  "spec_version": 1,
  "slug": "atmoce-mc100",
  "manufacturer": "Atmoce",
  "model": "MC100 / MC100-T balcony storage with MG100 M-gateway",
  "category": "Home battery",
  "supplier_url": "https://www.atmoce.com/en/homeowner",
  "default_configuration": {
    "protocol": "modbus_tcp",
    "port": 502,
    "unit_id": 1,
    "addressing": "zero_based",
    "byte_order": "BigEndian",
    "word_order": "HighFirst"
  },
  "coils": [],
  "discrete_inputs": [],
  "input_registers": [],
  "holding_registers": [
    {
      "address": 60027,
      "count": 2,
      "name": "Maximum AC power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "The system's maximum AC power."
    },
    {
      "address": 60029,
      "count": 2,
      "name": "Rated energy storage power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Rated (nameplate) battery power. The cited source derives its charging ceiling as 75 % of this value."
    },
    {
      "address": 60031,
      "count": 2,
      "name": "Energy storage capacity",
      "data_type": "UInt32",
      "units": "kWh",
      "scale_factor": 0.001,
      "offset": 0,
      "access": "R",
      "description": "Published in Wh; the factor converts to kWh."
    },
    {
      "address": 60069,
      "count": 2,
      "name": "PV power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Photovoltaic output of the system."
    },
    {
      "address": 60071,
      "count": 2,
      "name": "Battery power",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Storage charging/discharging power. The cited source reads it as signed and negates it for its own sign convention, so positive and negative correspond to the two directions, but which direction is positive is not stated by the source."
    },
    {
      "address": 60073,
      "count": 2,
      "name": "Grid active power",
      "data_type": "Int32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "R",
      "description": "Active power at the grid connection point."
    },
    {
      "address": 60089,
      "count": 1,
      "name": "Grid voltage, phase A",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60090,
      "count": 1,
      "name": "Grid current, phase A",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60091,
      "count": 1,
      "name": "Grid voltage, phase B",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60092,
      "count": 1,
      "name": "Grid current, phase B",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60093,
      "count": 1,
      "name": "Grid voltage, phase C",
      "data_type": "UInt16",
      "units": "V",
      "scale_factor": 0.1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60094,
      "count": 1,
      "name": "Grid current, phase C",
      "data_type": "Int16",
      "units": "A",
      "scale_factor": 0.01,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60095,
      "count": 1,
      "name": "State of charge",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "R"
    },
    {
      "address": 60310,
      "count": 1,
      "name": "Forced charging / discharging",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = forced charging, 1 = forced discharging, 2 = exit forced charging/discharging, 99 = pause. On firmware older than 01.01.00.28.15 the source also uses 99 to hold a direction off, because the power-limit registers below are not available there."
    },
    {
      "address": 60311,
      "count": 1,
      "name": "Forced charging / discharging mode",
      "data_type": "UInt16",
      "units": "",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0 = stop at a target state of charge, 1 = run for a charging/discharging duration."
    },
    {
      "address": 60312,
      "count": 1,
      "name": "Forced charging / discharging target state of charge",
      "data_type": "UInt16",
      "units": "%",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Target state of charge used when the mode register 60311 is 0. The source writes its configured minimum or maximum state of charge here (defaults 10 and 100, in percent) before starting a forced discharge or charge."
    },
    {
      "address": 60318,
      "count": 2,
      "name": "Maximum charging power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0xFFFFFFFF means no limit and 0 blocks charging, which is what the cited source writes in its hold-charge case. The source sets this register only on firmware 01.01.00.28.15 and later."
    },
    {
      "address": 60320,
      "count": 2,
      "name": "Maximum discharging power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "0xFFFFFFFF means no limit; 0 blocks discharging. The cited source sets this register only on firmware 01.01.00.28.15 and later."
    },
    {
      "address": 60322,
      "count": 2,
      "name": "Maximum PV power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Curtailment limit for the PV input in W: 0xFFFFFFFF means no limit, otherwise the source writes the permitted PV power. The source writes it only on firmware 01.01.00.28.15 and later."
    },
    {
      "address": 60326,
      "count": 2,
      "name": "Maximum grid import power",
      "data_type": "UInt32",
      "units": "W",
      "scale_factor": 1,
      "offset": 0,
      "access": "RW",
      "description": "Import limit at the grid connection point; 0xFFFFFFFF means no limit and 0 blocks import. The cited source writes it only on firmware 01.01.00.28.15 and later."
    }
  ],
  "combined_registers": [],
  "notes": "Register map from evcc's Atmoce template, templates/definition/meter/atmoce.yaml, pinned at evcc commit ebc78641c7017de55fc8dac2b0db6c0285771424 (2026-11-21), retrieved 2026-11-23. It is a community map (secondary), not an Atmoce document: no vendor register document is public and Atmoce's site serves product pages only. What the template itself states is carried into the notes and descriptions: the MG100 M-gateway ships with the MC100 and MC100-T; the installer must enable Modbus TCP in the gateway configuration or the Atmozen app, available from firmware 01.01.00.18.10; the app's grid-recharging and export-power functions must be enabled before the battery will charge from or discharge to the grid; firmware 01.01.00.28.15 or later is needed for hold-charge and hold-discharge, dimming and curtailment, older firmware supporting a hold-discharge only - which is why the four power-limit registers are described as gated by that version. Unit ID 1 is the template's own id; port 502 is evcc's default for a tcpip Modbus device and is not printed there, so it is a declared convention. Addresses are zero-based because evcc passes the template's register number straight into the PDU (plugin/modbus.go hands op.Addr to ReadHoldingRegisters and WriteMultipleRegisters unchanged), and the template's block comments count from the printed number. 32-bit values are decoded by evcc as big-endian words (its decoder packs the payload with binary.BigEndian and no template option changes the word order), hence HighFirst - the decoder's convention, not a printed frame. Left out on purpose: the five cumulative energy counters at 60160, 60166, 60172, 60178 and 60184 are 64-bit integers, which this schema cannot express, so there are no lifetime energy rows; and the 75 % charging ceiling the template derives from the rated power is a derivation of two sourced values, so it is described in that row rather than seeded."
}