-word values with word_order=\"little\" (bluetti-registers#20). Left out, and why: 51001 and 51004-51008, which answer only at unit ID 250 and read 0 at a device's own unit ID (Home Assistant core's bluetti_modbus); the SunSpec rows 50054-50310 without units and the DER status rows 50404-50410, in a block that reads empty on measured units; the 64-bit serials, the version registers, the BMS protect/error/alarm words, the int-or-uint grid power rows, the PV2-PV5 measurement rows (unit column slip; issue #12 measures 1 W / 0.1 V / 0.1 A), and the control rows with no printed valid values (57051-57513). The nine per-phase targets 57032-57048 are listed read/write but print no range, so they are read-only here. Cross-checked against bluetti-community/bluetti-registers at 3f0707a6 (ep2000.json): addresses agree. Seven write registers are seeded with their valid values; none is hardware-tested, the community profile keeping this block read-only. It has been read on three real units (issue #145), whose corrections are in the rows below, but written to by no source found."
}